Challenge: Is This Transformer Earthing System Compliant with IEC 60364-4-41?
Verify earth fault loop impedance compliance for a 1000kVA transformer with a 250m LV feeder. Calculate phase and PE conductor resistance at operating temperature, determine total Zs, check disconnection time per IEC 60364-4-41 Table 41.1, and assess touch voltage.
The Problem
| Parameter | Value |
|---|---|
| Transformer | 1000 kVA, 11kV/415V, Dyn11 |
| Transformer impedance | 6% (ZT) |
| System type | TN-S |
| LV feeder cable | 185 mm² 4-core XLPE aluminium + 95 mm² copper PE |
| Feeder length | 250 m |
| Protection at transformer LV | 100 A MCCB (thermal-magnetic) |
| System voltage | 415 V line-to-line, 240 V line-to-neutral |
| Conductor operating temperature | 80°C (XLPE under load) |
This is a distribution circuit feeding a sub-board. Per IEC 60364-4-41, Table 41.1, the maximum disconnection time for a distribution circuit in a TN system is 5 seconds.
Calculate Earth Fault Loop Impedance
Step 1: Transformer source impedance (Zsource).
The transformer impedance referred to the LV side:
ZT = (V2 / S) × z%
ZT = (4152 / 1,000,000) × 0.06
ZT = 0.1722 × 0.06 = 0.01033 Ω
For earth fault loop calculation, the relevant impedance is the transformer winding impedance in the fault loop. For a Dyn11 transformer with TN-S earthing, Zsource ≈ ZT = 0.010 Ω (predominantly reactive at this size).
Step 2: Phase conductor resistance (R1) — 185 mm² aluminium at 80°C.
Aluminium conductor resistance at 20°C: ρ20 = 0.0283 Ω·mm²/m.
Temperature correction to 80°C:
R80 = R20 × [1 + α × (80 − 20)]
Where α = 0.00403 /°C for aluminium:
R1/m = (0.0283 / 185) × [1 + 0.00403 × 60]
R1/m = 0.000153 × 1.2418 = 0.000190 Ω/m
For 250 m:
R1 = 0.000190 × 250 = 0.0475 Ω
Step 3: Protective conductor resistance (R2) — 95 mm² copper at 80°C.
Copper conductor resistance at 20°C: ρ20 = 0.01724 Ω·mm²/m.
Temperature correction to 80°C (α = 0.00393 /°C for copper):
R2/m = (0.01724 / 95) × [1 + 0.00393 × 60]
R2/m = 0.0001815 × 1.2358 = 0.000224 Ω/m
For 250 m:
R2 = 0.000224 × 250 = 0.0560 Ω
Step 4: Total earth fault loop impedance (Zs).
Zs = Zsource + R1 + R2
Zs = 0.010 + 0.0475 + 0.0560
Zs = 0.1135 Ω
Check Disconnection Time
Step 5: Calculate prospective earth fault current.
If = Uo / Zs = 240 / 0.1135 = 2,115 A
Step 6: Verify disconnection within 5 seconds.
Per IEC 60364-4-41, Table 41.1, for a TN system distribution circuit, the maximum disconnection time is 5 seconds. The 100 A thermal-magnetic MCCB must trip within 5 seconds at 2,115 A.
For a 100 A MCCB conforming to IEC 60947-2:
- The magnetic (instantaneous) trip threshold is typically 5–10 × In = 500–1,000 A (adjustable on most industrial MCCBs)
- Our fault current of 2,115 A significantly exceeds the maximum instantaneous trip threshold of 1,000 A
- The MCCB will trip instantaneously — within approximately 20–50 ms
Result: PASS. The disconnection time is well within the 5-second requirement. The 2,115 A fault current is more than twice the maximum instantaneous trip setting, so the MCCB trips in its magnetic region with substantial margin.
Touch Voltage Check
While the disconnection time is satisfactory, we should also check the prospective touch voltage during the fault — this is the voltage that appears on exposed metalwork at the sub-board during the brief period before the MCCB trips.
Touch voltage = If × R2(downstream)
Where R2(downstream) is the resistance of the PE conductor from the fault point back to the sub-board earth bar. For a fault at the sub-board:
Vtouch = If × R2 = 2,115 × 0.0560 = 118.4 V
This is a significant touch voltage. At 118 V, the IEC 60364-4-41 requirements for automatic disconnection become critical — the faster the disconnection, the lower the shock risk. Our MCCB trips instantaneously (20–50 ms), which is within the safe disconnection time curves for this voltage level.
However, consider what happens if the MCCB instantaneous trip is adjusted to a higher setting (as sometimes done to avoid nuisance tripping on motor starting at the sub-board). If the instantaneous setting were raised to 15 × In = 1,500 A, and the fault current were lower than calculated (perhaps due to higher conductor temperature or additional connection resistance), the MCCB might operate in its thermal-magnetic time-delay region. At 2,115 A on the thermal curve, the trip time could be 1–3 seconds — still within the 5-second limit, but exposing anyone touching the sub-board metalwork to 118 V for up to 3 seconds.
The Verdict and Remediation
Compliant? Yes. The earth fault loop impedance of 0.1135 Ω produces a fault current of 2,115 A, which trips the 100 A MCCB instantaneously — well within the 5-second disconnection requirement for a distribution circuit under IEC 60364-4-41.
But is it robust? Consider the following sensitivities:
| Scenario | Zs (Ω) | If (A) | Trips Instantaneously? |
|---|---|---|---|
| As designed (80°C) | 0.114 | 2,115 | Yes |
| Higher temperature (90°C) | 0.120 | 2,000 | Yes |
| Additional 50m extension | 0.145 | 1,655 | Yes (if Imag ≤ 1,000A) |
| Aluminium PE instead of copper | 0.140 | 1,714 | Yes (if Imag ≤ 1,000A) |
The design has margin, but that margin erodes with cable extensions, higher operating temperatures, or PE conductor substitution. If this sub-board will feed final circuits (not just other distribution circuits), those final circuits have a 0.4-second disconnection requirement — and the Zs at the end of those final circuits includes the 0.1135 Ω contribution from this feeder.
If remediation were needed, the most effective options are:
- Increase PE conductor size. A 120 mm² copper PE instead of 95 mm² reduces R2 by 21%, providing significant margin for downstream circuits.
- Add RCD protection at the sub-board. A time-delayed RCD (Type S, 100 ms) at the sub-board provides backup disconnection for earth faults that produce lower fault currents than the MCCB can detect quickly.
- Earth fault relay. For industrial installations, a dedicated earth fault relay with adjustable pickup and time settings provides more precise control over earth fault disconnection than relying on the MCCB’s overcurrent characteristics.
Standards referenced: IEC 60364-4-41:2005+A1:2017 (Table 41.1), IEC 60364-5-54 (protective conductors), IEC 60947-2 (MCCBs).
Try the Cable Sizing Calculator
Put this methodology into practice. Calculate results with full standard clause references — free, no sign-up required.
Or embed this calculator on your siteFrequently Asked Questions
Related Resources
Cable Sizing Calculator
Verify earth fault loop impedance and disconnection compliance as part of cable sizing.
Read moreShort Circuit Calculator
Calculate prospective fault currents for protection coordination studies.
Read moreEarthing Calculator
Design earthing systems and verify protective conductor sizing per IEC 60364-5-54.
Read more