Skip to main content
All Comparisons
COMPARISON

Short Circuit Withstand: The Distribution Board Feeder — k=115 vs k=143

A 50mm² cable, 10kA fault, 0.4s clearing time. BS 7671 and IEC say FAIL with k=115 while AS/NZS says PASS with k=143. Understanding why could save your design.

KholisFebruary 27, 202610 min read

The adiabatic equation is one of the most critical checks in electrical design. If a cable cannot withstand the prospective fault current for the time it takes the protective device to clear, the cable can be permanently damaged — or worse, catch fire. And here is where the standards diverge dramatically: the same cable, same fault, same clearing time can PASS under one standard and FAIL under another.

The Scenario

A sub-distribution board feeder in a commercial building:

  • Cable: 50mm² copper, PVC insulated (single-core)
  • Prospective fault current: 10kA at the cable origin
  • Protective device clearing time: 0.4 seconds
  • Initial conductor temperature: 70°C (operating temperature for PVC)
  • Final conductor temperature limit: varies by standard

The Adiabatic Equation

All four standards use the same fundamental equation:

Adiabatic Equation

I²t ≤ k²S²

Where:

  • I = prospective fault current (A)
  • t = protective device clearing time (s)
  • k = cable constant depending on insulation and conductor material
  • S = cable cross-sectional area (mm²)

The energy let-through (I²t) must not exceed the cable's withstand capacity (k²S²). The critical variable is k — and this is where the standards disagree.

Side-by-Side Results

Scenario

50mm² Cu PVC cable, 10kA fault, 0.4s clearing time

ParameterAS/NZSBS 7671IEC 60364NEC
k-factor (Cu/PVC)
k = 14370°C → 160°CAS/NZS 3008.1.1, Table 52k = 11570°C → 160°CBS 7671, Table 43.1k = 11570°C → 160°CIEC 60364-4-43, Table 43AVariesICEA P-32-382 methodNEC 110.10, 240.4
Cable withstand (k²S²)
51.1 × 10⁶ A²s(143 × 50)² = 51.1M33.1 × 10⁶ A²s(115 × 50)² = 33.1M33.1 × 10⁶ A²s(115 × 50)² = 33.1MN/ADifferent methodology
Fault energy (I²t)
40.0 × 10⁶ A²s10,000² × 0.440.0 × 10⁶ A²s10,000² × 0.440.0 × 10⁶ A²s10,000² × 0.440.0 × 10⁶ A²s10,000² × 0.4
Result: I²t ≤ k²S²?
PASS ✓40.0M < 51.1M (78%)FAIL ✗40.0M > 33.1M (121%)FAIL ✗40.0M > 33.1M (121%)DependsOn protective device I²t
Minimum cable to pass
50mm²Current size adequate70mm²k²S² = 64.8M > 40M ✓70mm²k²S² = 64.8M > 40M ✓Verify device I²tCable must exceed device let-through
Most conservative: BS 7671 / IEC 60364 (lower k-factor requires 70mm² vs 50mm²)
Run this comparison yourself
Standards agreeModerate differenceSignificant difference

Why k = 115 vs k = 143?

This is one of the most debated differences between the Australian and international standards. The k-factor is derived from the heat capacity of the conductor-insulation system:

k-Factor Derivation

k = √(Qc × (β + 20) / ρ₂₀ × ln((β + θf) / (β + θi)))

Where Qc is the volumetric heat capacity, β is the reciprocal of the temperature coefficient of resistance, ρ₂₀ is the resistivity at 20°C, θi is the initial temperature, and θf is the final temperature.

The Temperature Assumptions

Both standards use the same temperature range (70°C to 160°C for PVC) but differ in other parameters:

ParameterAS/NZS 3008BS 7671 / IEC
Initial temperature70°C70°C
Final temperature160°C160°C
Resistivity modelDifferent coefficientsIEC coefficients
Heat capacityHigher valueIEC standard value
Resulting k143115

AS/NZS 3008 uses material property data that yields a higher k-factor. The Australian standard committee has historically argued that the IEC values are overly conservative, while the IEC committee maintains that their values include a safety margin for real-world conductor quality variations.

24% Difference in Withstand Capacity

The k-factor difference is not trivial. k=143 gives a withstand capacity of 51.1 MA²s for a 50mm² cable. k=115 gives 33.1 MA²s. That is a 54% difference in calculated thermal withstand — the AS/NZS cable can theoretically absorb 54% more fault energy before exceeding its temperature limit.

The NEC Approach

NEC doesn't prescribe a simple k-factor table. Instead:

  1. The cable manufacturer provides I²t withstand data per ICEA P-32-382
  2. The protective device manufacturer provides I²t let-through data
  3. The designer verifies that device I²t < cable I²t

This shifts responsibility to the device-cable combination rather than a universal equation. In practice, UL-listed combinations are pre-verified, which is why NEC engineers rarely perform manual adiabatic calculations.

The Real-World Impact

For Engineers Working Across Standards

If you design a cable installation to AS/NZS 3008 and it passes the adiabatic check at 50mm², that same design would fail under BS 7671 or IEC 60364. This has real consequences for:

  • Australian firms bidding on Middle East projects (IEC 60364 applies)
  • UK firms designing for Australian mining (AS/NZS 3008 applies)
  • Any project with multiple jurisdictional requirements

What Happens When It Fails?

A cable that exceeds its I²t rating during a fault will:

  1. PVC insulation reaches above 160°C — the insulation softens and may melt
  2. Conductor resistance increases with temperature, generating more heat
  3. If the fault persists, the insulation ignites
  4. Adjacent cables in the same tray or conduit are also affected

Not Just the Cable at Risk

A cable that fails the adiabatic check at 50mm² won't necessarily fail catastrophically during a single fault. But it will be thermally degraded. Repeated faults (which happen in industrial installations) will progressively damage the insulation until a ground fault develops.

Solutions When BS/IEC Says FAIL

When your design passes under AS/NZS but fails under BS/IEC, you have several options:

  1. Increase cable size — the most straightforward solution (50mm² → 70mm²)
  2. Reduce clearing time — a faster protective device (0.4s → 0.2s reduces I²t by 50%)
  3. Current-limiting devices — MCCBs and fuses that limit the actual I²t below the prospective value
  4. Reduce fault level — impedance of the upstream transformer limits the prospective fault current

The most cost-effective approach is usually a current-limiting fuse or MCCB, which can reduce the actual I²t let-through to well below the cable withstand — regardless of which k-factor you use.

Key Takeaways

  1. k=143 (AS/NZS) vs k=115 (BS/IEC) is a 24% difference in the k-factor and 54% in withstand capacity
  2. Same cable, same fault, opposite results — 50mm² passes AS/NZS but fails BS/IEC at 10kA/0.4s
  3. BS 7671 and IEC 60364 require 70mm² where AS/NZS 3008 allows 50mm²
  4. NEC uses a different methodology — device-cable I²t matching instead of universal k-factors
  5. Always design to the applicable standard — using k=143 on a BS 7671 project is a compliance violation

Try the Short Circuit Calculator

Free online tool — no signup required

Open Calculator
Kholis

Kholis

Lead Electrical & Instrumentation Engineer

18+ years of experience in electrical engineering at large-scale mining operations. Specializing in power systems design, cable sizing, and protection coordination across BS 7671, IEC 60364, NEC, and AS/NZS standards.

18+ years electrical engineering experienceLead E&I Engineer at major mining operationECalPro founder & developer