Cable Sizing Calculator per SS 638:2018 (IEC 60364 / BS 7671) for Singapore
Cable sizing in Singapore follows SS 638:2018, the Singapore Standard for electrical installations based on both IEC 60364 and BS 7671. Engineers select cables using current-carrying capacity tables, apply tropical ambient derating (35-40 °C), comply with SP Group (utility) connection requirements, and verify voltage drop at 230/400 V, 50 Hz supply.
Quick Reference Table
| Singapore Cable Sizing Key References — SS 638 — SS 638:2018 (IEC 60364 / BS 7671) (2018 Edition) | ||
|---|---|---|
| Parameter | Value / Requirement | Clause Reference |
| National standard | SS 638:2018 — Code of Practice for Electrical Installations | SS 638:2018, Clause 1 |
| Supply voltage | 230 V single-phase / 400 V three-phase | SS 638:2018, Clause 132 |
| Frequency | 50 Hz (SP Group) | SS 638:2018, Clause 132 |
| Current-carrying capacity | Tables derived from IEC 60364-5-52 and BS 7671 | SS 638:2018, Appendix 4 |
| Design ambient temperature | 35-40 °C (tropical climate, year-round) | SS 638:2018, Table 4B1 |
| Voltage drop limits | 4% from the origin of the installation | SS 638:2018, Clause 525 |
| Utility requirements | SP Group connection standards and metering requirements | SP Group Technical Requirements |
| Common conductor sizes | 1.5, 2.5, 4, 6, 10, 16, 25, 35 mm² | SS 638:2018, Table 4D1A |
How to Calculate Cable Sizing for Singapore
- 1
Determine load per SS 638
Calculate design current per SS 638 maximum demand rules. For HDB flats, typical connections are 40-63 A single-phase. For condominiums and commercial, use assessed load with diversity per SS 638 Appendix A.
- 2
Select cable type for tropical conditions
Choose XLPE-insulated cables where possible — the 90 °C rating provides better margin in Singapore's 35-40 °C ambient. PVC cables are used for lighting and smaller circuits.
- 3
Apply tropical ambient derating
Singapore's year-round 35-40 °C ambient requires derating from the 30 °C reference. At 40 °C, the factor is approximately 0.87 for PVC cables. Apply grouping factors from SS 638 Table 4C1 for circuits in shared trunking.
- 4
Select conductor size
Choose the minimum conductor size from SS 638 Appendix 4 tables with derated ampacity exceeding the design current. Cross-reference with SP Group minimum requirements for service cables.
- 5
Check voltage drop per SS 638
Verify total voltage drop from the origin of installation does not exceed 4% per SS 638 Clause 525. At 230 V: maximum 9.2 V. Singapore's compact urban environment helps limit cable run lengths.