What Size Cable Do You Need for a 400 Amp Supply?
For a 400 amp supply, use 185mm² copper cable with PVC insulation under BS 7671 Table 4D1A, rated at 415A clipped direct. Under NEC, 500 kcmil at 75°C provides 380A — parallel runs of 2×250 kcmil are common. At this current level, parallel cable runs or busbar trunking are often more practical than single large conductors.
Quick Reference: Cable Size for 400 Amp Industrial Mains by Standard
| Standard | Cable Size | Conditions | Reference |
|---|---|---|---|
| BS 7671 | 185mm² | Method C or E, PVC insulation | Table 4D1A |
| NEC | 500 kcmil | THWN-2, 75°C column | Table 310.16 |
| AS/NZS 3008 | 150mm² | Clipped direct, PVC insulation | Table 13 |
| IEC 60364 | 185mm² | Reference method C or E, PVC | Table B.52.4 |
Values shown are for copper conductors in typical domestic/commercial conditions. Actual size depends on installation method, ambient temperature, and cable length. Use our free cable sizing calculator for your exact scenario.
Typical Applications for a 400 Amp Industrial Mains
- Industrial main switchboard
- Large commercial building supply
- Data centre main feed
- Manufacturing plant mains
Calculate Your Exact Cable Size
These are general guidelines. Your specific installation needs exact calculation accounting for cable route length, installation method, ambient temperature, and cable grouping.
Frequently Asked Questions
Is a single 185mm² cable practical for 400 amps?▼
Can I use aluminium cable for 400 amps?▼
What is 500 kcmil in mm²?▼
Should I use busbar trunking instead of cable for 400A?▼
What size earth conductor for a 400 amp circuit?▼