IEC 60909 vs ANSI/IEEE C37: Two Methods for Short-Circuit Calculation Compared
Side-by-side comparison of IEC 60909 and ANSI/IEEE C37 short-circuit calculation methods. Same 11kV fault scenario calculated both ways — showing where results diverge and why it matters for equipment specification.
If you calculate the short-circuit current at an 11 kV bus using IEC 60909 and then recalculate the same bus using ANSI/IEEE C37, you will get different numbers. Not wildly different — typically 5-15% — but enough to change equipment ratings, protection settings, and project costs.
These are not competing methods trying to solve different problems. They are two parallel methodologies developed by different standards bodies to answer the same question: what is the maximum fault current that can flow at a given point in a power system? The differences arise from how each method handles pre-fault voltage, impedance corrections, motor contributions, and DC offset decay.
Understanding these differences is essential for any engineer who works on international projects, or who needs to reconcile calculations from different software packages that may use different methodologies without making it obvious.
The Fundamental Methodological Difference
Both methods use Thevenin's theorem to reduce the power system to an equivalent voltage source behind an equivalent impedance at the fault point. The fault current is then V/Z. But they differ in how they define V and how they modify Z.
IEC 60909-0: Voltage Factor Approach
IEC 60909 does not use the actual pre-fault voltage at the fault point. Instead, it applies a voltage factor c to the nominal voltage:
Equivalent voltage source = c x Un / sqrt(3)
IEC 60909-0, Clause 5, Table 1 — Voltage factor c| Nominal Voltage | c_max (maximum fault current) | c_min (minimum fault current) |
|---|---|---|
| LV (100-1000V) | 1.05 | 0.95 |
| MV/HV (>1kV) | 1.10 | 1.00 |
The voltage factor accounts for voltage variations, transformer tap positions, and the subtransient behaviour of generators and motors — all in a single multiplier. This simplifies the calculation because you do not need to know the actual operating voltage; you apply the factor to the nominal voltage and get a conservative result.
ANSI/IEEE C37: Pre-Fault Voltage Approach
The ANSI/IEEE C37 method uses the actual pre-fault voltage at the fault point (or an assumed pre-fault voltage, typically 1.0 per unit of the bus nominal voltage). There is no voltage factor equivalent.
Instead, ANSI/IEEE C37 applies impedance multiplying factors to different types of machines (generators, synchronous motors, induction motors) to account for how their contribution changes over time. The calculation is performed at three distinct time intervals:
- First-cycle (momentary): 0-0.5 cycles — maximum asymmetrical current for bus bracing and instantaneous relay settings
- Interrupting (contact parting): 1.5-4 cycles — symmetrical current at the time circuit breaker contacts part
- Time-delayed (30 cycles): steady-state — for coordination of time-delayed relays
Key Differences: Point by Point
1. Motor Contribution Handling
This is the largest source of divergence between the two methods.
IEC 60909 treats motors as voltage sources behind their subtransient reactance. Induction motors contribute to the initial symmetrical short-circuit current Ik" with a ratio based on their locked-rotor current:
- Large motors (per unit power > 100 kW): included individually
- Small motors: may be combined as an equivalent motor
- Motor contribution decays rapidly — IEC 60909 accounts for this with the factors mu and q
ANSI/IEEE C37 separates motor contributions by type and applies different multiplying factors at each time interval:
| Motor Type | First-Cycle X" Multiplier | Interrupting X" Multiplier | 30-Cycle Multiplier |
|---|---|---|---|
| Synchronous motors | 1.0 x X"d | 1.0 x X"d | 1.0 x X'd |
| Large induction (>750 kW) | 1.0 x X" | 1.5 x X" | Neglected |
| Medium induction (185-750 kW) | 1.0 x X" | 3.0 x X" | Neglected |
| Small induction (under 185 kW) | 1.2 x X" | Neglected | Neglected |
The ANSI method increases the effective impedance (reduces contribution) of motors at the interrupting time because motor contribution decays significantly by the time breaker contacts part. IEC 60909 handles this decay through the breaking current factor mu.
2. DC Component Treatment
Both methods recognise that the DC offset in the fault current depends on the X/R ratio at the fault point, but they handle it differently.
IEC 60909 calculates the peak short-circuit current ip as:
ip = kappa x sqrt(2) x Ik"
where kappa is a function of R/X ratio (IEC 60909-0, Clause 8.1). For a typical industrial system with X/R = 15, kappa is approximately 1.8, giving a peak factor of approximately 2.55.
ANSI/IEEE C37 calculates the asymmetrical current using a multiplying factor based on X/R ratio applied to the symmetrical (RMS) current. The first-cycle asymmetrical current is used for bus bracing and momentary ratings. For X/R = 15, the asymmetry multiplying factor is approximately 1.55 (applied to RMS symmetrical).
IEC 60909-0, Clause 8.1, Figure 9 — Factor kappa for peak short-circuit current3. Impedance Correction Factors
IEC 60909 applies correction factors to transformer and generator impedances to account for operating conditions:
- Transformer correction factor KT = 0.95 x c_max / (1 + 0.6 x xT) where xT is transformer reactance in p.u.
- Generator correction factor KG accounts for subtransient reactance and voltage regulation
ANSI/IEEE C37 does not apply these correction factors. Transformer impedances are used at their nameplate values. The pre-fault voltage assumption and the machine multiplying factors are considered sufficient to cover the same variability.
Worked Example: Same System, Both Methods
System: 11 kV bus, supplied by a 40 MVA, 33/11 kV transformer (Z = 10%), grid fault level 500 MVA at 33 kV. Motor load: 5 MW of induction motors (average X" = 0.17 p.u.).
Base Values
- Base MVA: 40 MVA
- Base voltage: 11 kV
- Base impedance: 11^2 / 40 = 3.025 ohms
- Base current: 40 / (sqrt(3) x 11) = 2.099 kA
Grid Contribution (Both Methods)
Grid impedance at 11 kV: Z_grid = (11^2 / 500) = 0.242 ohms = 0.080 p.u.
Transformer impedance: Z_T = 0.10 p.u.
Total source impedance: Z_source = 0.080 + 0.10 = 0.180 p.u.
Motor Contribution
Motor MVA (at X" = 0.17): S_motor = 5 / 0.85 = 5.88 MVA (assuming 0.85 pf)
Motor impedance: Z_motor = 0.17 x (40/5.88) = 1.156 p.u.
IEC 60909 Result
Voltage factor c_max = 1.10
Ik" (source) = (1.10 x 1.0) / 0.180 = 6.11 p.u. = 12.83 kA
Apply transformer correction factor: KT = 0.95 x 1.10 / (1 + 0.6 x 0.10) = 0.985
Corrected source impedance: 0.180 x 0.985 = 0.177 p.u.
Ik" (source, corrected) = 1.10 / 0.177 = 6.21 p.u. = 13.04 kA
Ik" (motors) = 1.10 / 1.156 = 0.951 p.u. = 2.00 kA
Total Ik" = 13.04 + 2.00 = 15.04 kA
ANSI/IEEE C37 Result (First-Cycle)
Pre-fault voltage: 1.0 p.u.
I_sym (source) = 1.0 / 0.180 = 5.56 p.u. = 11.67 kA
I_sym (motors) = 1.0 / 1.156 = 0.865 p.u. = 1.82 kA
Total first-cycle symmetrical = 11.67 + 1.82 = 13.49 kA
ANSI/IEEE C37 Result (Interrupting, 5-Cycle Breaker)
Motor impedance multiplied by 1.5 for large induction motors:
I_sym (motors, interrupting) = 1.0 / (1.156 x 1.5) = 0.577 p.u. = 1.21 kA
Total interrupting symmetrical = 11.67 + 1.21 = 12.88 kA
Results Comparison
| Parameter | IEC 60909 | ANSI First-Cycle | ANSI Interrupting |
|---|---|---|---|
| Source contribution | 13.04 kA | 11.67 kA | 11.67 kA |
| Motor contribution | 2.00 kA | 1.82 kA | 1.21 kA |
| Total symmetrical | 15.04 kA | 13.49 kA | 12.88 kA |
| Difference from IEC | — | -10.3% | -14.4% |
The 10% Gap Matters
The IEC 60909 result is 10-14% higher than the ANSI result for the same system. This is primarily due to the voltage factor c = 1.10 in the IEC method. If you specify switchgear based on IEC calculations and the manufacturer rates their equipment to ANSI standards (or vice versa), you may either over-specify (wasting money) or under-specify (creating a safety risk). Always confirm which standard the equipment rating is based on.
Why the Results Diverge
The differences are not errors — they are deliberate design choices by each standards body:
-
Voltage factor vs actual voltage: IEC 60909's c = 1.10 adds a 10% margin to account for voltage variations and tap positions. ANSI assumes 1.0 p.u. pre-fault voltage. This single factor accounts for most of the difference.
-
Transformer correction: IEC 60909 slightly reduces transformer impedance (KT < 1.0), which increases fault current. ANSI uses nameplate impedance without correction.
-
Motor treatment: IEC 60909 applies the voltage factor to motor contributions, increasing them. ANSI increases motor impedance at the interrupting time, decreasing them.
-
Philosophy: IEC 60909 aims for a single conservative value (Ik") that covers worst-case conditions. ANSI provides multiple values at different time points, allowing more precise equipment selection.
When to Use Each Method
Use IEC 60909 When:
- The project is in any country outside North America
- Equipment is rated to IEC standards (IEC 62271, IEC 60947)
- The client specification calls for IEC calculations
- You need a single conservative value for equipment specification
- International projects with multiple stakeholders
Use ANSI/IEEE C37 When:
- The project is in the United States, Canada, or countries that adopt ANSI standards
- Equipment is rated to ANSI/IEEE standards (IEEE C37 series)
- The client or utility requires ANSI-basis calculations
- You need time-separated values (first-cycle, interrupting, 30-cycle)
- The project involves US-manufactured switchgear
Mixed Standards Projects
On international mining projects, it is common to have IEC-rated switchgear with ANSI-rated motors, or vice versa. In these cases, perform the calculation using the standard that matches the switchgear rating basis. If the 11 kV switchgear is rated to IEC 62271-200, calculate to IEC 60909. If the switchgear is ANSI-rated, calculate to ANSI/IEEE C37. Never mix methodologies within a single calculation.
Practical Recommendations
-
State your basis: every short-circuit study report should clearly state which standard was used for the calculation and which standard the equipment ratings are based on.
-
Do not convert between methods: multiplying an ANSI first-cycle result by 1.1 does not give you an IEC 60909 result. The methodologies are too different for simple conversion factors.
-
Software transparency: when using calculation software, verify which method it implements. Some packages default to IEC 60909, others to ANSI. Some allow selection but do not clearly indicate which is active.
-
Motor contribution sensitivity: for industrial plants with large motor loads (>30% of total fault contribution), the difference between methods can exceed 15%. Pay particular attention to motor modelling in these cases.
The calculation method is not a preference — it is determined by the project location, the equipment standards, and the client specification. Know which one you are using, and make sure everyone on the project team knows too.
Try the Short Circuit Calculator
Free online tool — no signup required

Lead Electrical & Instrumentation Engineer
18+ years of experience in electrical engineering at large-scale mining operations. Specializing in power systems design, cable sizing, and protection coordination across BS 7671, IEC 60364, NEC, and AS/NZS standards.
Related Articles
IEC 60909 Short-Circuit Calculation: Step-by-Step Walkthrough
Complete IEC 60909-0 short-circuit calculation walkthrough. 11kV/415V transformer, 30m cable, every impedance correction factor. Free calculator included.
Short Circuit Calculations: The 3 Numbers Every Engineer Must Know Before Specifying a Switchboard
Engineers specify switchboards without knowing the prospective fault current. If a 25kA-rated board sees 35kA, bus bars weld together. Here are the 3 numbers you MUST calculate first.
Short Circuit Ratings: The Cable Nobody Checks (Until It Fails)
Most engineers size cables for ampacity and voltage drop. The adiabatic equation (k²S² ≥ I²t) is often forgotten. Here's a real scenario where a properly-sized 4mm² cable fails at 16kA — and how to check yours.