Skip to main content

AS/NZS 3008 Table 13: Current Carrying Capacity

AS/NZS 3008 Table 13 explained — current-carrying capacity of multicore thermoplastic insulated cables. Column selection, common sizes from 1mm² to 400mm².

AS/NZS 300811 min readUpdated March 19, 2026
Share:

What Is AS/NZS 3008 Table 13?

Table 13 of AS/NZS 3008.1.1:2017 provides the current-carrying capacity (in amperes) for multicore cables with thermoplastic and thermosetting insulation. It is the primary table used for sizing multicore cables in Australian and New Zealand electrical installations.

The table covers:

  • Conductor materials: Copper and aluminium
  • Insulation types: V-75 (75°C PVC), V-90 (90°C PVC), and X-90 (90°C XLPE)
  • Cable sizes: 1 mm² through 630 mm²
  • Installation methods: 29 configurations from Table 3, each mapped to a specific column in Table 13

All values are based on the AS/NZS 3008 reference conditions: 40°C ambient air temperature (higher than the 30°C used by BS 7671 and IEC 60364), single circuit, no contact with thermal insulation, and conductor loaded to its maximum operating temperature.

For single-core cables, use Table 14 instead. For flat thermoplastic sheathed cables (TPS), use Table 15.

Understanding Column Selection

Table 13 has multiple columns, each corresponding to specific installation methods from Table 3. Selecting the correct column is the critical first step:

ColumnInstallation MethodDescription
1–4In wiring enclosure, touchingCables in conduit/trunking touching the enclosure surface
5–8In wiring enclosure, spacedCables in larger conduit/trunking with air gaps
9Clipped directCable clipped to a wall or ceiling surface
10–12Unperforated cable traySolid-bottom cable tray (limited ventilation)
13–15Perforated cable trayVentilated tray (better heat dissipation)
16Suspended from catenaryCable hanging from support wire
17–19Free air, spaced from surfaceMaximum ventilation, highest ratings
20–23Buried direct in groundIn soil, uses ground temperature reference
24–29In underground ducts/conduitIn pipes below ground, most restricted
Common trap: Using the wrong column is the single most common error in AS/NZS 3008 cable sizing. Always start with Table 3 to identify the correct installation method code, then map to the correct column number in Table 13. A one-column error can overstate or understate the cable rating by 10–20%.

Reference Current Ratings — Copper V-90 Multicore

The following table shows current-carrying capacity for copper conductors with V-90 (90°C PVC) insulation in multicore configuration. Values are at the 40°C reference ambient:

Size (mm²)Col 6 — Conduit (A)Col 9 — Clipped (A)Col 13 — Perf Tray (A)Col 17 — Free Air (A)
112141517
1.515181922
2.521252630
427333540
636434550
1049596269
1666798393
2587104109122
35107128135151
50130157164184
70165200210237
95200243254289
120232281295337
150258318334382
185294362380436
240347427450519
300396489514596
400467572605700

Note: These values are for the 40°C reference ambient. At 30°C ambient (common in many countries), a derating factor greater than 1.0 applies — see Table 22 — effectively increasing the cable’s usable capacity.

V-75 vs V-90 vs X-90 Insulation

AS/NZS 3008 covers three main insulation types, each with different maximum conductor operating temperatures and therefore different current ratings:

DesignationMaterialMax TempRelative Rating
V-75PVC (thermoplastic)75°CBaseline
V-90PVC (thermoplastic, heat resistant)90°C+15–20% over V-75
X-90XLPE (cross-linked polyethylene)90°CSimilar to V-90

While V-90 and X-90 both have a 90°C maximum temperature, XLPE has superior short-circuit withstand performance and better ageing characteristics. In practice, V-90 is the most common insulation type for general commercial and industrial installations in Australia, while X-90 (XLPE) is preferred for power distribution cables and heavy industrial applications.

V-75 cables are less common in new installations but are still encountered in older existing work. When assessing existing cables, always check the insulation type marking to use the correct column in Table 13.

Table 13 vs Table 14 vs Table 15

AS/NZS 3008 provides three main current rating tables, each for a different cable configuration:

TableCable TypeWhen to Use
Table 13Multicore cables (2C, 3C, 4C)Most commercial and industrial circuits
Table 14Single-core cablesLarge power circuits, parallel runs, switchboard connections
Table 15Flat TPS (twin and earth, flat sheathed)Domestic wiring, light commercial

Single-core cables (Table 14) generally have higher current ratings than equivalent-sized multicore cables (Table 13) because single-core cables have less mutual heating between conductors. However, single-core cables require careful installation to avoid circulating currents in metallic enclosures.

Table 15 applies specifically to the flat thermoplastic sheathed (TPS) cables commonly used in Australian domestic wiring. These cables have unique flat construction and are typically clipped directly to timber framing inside walls and ceilings.

Practical Cable Selection Using Table 13

A worked example demonstrates how Table 13 is used in practice:

Design brief:
  Three-phase motor circuit, 45 A full-load current
  Multicore V-90 copper cable in perforated tray
  Ambient temperature: 45°C
  3 other circuits on the same tray

Step 1: Installation method → Table 3 = Column 13 (perforated tray)

Step 2: Derating factors
  Temperature: Table 22, 45°C for V-90 → Ct = 0.89
  Grouping: Table 25, 4 circuits on perf tray → Cg = 0.77
  Overall: 0.89 × 0.77 = 0.685

Step 3: Required tabulated rating
  It = 45 / 0.685 = 65.7 A

Step 4: Table 13, Column 13, V-90 copper
  6 mm² = 45 A  (too low)
  10 mm² = 62 A  (too low)
  16 mm² = 83 A  (65.7 ≤ 83 √)

Step 5: Verify voltage drop using Tables 30–42

Selected cable: 16 mm² 4-core V-90 copper

Try the Cable Sizing Calculator

Put this methodology into practice. Calculate results with full standard clause references — free, no sign-up required.

Or embed this calculator on your site
Calculate Cable Sizing

Frequently Asked Questions

AS/NZS 3008 uses 40°C as the reference ambient temperature because Australian climate conditions are significantly hotter than the UK or Europe. Many installations in Australia regularly experience ambient temperatures above 30°C, particularly in roof spaces, outdoor enclosures, and plant rooms. Using 40°C as the reference means the tabulated ratings already account for typical Australian conditions without requiring temperature derating in most situations.
Start with Table 3 in AS/NZS 3008, which lists 29 installation methods. Each method has a description (e.g., 'multicore cable enclosed in conduit fixed to a wall') and maps to a specific column number. Find the description that best matches your actual installation, note the column number, then use that column in Table 13. For example, conduit on a wall = Column 6, perforated tray = Column 13, free air = Column 17.
Table 13 is exclusively for multicore cables (2-core, 3-core, 4-core, etc.). For single-core cables (individual conductors installed separately), use Table 14. For flat TPS (twin and earth) cables used in domestic wiring, use Table 15. Using the wrong table can result in incorrect cable sizing — single-core ratings are typically higher than multicore for the same size.

Related Resources