Skip to main content

Myth: VFD Output Cables Don't Need Special Treatment

VFD output cables carry high dV/dt PWM waveforms (up to 8kV/µs) that cause bearing currents, insulation stress from voltage reflections, and EMI radiation. Symmetrical cable construction, low capacitance, and proper shield termination are essential — not optional.

4 min readUpdated March 12, 2026
Share:

The Myth

“A VFD is just a motor starter. Use the same cable you’d use for a DOL motor — it carries the same current.”

This was arguably true for early six-step inverters. For modern IGBT-based PWM drives with switching frequencies of 4–16 kHz and voltage rise times of 50–200 ns, it is dangerously wrong. The cable between a VFD and its motor carries a waveform that looks nothing like a sinusoid, and it creates failure modes that do not exist in conventional motor circuits.

What VFD Output Actually Looks Like

A modern VFD output is a series of DC voltage pulses at the switching frequency (typically 4–8 kHz for LV drives). Each pulse has:

  • Rise time: 50–200 ns (modern IGBTs)
  • dV/dt: up to 5–8 kV/μs
  • Peak voltage: 1.0–1.414 × DC bus voltage (565–800 V for a 400V drive)
  • Common-mode voltage: oscillating between +VDC/2 and −VDC/2 at switching frequency

This is not an engineering nuance. It is a fundamentally different electrical stress regime on the cable and motor.

Three Failure Modes Standard Cables Cannot Handle

1. Bearing Currents

Common-mode voltage on the motor frame couples capacitively through the motor bearings to the shaft. At each switching edge, a displacement current pulse flows through the bearing oil film. Over millions of pulses per second, the bearing surfaces erode in a pattern called “fluting” — microscopic craters that eventually cause bearing failure, typically within 6–24 months.

IEC 60034-17, Section 7 describes this mechanism and recommends: insulated bearings (DE or NDE), shaft grounding brushes, and — critically — low-impedance, symmetrical cable with a continuous shield grounded at both ends to provide a low-impedance path for common-mode current.

2. Voltage Reflections and Insulation Stress

When a voltage pulse with 100 ns rise time travels down a cable, it reflects at the motor terminals (impedance mismatch). The reflected wave adds to the incident wave, producing peak voltage at the motor terminals up to 2× the DC bus voltage. For a 400V drive with 565V DC bus, the motor terminal voltage can spike to 1130V — well above the 600V insulation rating of standard PVC cables.

The critical cable length depends on rise time. For a 100 ns rise time:

Lcritical = v × trise / 2 ≈ 150 × 106 × 100 × 10−9 / 2 ≈ 7.5m

For cables longer than 7.5m (which is most installations), voltage doubling occurs. Above approximately 30m, the full 2× reflection is established. Cable insulation must withstand these repeated impulse voltages for the 20–30 year life of the installation — standard PVC/XLPE insulation systems are not rated for this duty.

3. Capacitive Leakage Current and EMI

The cable’s capacitance to ground (typically 100–250 pF/m for standard cables) creates a leakage current path at each switching edge:

Icap = C × dV/dt

For a 100m cable at 150 pF/m with dV/dt = 5 kV/μs:

Icap = (100 × 150 × 10−12) × (5 × 109) = 75A peak

This 75A peak capacitive current pulse — at every switching edge, 8,000–16,000 times per second — flows through the cable shield (if present) or radiates as EMI (if not). Without a proper shield, this current radiates into parallel signal cables, instrument loops, and communication networks. With a shield grounded at one end only, the shield carries the full current to one ground point, creating ground potential differences.

What VFD Output Cables Actually Need

A properly specified VFD output cable has these characteristics:

  • Symmetrical construction: 3 phase conductors + 3 earth conductors (not 3C+E), arranged symmetrically so that capacitive coupling to the shield is balanced across all phases. This reduces common-mode current.
  • Low capacitance: <200 pF/m preferred, achieved through XLPE or EPR insulation with appropriate wall thickness. Standard PVC cables typically have 150–300 pF/m; purpose-built VFD cables achieve 80–150 pF/m.
  • Continuous shield: Copper braid or tape with ≥85% coverage, terminated at both ends with 360° compression glands — not pigtail connections. The shield provides a low-impedance return path for common-mode current, keeping it out of the building’s earthing system.
  • Insulation rated for impulse voltage: The cable must withstand repeated voltage spikes up to 2× DC bus voltage. Some manufacturers specify “inverter duty” or “VFD rated” cables tested per IEC 60502 with additional impulse withstand requirements.
Field note: At the Batu Hijau concentrator, we replaced 14 VFD-fed pump motor cables in year two of operation. Every one had bearing failures within 18 months. The original cables were standard 4-core SWA — no symmetrical construction, steel wire armour instead of copper braid. We replaced them with symmetrical XLPE/copper-braid cables and added shaft grounding brushes. Three years later, zero bearing failures on the same motors. The cable cost difference was 40%. The bearing replacement cost difference was infinite.

Try the Motor Calculator

Put this methodology into practice. Calculate results with full standard clause references — free, no sign-up required.

Or embed this calculator on your site
Calculate Motor

Frequently Asked Questions

An output reactor (3-5% impedance) reduces dV/dt and limits voltage reflection magnitude, which helps with insulation stress and bearing currents. A dV/dt filter (LC type) is more effective, reducing rise time to 1-2 µs. However, neither eliminates the EMI issue — you still need a shielded cable to contain radiated emissions. For cables under 10m with an output reactor, standard cable may be acceptable. For longer runs, purpose-built VFD cable is the correct engineering solution.
Yes, although the consequences are less severe. Small drives use the same IGBT switching technology with similar dV/dt. Bearing currents still occur but may take longer to cause failure in smaller bearings. EMI radiation is proportional to cable length and capacitance, so short runs to small motors produce less interference. The engineering principles are identical regardless of drive size — the question is whether the cost of proper cable is justified by the failure risk. For motors where bearing replacement is cheap and downtime is inconsequential, standard cable with an output reactor may be an acceptable compromise.
Steel wire armour has high impedance at the switching frequencies involved (4-16 kHz). It is ineffective as a high-frequency shield compared to copper braid. The steel wires also have ferromagnetic properties that increase common-mode impedance rather than reducing it. For VFD output applications, copper braid or copper tape screen is required. SWA provides mechanical protection only — it does not address the electrical requirements of a VFD output cable.

Related Resources