Challenge: Determine If This Circuit Breaker Provides Fault Protection Within 0.4s
Work through an earth fault loop impedance verification for a 32A Type C MCB on a 6mm2 copper cable in a TN-S system. Calculate Zs, determine fault current, check against BS 7671 Table 41.3 maximum Zs, and explore remediation options if it fails.
The Problem
| Parameter | Value |
|---|---|
| Protection device | 32 A Type C MCB to BS EN 60898-1 |
| Circuit cable | 6 mm² copper, single-phase |
| Cable length | 25 m |
| Installation method | In conduit (Reference Method B1) |
| System type | TN-S |
| Ze (external earth fault loop impedance) | 0.35 Ω |
| CPC size | 2.5 mm² copper (separate CPC in conduit) |
| Supply voltage (Uo) | 230 V |
The question is simple: under an earth fault condition at the far end of this circuit, will the fault current be high enough to trip the MCB within 0.4 seconds?
Per BS 7671:2018, Regulation 411.3.2.2, the maximum disconnection time for a final circuit not exceeding 32 A in a TN system is 0.4 seconds.
Work Through It
Step 1: Calculate the circuit conductor resistances (R1 and R2).
From BS 7671, Table 4D1B, Column 3 (resistance at conductor operating temperature for thermoplastic insulation, 70°C):
- 6 mm² copper: R1/m = 3.70 mΩ/m
- 2.5 mm² copper: R2/m = 9.22 mΩ/m
For the 25 m cable run:
R1 = 3.70 × 25 / 1000 = 0.0925 Ω
R2 = 9.22 × 25 / 1000 = 0.2305 Ω
Step 2: Calculate total earth fault loop impedance (Zs).
Zs = Ze + R1 + R2
Zs = 0.35 + 0.0925 + 0.2305
Zs = 0.673 Ω
Step 3: Calculate prospective earth fault current (If).
If = Uo / Zs
If = 230 / 0.673
If = 341.8 A
Step 4: Check against the MCB requirements.
A Type C MCB has a magnetic (instantaneous) trip range of 5–10 times its rated current (In). For a 32 A Type C MCB:
- Minimum instantaneous trip current: 5 × 32 = 160 A
- Guaranteed instantaneous trip current: 10 × 32 = 320 A
Our fault current of 341.8 A exceeds 320 A, so the MCB will trip instantaneously (within approximately 10 ms). But wait — we should also check against the published maximum Zs from BS 7671, Table 41.3.
The Verdict
From BS 7671:2018, Table 41.3, the maximum Zs for a 32 A Type C MCB for 0.4-second disconnection is:
Zs(max) = 0.73 Ω
Our calculated Zs = 0.673 Ω.
0.673 Ω < 0.73 Ω — PASS
The circuit complies with the 0.4-second disconnection requirement. But look at the margin: only 0.057 Ω separating compliance from failure. That is an 8% margin.
In practice, this margin is tight for several reasons:
- Ze varies. The supply authority’s declared Ze is a maximum value, but actual Ze at the installation can vary with network loading and switching. A Ze of 0.40 Ω (within the supply authority’s declared range for TN-S) would push Zs to 0.723 Ω — still passing but with only 1% margin.
- Temperature affects resistance. The Table 4D1B values are at 70°C operating temperature. If the conductors are hotter (overloaded circuit, high ambient), resistance increases and Zs increases.
- Connections add impedance. Every junction box, terminal, and connector adds a small impedance. Over a 25 m run with multiple connection points, this can add 0.01–0.05 Ω.
A measured Zs at commissioning that exceeds 0.73 Ω would fail the installation test. With a calculated margin this tight, there is a real risk of failing on test.
What If It Fails?
If Zs exceeded 0.73 Ω — or if you want a more comfortable margin — four remediation options exist:
- Increase the CPC size. Replacing the 2.5 mm² CPC with a 4 mm² CPC reduces R2 from 0.2305 Ω to 0.1438 Ω (Table 4D1B: 5.75 mΩ/m × 25 m). New Zs = 0.35 + 0.0925 + 0.1438 = 0.586 Ω. This provides a 20% margin and is the simplest fix if the conduit can accommodate the larger CPC.
- Use a Type B MCB instead of Type C. A 32 A Type B MCB has a maximum Zs of 1.15 Ω for 0.4-second disconnection (Table 41.3). Our Zs of 0.673 Ω would have a 41% margin. However, Type B may nuisance-trip on motor starting currents in a commercial kitchen (compressor motors for refrigeration, dishwasher pumps). Assess the load profile before changing MCB type.
- Shorten the cable run. Not always possible, but if the distribution board can be relocated closer to the load, R1 and R2 decrease proportionally. A 20 m run instead of 25 m gives Zs = 0.608 Ω.
- Add supplementary RCD protection. Per BS 7671, Regulation 411.4.9, where fault protection by overcurrent device alone cannot be achieved, a 30 mA RCD provides supplementary protection. The RCD will trip at earth fault currents as low as 30 mA within 40 ms, ensuring disconnection regardless of Zs. Note: this is supplementary protection — the overcurrent device must still provide overload and short-circuit protection. The RCD addresses the earth fault disconnection time only.
Standards referenced: BS 7671:2018+A2, Regulation 411.3.2.2, Table 41.3, Table 4D1B. MCB standard: BS EN 60898-1.
Try the Cable Sizing Calculator
Put this methodology into practice. Calculate results with full standard clause references — free, no sign-up required.
Or embed this calculator on your siteFrequently Asked Questions
Related Resources
Cable Sizing Calculator
Verify earth fault loop impedance and disconnection times as part of the cable sizing calculation.
Read moreProtection Coordination Calculator
Check MCB discrimination and fault protection compliance for complete distribution systems.
Read moreBS 7671 Amendment 4 Changes
What is changing in Amendment 4 including updated protection provisions.
Read more