AS/NZS 3008 Table 22: Temperature Derating Factors
AS/NZS 3008 Table 22 explained — ambient temperature derating factors for above-ground cables. Correction values from 25°C to 80°C for V-75, V-90, and X-90 insulation.
What Is AS/NZS 3008 Table 22?
Table 22 of AS/NZS 3008.1.1:2017 provides ambient temperature derating factors for cables installed above ground. These factors adjust the base current-carrying capacity (from Tables 13, 14, or 15) when the actual ambient air temperature differs from the 40°C reference temperature.
Unlike BS 7671 and IEC 60364 (which use 30°C as the reference), AS/NZS 3008 uses 40°C because Australian conditions frequently expose cables to elevated ambient temperatures — particularly in roof spaces, outdoor enclosures, plant rooms, and northern Australian locations where summer temperatures routinely exceed 40°C.
Table 22 covers temperatures from 25°C to 80°C and provides factors for three conductor operating temperature ratings:
- 75°C — V-75 (standard PVC/thermoplastic)
- 90°C — V-90 (heat-resistant PVC) and X-90 (XLPE)
- 110°C — Silicone and other high-temperature insulations
For buried cables, use Table 23 instead, which provides factors based on ground (soil) temperature with a 25°C reference.
Table 22 — Complete Derating Factor Values
The following table reproduces the key values from AS/NZS 3008 Table 22:
| Ambient Temp (°C) | 75°C Insulation | 90°C Insulation | 110°C Insulation |
|---|---|---|---|
| 25 | 1.20 | 1.14 | 1.10 |
| 30 | 1.13 | 1.10 | 1.07 |
| 35 | 1.07 | 1.05 | 1.04 |
| 40 (reference) | 1.00 | 1.00 | 1.00 |
| 45 | 0.93 | 0.95 | 0.96 |
| 50 | 0.84 | 0.89 | 0.93 |
| 55 | 0.76 | 0.84 | 0.89 |
| 60 | 0.65 | 0.77 | 0.84 |
| 65 | 0.53 | 0.71 | 0.80 |
| 70 | 0.38 | 0.63 | 0.76 |
| 75 | — | 0.55 | 0.71 |
| 80 | — | 0.45 | 0.65 |
Uprating Below 40°C — A Unique AS/NZS Feature
Because the AS/NZS 3008 reference is 40°C (higher than BS 7671’s 30°C), cables installed in environments below 40°C benefit from an uprating factor greater than 1.0. This is a common situation in:
- Temperate southern Australian cities (Melbourne, Hobart, Adelaide) where typical ambient is 25–35°C
- Air-conditioned plant rooms maintained at 25°C year-round
- Underground car parks and basements where ambient rarely exceeds 30°C
- New Zealand installations where ambient seldom exceeds 30°C
For example, at 25°C ambient with 90°C insulation, the factor is 1.14 — meaning a cable rated at 100 A in Table 13 can actually carry 114 A. This can sometimes allow a smaller cable size, reducing cost and installation effort.
However, uprating should only be applied when the lower ambient temperature can be guaranteed for the cable’s entire service life. A cable installed in an air-conditioned room today may be in a non-conditioned space after a building refurbishment 15 years later.
Hot Climate Derating — The Australian Challenge
In hot Australian environments, temperature derating can have a dramatic effect on cable sizing:
Scenario: Cable in outdoor enclosure, inland Queensland
Maximum ambient temperature: 55°C
Cable type: V-90 copper multicore
Design current: 80 A
Table 22 factor at 55°C for 90°C insulation: 0.84
Required tabulated rating: 80 / 0.84 = 95.2 A
Without temperature derating, a 25 mm² cable (87 A, Col 6) suffices.
With derating, 35 mm² (107 A, Col 6) is needed.
Impact: One cable size larger = 40% more copper by weight.
The situation is even more severe for V-75 insulation: at 55°C, the factor drops to 0.76, requiring a tabulated rating of 80 / 0.76 = 105.3 A — pushing to the same 35 mm² cable but with less safety margin.
Environments that commonly exceed 40°C in Australian practice include:
- Roof spaces: Can reach 60–70°C in summer
- Outdoor switchboards: 45–55°C with sun exposure
- Engine rooms and plant rooms: 40–50°C from equipment heat
- North-facing walls: Radiant heating can add 10–15°C to ambient
Mathematical Basis of Temperature Correction
The temperature correction factor is derived from the thermal equation for cable current-carrying capacity. The factor is calculated as:
kt = √((Tmax − Ta) / (Tmax − Tref))
where:
- Tmax = maximum conductor operating temperature (75°C for V-75, 90°C for V-90/X-90)
- Ta = actual ambient temperature
- Tref = reference ambient temperature (40°C)
For example, V-90 cable at 50°C ambient:
kt = √((90 − 50) / (90 − 40))
= √(40 / 50)
= √0.80
= 0.894 ≈ 0.89
This formula also explains why cables with higher insulation ratings are less affected by temperature increases — the larger the (Tmax − Tref) denominator, the less impact each degree of ambient increase has on the square root ratio.
Table 22 vs Table 23 — Air vs Ground Temperature
AS/NZS 3008 provides two separate temperature derating tables:
| Table | Applies To | Reference Temp | Typical Range |
|---|---|---|---|
| Table 22 | Above-ground installations (air) | 40°C | 25–80°C |
| Table 23 | Underground/buried installations | 25°C | 10–40°C |
Ground temperatures are more stable than air temperatures and are generally lower in summer. In most Australian locations, the ground temperature at 500 mm depth (standard burial depth) is 20–30°C even when the air temperature exceeds 40°C. This is why Table 23 uses a lower reference (25°C) and covers a narrower temperature range.
Never use Table 22 for buried cables or Table 23 for above-ground installations. The different reference temperatures and the different thermal environments (convective air vs conductive soil) make the factors non-interchangeable.
Try the Cable Sizing Calculator
Put this methodology into practice. Calculate results with full standard clause references — free, no sign-up required.
Or embed this calculator on your siteFrequently Asked Questions
Related Resources
Cable Sizing Calculator
Automated cable sizing with AS/NZS 3008 Table 22 temperature derating built in.
Read moreAS/NZS 3008 Table 13: Current Ratings
Base current-carrying capacity values to which Table 22 factors are applied.
Read moreAS/NZS 3008 Overview
Complete overview of AS/NZS 3008.1.1:2017 including all derating tables.
Read moreDerating Factors Explained
Cross-standard comparison of temperature derating across BS 7671, IEC 60364, and AS/NZS 3008.
Read more