Skip to main content

MCB Tripping Curves Pocket Card — B, C, D Curves Reference

Instant reference card for MCB tripping curves (B, C, D types). Shows magnetic & thermal trip thresholds per IEC 60898. Free printable PDF.

Multi-Standard4 min readUpdated March 3, 2026
Share:

Credit-card size (85.6 × 54 mm), double-sided, 250–300 gsm coated cardstock, gloss or matte lamination both sides. CMYK colour mode. QR code minimum 12 × 12 mm linking to ecalpro.com/calc/protection.

ParameterValue
Dimensions85.6 mm × 54 mm (ISO/IEC 7810 ID-1)
Bleed3 mm all sides (final trim: 91.6 × 60 mm)
Safe zone3 mm inside trim (content area: 79.6 × 48 mm)
Stock250–300 gsm coated cardstock

Front — Magnetic Trip Ranges & Visual Curve Comparison

Simplified Trip Curve Description

The trip curve is a log-log chart with current (as multiple of In) on the X-axis and trip time on the Y-axis. All MCB types share the same thermal region:

  • At 1.13 × In: Must NOT trip within 1 hour (cold start)
  • At 1.45 × In: MUST trip within 1 hour (cold start)

The magnetic trip bands are the key differentiator between types:

  • Type B (green band): Instantaneous trip between 3× and 5× In
  • Type C (amber band): Instantaneous trip between 5× and 10× In
  • Type D (red band): Instantaneous trip between 10× and 20× In

Magnetic Trip Range Summary

TypeMagnetic Trip RangeGuaranteed Trip
B3× In to 5× InMust trip at 5× In
C5× In to 10× InMust trip at 10× In
D10× In to 20× InMust trip at 20× In

Worked Example

Example: 32 A Type B MCB

  • Magnetic trip range: 96 A to 160 A
  • Guaranteed instant trip: 160 A (5 × 32 A)
  • Below 96 A: thermal trip only (slower)

Back — Application Guide, I2t Let-Through & Selection Matrix

Application Selection Guide

TypeDesigned ForTypical ApplicationsInrush Tolerance
BResistive and lightly inductive loadsLighting circuits, socket outlets, electric heating, residential generalLow (3–5×)
CModerate inductive loadsSmall motors, fluorescent lighting with EM ballasts, IT equipment, commercial generalMedium (5–10×)
DHeavy inductive loadsLarge motors, transformers, welding equipment, X-ray machines, compressorsHigh (10–20×)

Practical Decision Flowchart

Is the load purely resistive (heaters, incandescent)?
  YES --> Type B

Does the load have moderate inrush (< 10×)?
  (small motors, IT, fluorescent)
  YES --> Type C

Does the load have high inrush (> 10×)?
  (large DOL motors, transformers, welding)
  YES --> Type D

I²t Energy Let-Through Comparison

Reference: IEC 60898-1, Table 11 & 12

Key Insight: A Type D MCB lets through 2–3× MORE energy (I²t) than a Type B during a short circuit. PPE selection should consider MCB type, not just prospective fault current.
Rating (In)Type B I²t (kA²s)Type C I²t (kA²s)Type D I²t (kA²s)
6 A4,5009,00018,000
10 A8,00015,00030,000
16 A18,00030,00055,000
20 A25,00042,00075,000
25 A35,00055,000100,000
32 A50,00075,000140,000
40 A72,000100,000190,000
50 A100,000140,000260,000
63 A140,000190,000350,000

Values are maximum I²t let-through at 6 kA prospective fault current, energy limiting class 3. Actual values vary by manufacturer — always check datasheets.

Peak Let-Through Current (Ip) Comparison

Prospective IscType B Ip (kA)Type C Ip (kA)Type D Ip (kA)
3 kA3.54.56.0
6 kA5.57.010.0
10 kA7.510.015.0

Values are typical for energy limiting class 3 MCBs per IEC 60898-1.

Additional MCB Types (Less Common)

TypeMagnetic RangeRegion / Standard
A2×–3× InNot in IEC 60898 (some European)
K8×–12× InMotor protection (IEC 60947-2)
Z2×–3× InSensitive electronics (IEC 60947-2)
MANo thermal, magnetic onlyMotor short-circuit protection

Data Source References

DataSource
Type B/C/D magnetic rangesIEC 60898-1:2015+A1:2019, Section 8.6.1, Table 3
Thermal trip characteristicsIEC 60898-1:2015, Section 8.6.1, Table 2 (1.13×/1.45× thresholds)
I²t let-through valuesIEC 60898-1:2015, Section 8.6.5, Tables 11–12; typical manufacturer data (ABB S200, Schneider iC60)
Peak let-through currentIEC 60898-1:2015, Section 8.6.5; manufacturer selection guides
Application guidanceBS 7671:2018 Appendix 3; IEC 60364-4-43; Schneider Electrical Installation Guide
Type K/Z/MAIEC 60947-2:2016, Annex K; circuit breaker application guides
NEC equivalentUL 489: Types rated by AIR (ampere interrupting rating) rather than B/C/D curves
Energy limiting classesIEC 60898-1:2015, Section 3.5.8 (Class 1, 2, 3)

Try the Protection Coordination Calculator

Put this methodology into practice. Calculate results with full standard clause references — free, no sign-up required.

Or embed this calculator on your site
Calculate Protection Coordination

Frequently Asked Questions

Type B trips at 3-5 times rated current (resistive loads), Type C at 5-10 times (motor/transformer inrush), and Type D at 10-20 times (high inrush like welding machines). All per IEC 60898-1.
Type B is standard for socket outlets and lighting circuits in most jurisdictions. Type C is used when circuits supply small motors or fluorescent lighting with high inrush.
Yes. Download the PDF, print double-sided on card stock, and cut to credit-card size (85 x 54mm). Laminate for durability. Free to distribute to your team.

Related Resources