Skip to main content
Back to Insights
CHALLENGEIEC 60076-1 · AS/NZS 3000:2018 · IEEE C57.110

Challenge: Size the Transformer for This Hospital — It's Not Just kVA

A 2,000 kVA load study for a hospital. But harmonics, motor starting, and essential services change everything. What size transformer do you actually need?

February 26, 2026

The Problem

A new 200-bed regional hospital. The maximum demand study shows:

Load CategoryDemand (kVA)
Lighting (LED throughout)280
General power (GPOs, IT)420
HVAC (chillers, AHUs, fans)650
Medical equipment (imaging, theatres)310
Kitchen and laundry180
Lifts and vertical transport120
Total calculated demand1,960 kVA

The project electrical engineer specifies a 2,000 kVA transformer with 5% impedance. Is this correct?

The Challenge

Identify at least four reasons why a 2,000 kVA transformer is wrong for this application, and determine the correct size.

The Solution

Problem 1: Harmonic Derating

LED lighting (280 kVA) and IT/GPO loads (420 kVA) are high-harmonic sources. Combined, they represent 700 kVA of non-linear load — 36% of total.

Per IEEE C57.110, a transformer supplying significant harmonic loads must be derated. With a K-factor of approximately 7 (typical for mixed LED/IT load profile), the transformer must be derated to approximately 85% of nameplate capacity.

2,000 kVA × 0.85 = 1,700 kVA effective capacity — insufficient for 1,960 kVA demand.

Problem 2: Motor Starting Voltage Dip

The largest HVAC chiller has a 200 kW DOL-start compressor motor. Starting current: approximately 6× FLC = ~1,800A at 415V = ~1,300 kVA.

Voltage dip during motor starting:

ΔV% = (S_start / S_tx) × Z_tx% = (1,300 / 2,000) × 5% = 3.25%

AS/NZS 61000.3.3 and most hospital standards require voltage dips to be less than 3% for sensitive medical equipment. At 3.25%, imaging equipment (MRI, CT) may produce artefacts or require recalibration.

Increasing transformer size to 2,500 kVA: ΔV% = (1,300 / 2,500) × 5% = 2.6% — passes.

Problem 3: Essential Services Redundancy

Hospital electrical systems require redundancy per AS/NZS 3009 (Electrical installations — Emergency power supplies in hospitals). Essential services (theatres, ICU, emergency department) must have:

  • N+1 transformer configuration or automatic changeover from utility to generator
  • If using a single transformer, it must be rated for the essential load with adequate margin for generator synchronisation transients

Essential services typically represent 60–70% of hospital demand. If the single transformer fails, the generator must support ~1,300 kVA. The transformer itself needs headroom above calculated demand for transient load acceptance.

Problem 4: Future Load Growth

Hospital load typically grows 2–3% per year as services expand and technology evolves. Over a 20-year transformer life:

1,960 kVA × (1.025)^20 = 3,211 kVA

Even with conservative 1.5% growth: 1,960 × (1.015)^20 = 2,638 kVA

The Correct Specification

ConsiderationRequired Capacity
Calculated demand1,960 kVA
Harmonic derating (K-7, 85%)2,306 kVA minimum nameplate
Motor starting (ΔV < 3%)2,500 kVA minimum
10-year growth (1.5%/yr)2,271 kVA demand
20-year growth (1.5%/yr)2,638 kVA demand

Recommended: 2,500 kVA transformer (or 2×1,600 kVA in parallel for redundancy), with K-factor rating or de-rated accordingly.

The 2,000 kVA specification was undersized by 25% once real-world factors were considered.

Run your own analysis: Use the Transformer Calculator and Maximum Demand Calculator together.


Frequently Asked Questions

How do I size a transformer?

Size based on maximum demand (not connected load), diversity factors per AS/NZS 3000 Table C2, and future growth (typically 125-150% of current load). Don't forget power factor correction and harmonics per IEEE C57.110.


Related Articles

Browse all calculators → | Read more insights →

Try It Yourself

Run the calculations from this article using our free calculators:

Standards Referenced

IEC 60076-1AS/NZS 3000:2018IEEE C57.110