Myth: If It Passed the Megger Test, the Cable Is Fine

Insulation resistance (megger) testing at 500V or 1000V DC detects only gross insulation failures. It misses partial discharge, water treeing, thermal aging, and high-resistance joints. A cable can show 500MΩ on a megger and fail catastrophically under load. IEEE 400-2012 describes far more diagnostic methods.

3 min readUpdated March 12, 2026
Share:

The Myth

“We meggered it. 500 meg-ohms. The cable is fine.”

This statement is heard on every construction site, in every maintenance shutdown report, after every cable fault investigation. It reflects a fundamental misunderstanding of what insulation resistance testing actually measures — and, more importantly, what it does not.

What a Megger Test Actually Measures

An insulation resistance test applies a DC voltage (typically 500V or 1000V for LV cables, 2.5kV or 5kV for MV cables) and measures the resulting leakage current. The ratio gives insulation resistance in megohms.

This test detects:

  • Gross insulation damage — cuts, crushing, burn-through
  • Water saturation — fully flooded cable sections
  • Contaminated terminations — dirt, salt, moisture on exposed insulation surfaces
  • Manufacturing defects — voids, inclusions, thin spots (if severe)

In other words, it finds catastrophic damage. If a cable has a hole in the insulation or is sitting in a flooded pit, the megger will find it. This is genuinely useful for commissioning tests and post-installation verification.

Five Things the Megger Cannot Find

1. Partial Discharge

Partial discharge (PD) is localised electrical breakdown within a void or defect in the insulation, without complete bridging. PD requires AC voltage above the inception voltage — typically 1.5–3× the cable’s rated voltage. A DC megger test at 500V or 1000V does not excite PD in a cable rated for 600V or 3.3kV. The defect is invisible. But under normal AC operating voltage, PD progressively erodes the insulation from inside until catastrophic failure occurs — typically in 2–10 years.

2. Water Treeing

Water trees are microscopic tree-shaped structures that grow in XLPE insulation in the presence of moisture and electric field stress. They develop over 5–20 years and progressively reduce the insulation’s dielectric strength. A cable with advanced water treeing can show perfectly acceptable insulation resistance on a megger test — the DC resistance of the tree structure is extremely high. But under AC stress, the capacitive coupling through the water tree creates a low-impedance path that eventually converts to an electrical tree and fails in milliseconds.

3. Thermal Aging

Insulation that has been chronically overheated (e.g., from sustained overloading or inadequate derating) undergoes polymer degradation — chain scission, oxidation, loss of plasticiser. The insulation becomes brittle and its dielectric strength decreases, but its volume resistivity (what the megger measures) may remain acceptable until very late in the degradation process. A thermally aged cable can pass a megger test at 500 MΩ and fail the next day under a voltage transient that healthy insulation would easily withstand.

4. High-Resistance Joints

A poorly made joint or termination can have a connection resistance of 10–100 mΩ (compared to <1 mΩ for a good joint). Under load, this creates localised heating that degrades the surrounding insulation over time. A megger test measures insulation resistance between conductors or conductor-to-earth — not the resistance of the conductor path itself. A joint that will overheat and fail at 200A passes the megger test without comment.

5. Mechanical Damage to Individual Strands

A cable with 30% of its strands severed (from an installation nick, compression, or rodent damage) still shows excellent insulation resistance — the insulation is intact. But the remaining strands carry 143% of their design current density, causing localised heating, accelerated aging, and eventual failure. Only a resistance test (comparing measured resistance against the manufacturer’s published value for the conductor size and length) or a detailed visual inspection can detect this.

What to Use Instead (or in Addition)

IEEE 400-2012 describes a hierarchy of cable testing methods, from least to most diagnostic:

MethodWhat It DetectsStandard ReferenceWhen to Use
Insulation resistance (megger)Gross damage, contaminationIEEE 400, Clause 5Commissioning, routine maintenance
DC hipot (high potential)Weak insulation (go/no-go)IEEE 400, Clause 6Post-installation (with caution on aged XLPE)
VLF (very low frequency) withstandInsulation defects without DC damage riskIEEE 400.2MV cable commissioning and maintenance
Tan delta (δ) measurementWater treeing, bulk aging, contaminationIEEE 400.2, IEC 60502-2Condition assessment of aged MV cables
Partial discharge testingVoids, defects, localised degradationIEEE 400.3, IEC 60270Condition assessment, defect location
Time domain reflectometry (TDR)Impedance changes, splices, damage locationIEEE 400, Clause 10Fault location, splice quality verification

For critical cables (MV feeders, life-safety circuits, process-critical supplies), a megger test alone is insufficient for condition assessment. Tan delta and partial discharge testing provide actual diagnostic information about remaining insulation life.

Field note: At Batu Hijau, a 3.3kV feeder cable to the SAG mill auxiliary transformer passed a 5kV megger test at 200 MΩ. Two weeks later, it failed catastrophically — a phase-to-earth fault that tripped the 11kV incomer and shut down the entire grinding circuit for 18 hours. The post-mortem found extensive water treeing at a low point in the cable route where the cable duct had flooded periodically during wet season. The insulation had been degrading for years. A tan delta test would have shown elevated dissipation factor and flagged the cable for replacement during the planned shutdown — not during production.

Frequently Asked Questions

Yes, for new cable commissioning on LV circuits. A megger test after installation confirms that no damage occurred during pulling, termination, and handling. For new cables with no thermal or moisture history, the failure modes that the megger misses (water treeing, thermal aging, partial discharge) have not had time to develop. The megger test is the appropriate commissioning test per AS/NZS 3000 Clause 8.3.6 and BS 7671 Regulation 612.3.
Yes — this is a critical point. DC voltage applied to aged XLPE insulation can cause space charge accumulation that actually accelerates water tree conversion to electrical trees, potentially causing failure during or shortly after the test. IEEE 400-2012 recommends VLF (very low frequency, 0.01-0.1 Hz) AC testing as a safer alternative for condition assessment of aged XLPE-insulated MV cables. The DC hipot remains appropriate for new cables and for paper-insulated cables.
For LV cables, AS/NZS 3000 requires a minimum of 1 MΩ at commissioning. Values below 2 MΩ on an in-service cable warrant investigation. However, absolute values are less diagnostic than trends — a cable that measured 500 MΩ last year and 50 MΩ this year has a developing problem, even though 50 MΩ is technically well above the minimum. Always compare against previous measurements and against other cables of the same type and age in the same installation.