Skip to main content
ProtectionAlso: selectivity, protective device coordination, cascade protection

Discrimination (Selectivity)

Discrimination, also called selectivity, is the coordination between series-connected protective devices so that only the device nearest the fault operates, leaving upstream circuits unaffected. IEC 60947-2 Annex A defines methods for verifying full and partial discrimination using time-current characteristic curves and manufacturers' selectivity tables for circuit breaker combinations.

Detailed Explanation

In a properly coordinated protection system, a fault on a final circuit should trip only the local circuit breaker, not the distribution board main switch or upstream devices. This selective operation — discrimination — prevents unnecessary supply interruption to healthy circuits. Full discrimination means the downstream device always operates first, regardless of fault current magnitude. Partial discrimination means selectivity is maintained up to a specified fault current level, above which both devices may trip. Engineers verify discrimination by comparing time-current curves: the downstream device curve must lie entirely below and to the left of the upstream device curve across all relevant fault current levels. Manufacturers publish selectivity tables showing verified combinations. Achieving discrimination becomes more challenging at high fault levels where circuit breakers operate in their instantaneous region. Solutions include using time-delayed upstream devices, selecting devices with energy-limiting characteristics, or using zone-selective interlocking. Poor discrimination results in widespread blackouts from a single local fault, which is unacceptable in hospitals, data centres, and industrial processes.

Standard References

StandardClause
IEC 60947-2Annex A
BS 7671:2018Regulation 536.4

Related Terms