IDMT Curve Reference Card — IEC 60255-151 Standard, Very Inverse, and Extremely Inverse
Free download · A4 landscape
Protection coordination relies on understanding IDMT (Inverse Definite Minimum Time) curves, yet many engineers have to look up the equations every time they set a relay. This A4 landscape reference card overlays all three IEC 60255-151 IDMT curve types — Standard Inverse (SI), Very Inverse (VI), and Extremely Inverse (EI) — on a single log-log time-current graph so you can visually compare their characteristics at any current multiple. Alongside the graph, each curve's time equation is presented in full: t = TMS × k / ((I/Is)^α - 1), with the specific constants (k and α) for each curve type clearly tabulated — SI (k=0.14, α=0.02), VI (k=13.5, α=1.0), EI (k=80.0, α=2.0). The reverse side covers practical grading guidance: current transformer ratio (CTI) grading margins of 0.3–0.5 seconds between upstream and downstream relays, TMS (Time Multiplier Setting) selection methodology with worked example, pickup current setting rules (1.05–1.3 × maximum load current), and a decision guide for choosing between SI, VI, and EI curves based on fault current characteristics and downstream device coordination requirements. A quick-reference table shows typical TMS values for common distribution network configurations. Scan the QR code for our online protection coordination calculator.
What's Included
How to Print
- ●Recommended paper: 250–300gsm cardstock
- ●Print double-sided, flip on short edge
- ●Cut along crop marks with a paper trimmer
- ●Laminate with 80–125 micron pouches for durability
- ●Fits in wallet, toolbox, or pocket
Try the Interactive Calculator
Need precise calculations beyond quick reference? Try our free online calculator with full clause references and professional report output.
Open CalculatorRelated Downloads
Transformer Decoder
Free printable transformer nameplate decoder poster. Annotated nameplate diagram with every parameter explained per IEC 60076. Includes vector group table and practical implications.
Standards Cross-Ref
Free printable cross-reference table mapping key clauses between AS/NZS 3000, BS 7671, and IEC 60364. Covers voltage drop, earth sizing, max demand, overcurrent, isolation, disconnection times, and testing.
Cable Sizing Card
Free printable cable sizing quick reference card covering current-carrying capacity for common sizes (1.5–300 mm²) across AS/NZS 3008, BS 7671, IEC 60364, and NEC. Includes voltage drop formula and derating table.
Frequently Asked Questions
Which IDMT curve should I use?
Standard Inverse (SI) is the default for most distribution networks. Very Inverse (VI) suits systems with high fault currents that drop off quickly with distance. Extremely Inverse (EI) is used for fuse-relay coordination and transformer inrush avoidance.
What paper should I print this on?
Print on A4 landscape, double-sided. Use colour printing for the overlaid curves — each curve type is colour-coded. Laminate for repeated desk use during protection setting studies.
What standard does this reference?
Curve equations and constants per IEC 60255-151 (measuring relays and protection equipment — functional requirements for overcurrent protection). Grading methodology follows standard protection coordination practice per IEC 60909 and IEEE C37 series.
How often is this updated?
IDMT curve equations are defined constants in IEC 60255-151 and do not change between editions. Updated only if IEC revises the standard curve definitions.