Protection Coordination Calculator
Verify upstream/downstream device discrimination with time-current characteristic analysis.
Configure devices and click Calculate to see protection coordination analysis.
Export Professional Reports
Save your protection coordination calculator results as branded PDF, Excel, or Word reports with full standard references and clause numbers.
Discrimination, also called selectivity, is the coordination between series-connected protective devices so that only the device nearest the fault operates, leaving upstream circuits unaffected. IEC 60947-2 Annex A defines methods for verifying full and partial discrimination using time-current characteristic curves and manufacturers' selectivity tables for circuit breaker combinations.
How to Select a Circuit Protection Device
- 1Determine the design current — Calculate the design current Ib of the circuit from the connected load. For motor circuits, use the full-load current from the motor nameplate and consider starting current requirements.[IEC 60364-4-43 Clause 433.1]
- 2Select nominal device rating — Choose a protective device with nominal rating In where In is greater than or equal to Ib, and In is less than or equal to the cable's current-carrying capacity Iz after derating.[IEC 60364-4-43 Clause 433.1]
- 3Verify breaking capacity — Ensure the device's rated breaking capacity Icu exceeds the prospective short-circuit current at the installation point. The device must safely interrupt the maximum fault current.[IEC 60947-2 Clause 2]
- 4Check disconnection time — Verify the device disconnects the supply within the required time for the circuit type: 0.4 seconds for 230V final circuits or 5 seconds for distribution circuits, using the earth fault loop impedance.[BS 7671 Regulation 411.3.2]
- 5Verify cable thermal protection — Confirm the device's let-through energy I2t does not exceed the cable's adiabatic withstand capacity k2S2. This ensures the cable survives a short circuit without insulation damage.[IEC 60364-4-43 Clause 434.5]
- 6Check upstream discrimination — Verify discrimination with the upstream device using time-current curves or the manufacturer's selectivity tables. Full discrimination ensures only the device nearest the fault operates.[IEC 60947-2 Annex A]
How Protection Coordination Works
The protection coordination calculator verifies that upstream and downstream protective devices operate in the correct sequence during fault conditions, ensuring selectivity (discrimination) throughout the installation.
The calculator plots time-current characteristic (TCC) curves for circuit breakers and fuses using manufacturer data and standard trip curves (B, C, D per IEC 60898-1, or Type 1/2/3 per NEC). It checks that the downstream device trips before the upstream device across the full range of prospective fault currents. Per IEC 60947-2, selectivity is confirmed when the downstream device clears the fault within its breaking capacity while the upstream device remains closed.
BS 7671 Chapter 43 requires that protective devices disconnect the supply within the time limits of Regulation 411.3.2. Cable I2t withstand (adiabatic limit) is overlaid to verify conductor protection. Results include TCC coordination plots, selectivity assessment, cable damage curves, and recommended device settings.
MCB Instantaneous Trip Ranges (IEC 60898-1)
| Type | Trip Range (× In) | Application | Reference |
|---|---|---|---|
| Type B | 3–5× | Resistive loads, lighting, long cables | IEC 60898-1 Clause 8.6 |
| Type C | 5–10× | Moderate inductive loads, small motors | IEC 60898-1 Clause 8.6 |
| Type D | 10–20× | High inrush loads, transformers, motors | IEC 60898-1 Clause 8.6 |
Source: IEC 60898-1 Clause 8.6.1
Frequently Asked Questions
What is protection coordination and why is it important?
How do you achieve time-based discrimination between circuit breakers?
What is current-based discrimination and when is it used?
How do I check discrimination between a fuse and a circuit breaker?
What is the cable damage curve and how does it relate to protection?
What are the maximum disconnection times required by BS 7671?
Why does a Type B MCB sometimes fail to discriminate with a Type C MCB upstream, even when the upstream device is rated at double the current?
What is cascading (back-up protection) under IEC 60947-2, and why does it allow apparently underrated downstream devices?
How does the let-through energy (I2t) of a fuse or MCB interact with the cable's thermal withstand, and why is checking only the trip time insufficient?
Why does zone-selective interlocking (ZSI) dramatically improve both protection coordination and arc flash results?
What is the cross-over point problem in fuse-MCB coordination, and why does every protection engineer need to check it manually?
Related Calculators
Related Guides & Examples
Key Terms
Related FAQ
Standards Reference
- IEC 60947-2 — Circuit breakers
- BS 7671:2018+A2 — Chapter 43
- IEC 60269 — Fuses