Skip to main content
All Comparisons
COMPARISON

Cable Derating: 12 Cables in a Tray at 40°C — NEC's 90°C Advantage

12 cables on a perforated tray at 40°C ambient. All standards apply the same 50% grouping factor — but NEC starts from a 90°C base rating, ending with a smaller cable. Is that safe?

KholisFebruary 27, 202610 min read

Cable derating is where the standards appear to agree — similar grouping factors, similar temperature corrections — until you look at the starting point. NEC's approach of using the 90°C conductor rating as the base ampacity, then derating to the termination temperature, can result in a cable one or two sizes smaller than BS 7671 or IEC 60364 would require. This article examines whether that's clever engineering or a hidden risk.

The Scenario

A cable tray in a plant room:

  • 12 single-core cables (6 circuits, 2 conductors each) on a perforated cable tray
  • Each circuit: 32A three-phase
  • Cable type: Copper, PVC insulated (or THHN for NEC)
  • Installation: Single layer on perforated tray, cables touching
  • Ambient temperature: 40°C
  • Required: minimum cable size for each circuit

Side-by-Side Results

Scenario

12 cables on perforated tray, 32A each, 40°C ambient, single layer touching

ParameterAS/NZSBS 7671IEC 60364NEC
Base conductor temp rating
75°C PVCAS/NZS 3008, default70°C PVCBS 7671, Table 4D1A70°C PVCIEC 60364-5-5290°C THHNDerated to termination tempNEC 310.16, 90°C column
Base ampacity for 6mm²
41A75°C, Method ETable 1336A70°C, Method ETable 4D2A36A70°C, Method ETable B.52.455A90°C, #10 AWGTable 310.16
Grouping factor (12 conductors)
0.50Table 220.50Table C.2 or Table B.52.17Table 4C10.50Table B.52.170.5010-20 conductorsTable 310.15(C)(1)
Temperature factor (40°C)
0.8740°C, 75°C ratedTable 220.8740°C, 70°C ratedTable 4B10.8740°C, 70°C ratedTable B.52.140.9140°C, 90°C ratedTable 310.15(B)(1)
Combined derating factor
0.4350.50 × 0.870.4350.50 × 0.870.4350.50 × 0.870.4550.50 × 0.91
Derated capacity of 6mm²
17.8A41 × 0.435 — FAIL for 32A15.7A36 × 0.435 — FAIL for 32A15.7A36 × 0.435 — FAIL for 32A25.0A55 × 0.455 — FAIL for 32A
Minimum cable size to carry 32A
16mm²76A × 0.435 = 33.1A ✓25mm²89A × 0.435 = 38.7A ✓25mm²89A × 0.435 = 38.7A ✓10mm² (#8 AWG)80A × 0.455 = 36.4A ✓Table 310.16, 90°C
Most conservative: IEC 60364 / BS 7671 (25mm² — largest cable required)
Run this comparison yourself
Standards agreeModerate differenceSignificant difference

The NEC 90°C Advantage Explained

How NEC Uses Two Temperature Ratings

NEC 310.15(B) permits an approach that other standards do not allow in the same way:

  1. Start with the 90°C ampacity from Table 310.16 (highest current rating)
  2. Apply derating factors (grouping + temperature) to this higher starting value
  3. The final derated value must not exceed the termination temperature rating (usually 60°C or 75°C)

NEC Derating Method

I_derated = I_90°C × f_group × f_temp

NEC Final Check

I_derated ≤ I_75°C (or I_60°C for termination limit)

This means: even though the termination can only handle the 75°C rating, the cable itself can run hotter in the middle of the run (up to 90°C), giving more thermal headroom for derating.

Why Other Standards Don't Allow This

BS 7671, IEC 60364, and AS/NZS 3008 take the position that the cable temperature should be referenced to the conductor operating temperature, not the insulation temperature limit. If the cable is PVC rated at 70°C, you use the 70°C ampacity as your starting point — period.

The reasoning: conductor temperature affects resistance, which affects voltage drop and losses. A cable running at 90°C in the middle of a grouped installation has higher resistance (and therefore higher voltage drop) than one running at 70°C. The IEC/BS approach is more conservative but also more thermally consistent.

The Voltage Drop Catch

NEC's 90°C advantage gives a smaller cable for current carrying — but the higher conductor temperature means higher resistance, which means more voltage drop. A cable sized to NEC's derated 90°C method may pass the ampacity check but fail the voltage drop check on long runs. Always verify both.

The Real-World Impact: Cable Tray Fill

For our 12-cable scenario, the cable sizes are:

StandardCable SizeCross-Section AreaTray Space Needed
NEC10mm² (#8 AWG)8.37mm² per conductor100mm² total
AS/NZS16mm²15.2mm² per conductor182mm² total
BS 7671 / IEC25mm²24.0mm² per conductor288mm² total

The NEC installation uses 65% less tray space than BS 7671. For a large industrial plant with hundreds of cable runs, this means smaller trays, lighter supports, and significantly lower installation costs.

Is NEC's Approach Safe?

This is the fundamental question. The engineering community is split:

Arguments For (NEC Position)

  1. Cable insulation is rated for 90°C — it can safely operate at that temperature
  2. The termination temperature limit protects the weakest point (the connection)
  3. Decades of US installations prove the method works in practice
  4. Manufacturers design THHN cable specifically for this application

Arguments Against (IEC/BS Position)

  1. Conductor at 90°C in a grouped tray transfers heat to adjacent cables
  2. The 70°C/75°C tables already account for the thermal environment
  3. Higher conductor temperature accelerates insulation ageing
  4. Voltage drop and I²R losses increase — the cable is less efficient

The Practical Consensus

Both approaches are safe when correctly applied. The NEC method is more optimised (less copper for the same safety margin). The IEC/BS method has more built-in margin (the cable runs cooler than its limit). The choice is made by your jurisdiction, not by engineering preference.

Derating Factor Sources

Grouping Factors

All four standards agree on approximately 0.50 for 12 cables in a single layer on a tray. The values come from heat-transfer calculations validated by IEC TC 20 testing. Small differences exist in exact boundaries (e.g., "7-9 cables" vs "7-12 cables" in different tables), but the physics is the same.

Temperature Correction

The temperature correction factor is derived from:

Temperature Correction Factor

Ct = √((T_max - T_ambient) / (T_max - T_reference))

Where T_max is the conductor temperature rating, T_reference is 30°C (standard ambient), and T_ambient is the actual ambient temperature.

For 90°C cable at 40°C: Ct = √((90-40)/(90-30)) = √(50/60) = 0.913 For 70°C cable at 40°C: Ct = √((70-40)/(70-30)) = √(30/40) = 0.866

The 90°C cable retains more of its capacity at elevated ambient temperatures — another advantage of the NEC approach.

Practical Guidance

  1. Always use the derating method required by your applicable standard — mixing approaches is a compliance violation
  2. For international projects, the IEC/BS method is the safe default
  3. NEC's 90°C method is only valid for 90°C-rated conductors (THHN, THWN-2) — not for all cable types
  4. Verify voltage drop independently — a cable sized by NEC 90°C derating may need upsizing for voltage drop
  5. Cable tray fill calculations differ between standards — size the tray for the cable sizes you actually use

Key Takeaways

  1. NEC allows 10mm² where IEC/BS requires 25mm² — a 2.5× difference in copper for the same circuit
  2. The NEC 90°C base rating starts from a higher ampacity, giving more derating headroom
  3. All four standards use similar grouping factors (~0.50 for 12 cables) — the divergence is in the starting point
  4. Temperature correction is more favourable for 90°C cable (0.91 vs 0.87 at 40°C)
  5. Neither approach is wrong — they represent different engineering philosophies about thermal margins

Try the Cable Sizing Calculator

Free online tool — no signup required

Open Calculator
Kholis

Kholis

Lead Electrical & Instrumentation Engineer

18+ years of experience in electrical engineering at large-scale mining operations. Specializing in power systems design, cable sizing, and protection coordination across BS 7671, IEC 60364, NEC, and AS/NZS standards.

18+ years electrical engineering experienceLead E&I Engineer at major mining operationECalPro founder & developer