Skip to main content
All Comparisons
COMPARISON

Cable Sizing: The 50m Office Feeder — AS/NZS vs BS 7671 vs IEC vs NEC

Same 100A three-phase load, same 50m cable run, four different standards. See exactly where AS/NZS 3008, BS 7671, IEC 60364, and NEC give different cable sizes — and why.

KholisFebruary 27, 202610 min read

Every electrical engineer has faced this question: which cable size does this circuit need? The answer depends entirely on which standard you design to. This article takes one scenario and runs it through all four major standards to show exactly where the results diverge and why.

The Scenario

A straightforward three-phase distribution circuit in a commercial office building:

  • Load: 100A three-phase balanced
  • Cable run: 50 metres
  • Installation: PVC/XLPE copper cables in surface-mounted conduit
  • Ambient temperature: 30°C (standard conditions)
  • Grouping: Single circuit (no grouping derating)
  • Voltage: 400V three-phase

This is about as simple as cable sizing gets — no exotic installation methods, no extreme temperatures, no grouped circuits. The differences you see here are purely from how each standard defines base current ratings and derating methodologies.

Side-by-Side Results

Scenario

100A three-phase, 50m, PVC copper, surface conduit, 30°C ambient

ParameterAS/NZSBS 7671IEC 60364NEC
Installation method designation
Method B2Enclosed in conduit on wallAS/NZS 3008.1.1, Table 3Reference Method BEnclosed in conduit on wallBS 7671, Table 4A2Reference Method BEnclosed in conduit on wallIEC 60364-5-52, Table B.52.1Table 310.16Raceway/conduitNEC 310.16
Base current rating (35mm²)
126APVC 75°C, 3-coreTable 13, Col 7110APVC 70°C, 3 or 4-coreTable 4D2A, Col 6110APVC 70°C, 3-coreTable B.52.4110A75°C column, #2 AWG ≈ 33.6mm²Table 310.16
Temperature correction (30°C)
1.0030°C is referenceTable 221.0030°C is referenceTable 4B11.0030°C is referenceTable B.52.141.0030°C is reference310.15(B)(1)
Minimum cable size selected
35mm²126A > 100A ✓Table 1335mm²110A > 100A ✓Table 4D2A35mm²110A > 100A ✓Table B.52.4#2 AWG (33.6mm²)115A at 75°C > 100A ✓Table 310.16
Voltage drop (%)
1.8%mV/A/m methodTable 301.9%mV/A/m methodTable 4Ab1.9%mV/A/m methodAnnex G1.7%Different R/X valuesNEC Ch.9, Table 9
Voltage drop limit
5%Total circuitAS/NZS 3000, 3.6.25%Total circuitTable 4Ab Note4%Total circuitIEC 60364-5-52, 5253% branch / 5% totalRecommended, not mandatoryNEC 210.19(A) Note
Most conservative: IEC 60364 (strictest voltage drop limit at 4%)
Run this comparison yourself
Standards agreeModerate differenceSignificant difference

Why the Numbers Differ

Conductor Temperature Rating

The single biggest difference is the assumed maximum conductor temperature:

  • AS/NZS 3008 uses 75°C as the standard rating for PVC cables — this gives higher base ampacities
  • BS 7671 and IEC 60364 use 70°C for PVC cables — 5°C lower means lower base ampacity
  • NEC offers both 60°C and 75°C columns in Table 310.16, with the termination temperature often governing (60°C for most connections)

The Temperature Rating Trap

An engineer moving from AS/NZS to BS 7671 will find that the "same" cable has a lower current rating. This is not an error — it reflects a more conservative thermal assumption in the BS/IEC framework. A 35mm² PVC cable rated at 126A under AS/NZS is only rated at 110A under BS 7671.

Installation Method Classification

All four standards classify installation methods into reference categories, but the boundaries differ:

  • AS/NZS has unique methods (e.g., Method V — cables on ventilated trays) not found in BS/IEC
  • BS 7671 follows IEC closely but adds UK-specific methods (e.g., Method 100 for thermally insulating walls)
  • NEC uses a fundamentally different table structure — one large table (310.16) covers most raceway and cable installations

Voltage Drop Methodology

While all four standards use similar physics (I × Z × L), the impedance values in their lookup tables differ because they are derived from different national cable manufacturing standards and testing conditions.

Voltage Drop (All Standards)

Vd = (mV/A/m) × I_b × L / 1000

The mV/A/m values differ between standards because:

  1. AS/NZS uses Australian cable manufacturing data (based on AS/NZS 1125)
  2. BS 7671 uses UK cable data (based on BS 6004/BS 5467)
  3. NEC Chapter 9 Table 9 uses American conductor dimensions (AWG system)

AWG vs Metric Sizing

NEC uses the American Wire Gauge system. The nearest AWG equivalent to 35mm² is #2 AWG (33.6mm²), which is slightly smaller. This means:

  • At 75°C: #2 AWG is rated at 115A — adequate for 100A
  • At 60°C: #2 AWG is rated at 95A — not adequate, requiring #1 AWG (42.4mm²)

The termination temperature rating (not the cable insulation rating) often controls the NEC result.

Practical Guidance

For this scenario, all four standards agree on 35mm² (or the AWG equivalent). But this agreement breaks down quickly when you add:

  • Higher ambient temperature — AS/NZS becomes more permissive due to the 75°C base
  • Grouped circuits — grouping factor tables differ between standards
  • Longer cable runs — NEC's 3% branch circuit limit catches longer runs faster

Multi-Standard Projects

When designing for projects that must comply with multiple standards (e.g., an Australian firm designing for a Middle East project referencing IEC), always size to the most conservative standard applicable. In most cases, this means IEC 60364 for voltage drop and BS 7671 for current rating.

Key Takeaways

  1. Same scenario, same answer (this time) — all four standards select 35mm² for this simple case
  2. The margins differ — AS/NZS has 26% headroom (126A vs 100A), BS/IEC have only 10% (110A vs 100A)
  3. Voltage drop limits vary significantly — from 3% (NEC branch) to 5% (AS/NZS and BS 7671)
  4. AWG vs metric creates confusion — #2 AWG is close to but not exactly 35mm²
  5. Temperature rating is the root cause — 70°C vs 75°C PVC rating drives most of the ampacity difference

Try the Cable Sizing Calculator

Free online tool — no signup required

Open Calculator
Kholis

Kholis

Lead Electrical & Instrumentation Engineer

18+ years of experience in electrical engineering at large-scale mining operations. Specializing in power systems design, cable sizing, and protection coordination across BS 7671, IEC 60364, NEC, and AS/NZS standards.

18+ years electrical engineering experienceLead E&I Engineer at major mining operationECalPro founder & developer