Skip to main content

Myth: AS/NZS and IEC Give the Same Result for the Same Installation

AS/NZS 3008 is based on IEC 60364, but different reference ambient temperatures (40°C vs 30°C), different installation method definitions, and different grouping factor tables mean the same installation scenario produces results differing by 8-15% between standards.

3 min readUpdated March 12, 2026
Share:

The Myth

“AS/NZS 3008 is based on IEC 60364, so they give the same cable size. Just use whichever tables you have handy.”

This assumption appears in engineering offices across the Asia-Pacific region, where projects may reference AS/NZS domestically and IEC internationally. It is wrong, and it leads to cables that are either oversized (wasting copper) or undersized (risking failure).

The Key Differences

While AS/NZS 3008.1.1:2017 shares DNA with IEC 60364-5-52, the two standards diverge in several critical areas:

ParameterAS/NZS 3008.1.1:2017IEC 60364-5-52:2009
Reference ambient (air)40°C30°C
Reference soil temperature25°C20°C
Installation methods29 methods (Table 3, Columns 1–29)~10 reference methods (Table B.52.1)
Grouping factorsTable 22 (detailed, method-specific)Table B.52.17 (fewer rows, broader categories)
Conductor max temperature (XLPE)90°C (same)90°C (same)
Soil thermal resistivity reference1.2 K·m/W2.5 K·m/W

The ambient temperature difference is the most significant. AS/NZS uses 40°C as the reference because Australian conditions are hotter than the European baseline. This means the base ratings in AS/NZS tables are lower for the same cable — they already assume a hotter environment. When you apply temperature correction factors, the results diverge further depending on the actual site temperature.

Worked Comparison: Same Cable, Same Site, Different Standards

Scenario: 50mm² 4-core Cu/XLPE cable, installed on a perforated cable tray with 6 circuits grouped together, actual ambient temperature 35°C.

Under AS/NZS 3008.1.1:2017

  • Base rating (Table 4, Column 17, perforated tray, touching): 110A
  • Temperature correction for 35°C (Table 27, ref 40°C, max 90°C): × 1.07
  • Grouping factor for 6 circuits (Table 22, perforated tray): × 0.73
  • Derated capacity: 110 × 1.07 × 0.73 = 85.9A

Under IEC 60364-5-52:2009

  • Base rating (Table B.52.5, method E, perforated tray): 125A
  • Temperature correction for 35°C (Table B.52.14, ref 30°C, max 90°C): × 0.96
  • Grouping factor for 6 circuits (Table B.52.17, single layer, touching): × 0.72
  • Derated capacity: 125 × 0.96 × 0.72 = 86.4A

In this example, the results happen to be close (85.9A vs 86.4A — less than 1% difference). But change the ambient to 25°C:

  • AS/NZS: 110 × 1.20 × 0.73 = 96.4A (cooler than reference, so capacity increases)
  • IEC: 125 × 1.04 × 0.72 = 93.6A (slightly cooler than reference, small increase)

At 50°C ambient:

  • AS/NZS: 110 × 0.89 × 0.73 = 71.5A
  • IEC: 125 × 0.82 × 0.72 = 73.8A

The differences range from negligible to over 10% depending on conditions. At extreme ambient temperatures (common in Middle Eastern, African, and Australian projects), the gap widens further.

Field note: At Batu Hijau we used AS/NZS 3008 for the process plant and IEC 60364 for the port facility (international EPC contractor). Same island, same climate, same cable manufacturers — different cable sizes on the BOQ. The project manager wanted to know why. This is why.

The Reality: Use the Correct Standard

The standards are not interchangeable. The correct approach:

  • Identify the governing standard from the project specification, local regulations, or client requirements.
  • Use that standard’s tables exclusively — do not mix AS/NZS base ratings with IEC correction factors.
  • When comparing across standards (e.g., checking an IEC-designed system against AS/NZS for an Australian installation), run the full calculation under each standard independently and compare the final derated values.

“Based on IEC” does not mean “identical to IEC.” The national adaptations exist because local conditions, practices, and safety philosophies differ. Respect those differences.

Try the Cable Sizing Calculator

Put this methodology into practice. Calculate results with full standard clause references — free, no sign-up required.

Or embed this calculator on your site
Calculate Cable Sizing

Frequently Asked Questions

Australia and New Zealand experience higher average ambient temperatures than Central Europe, where IEC was historically developed. Using 40°C as the reference means the base ampacity tables already account for hot conditions. When an Australian engineer applies a temperature correction factor for a 35°C site, the factor is greater than 1.0 (capacity increases). An IEC engineer at the same site applies a factor less than 1.0 (capacity decreases from the 30°C base). The net result should be similar, but the different base values and correction factor tables introduce differences.
No. Compliance means using the specified standard's methodology and tables. A more conservative result from a different standard is not the same as a compliant result. The installation methods, grouping definitions, and correction factors are specific to each standard. An inspector or certifier will verify against the governing standard's tables, not a mix-and-match calculation.
It depends on the conditions. At high ambient temperatures (above 35°C), AS/NZS often gives slightly larger cables because the temperature correction from the 40°C base is less favourable than IEC's correction from 30°C. At moderate temperatures (25-30°C), AS/NZS may give smaller cables because the base rating already assumes a hotter environment. There is no universal answer — calculate both and compare.

Related Resources