Skip to main content
Back to Insights
BRIEFINGIEC 62305-1:2010 · IEC 62305-2:2010 · AS/NZS 1768:2007

IEC 62305 Lightning Protection Levels — When You Need What

Four protection levels (I-IV), rolling sphere radii from 20m to 60m, and the risk assessment that determines which level applies. Decoded in 5 minutes.

February 26, 2026

The Four Protection Levels

IEC 62305-1 defines four Lightning Protection Levels (LPL), each with increasing capture efficiency:

ParameterLPL ILPL IILPL IIILPL IV
Rolling sphere radius20m30m45m60m
Mesh size5m × 5m10m × 10m15m × 15m20m × 20m
Protection angle25° (at 20m height)35°45°55°
Min peak current captured3 kA5 kA10 kA16 kA
Capture efficiency99%97%91%84%
Conductor cross-section (Cu)50mm²25mm²16mm²16mm²

LPL I captures 99% of all lightning strikes. LPL IV captures only 84%. The 16% of strikes that bypass LPL IV are low-current events (<16 kA) that are less likely to cause structural damage but can still destroy electronics.

How to Determine the Required Level

IEC 62305-2 prescribes a risk assessment based on four risk components:

  • R1: Risk of loss of human life
  • R2: Risk of loss of service to the public
  • R3: Risk of loss of cultural heritage
  • R4: Risk of loss of economic value

For each risk component:

R = N × P × L

Where:

  • N = number of dangerous events per year (based on flash density, building dimensions, environment)
  • P = probability of damage (depends on protection measures)
  • L = consequential loss (ratio of expected loss)

If R exceeds the tolerable risk (R_T), lightning protection is required. The LPL is selected to reduce R below R_T.

Simplified Selection Guide

For projects without a full risk assessment:

Building TypeTypical LPL
Hospitals, data centres, emergency servicesLPL I
Schools, office towers (>30m), public assemblyLPL II
Commercial buildings, industrial facilitiesLPL III
Residential, small structuresLPL IV
Explosive/flammable storageLPL I (mandatory)

Rolling Sphere Method

The rolling sphere is the primary design tool. Imagine a sphere of radius R (per LPL) rolling over the building:

  • Where the sphere touches the building surface: that surface needs protection
  • Where the sphere rests on air terminals or natural components: those points become the lightning capture zone
  • Areas in the "shadow" under the sphere between air terminals: protected zone

For LPL I with R = 20m, air terminals must be closely spaced. For LPL IV with R = 60m, fewer air terminals are needed because the larger sphere "bridges" larger gaps.

Down Conductors

LPLMinimum Down ConductorsMaximum Spacing
IAs required by design10m
IIAs required10m
IIIAs required15m
IVAs required20m

Down conductors must be routed as directly as possible from the air termination to the earth termination, avoiding sharp bends (<90° preferred, never <60°).

Earth Termination

All LPLs require earth resistance ≤ 10Ω (lower values required for sensitive installations). Type A (vertical/horizontal electrodes) or Type B (ring earth electrode around the building) arrangements are specified per IEC 62305-3.

Design your system: Calculate rolling sphere coverage and protection zones with the Lightning Protection Calculator.


Frequently Asked Questions

What is protection coordination?

Protection coordination ensures that the protective device closest to a fault operates first, minimizing the affected area. This requires analyzing time-current curves (TCC) for all devices in series per IEEE 242.

How do I select between MCB and fuse?

MCBs offer adjustable trip settings and reusability but cost more. Fuses are cheaper, faster at high fault currents, and better for motor starting (withstand inrush). Choice depends on application per IEC 60947-2.


Related Articles

  • Lightning - Interactive calculator with standards compliance

Browse all calculators → | Read more insights →

Try It Yourself

Run the calculations from this article using our free calculators:

Standards Referenced

IEC 62305-1:2010IEC 62305-2:2010AS/NZS 1768:2007