How to Read a Cable Sizing Table (AS/NZS 3008 Table 13 Explained)
Learn exactly how to navigate AS/NZS 3008.1.1:2017 Table 13 for cable current ratings. Step-by-step guide covering installation methods, insulation types, conductor formations, and common mistakes.
I have watched experienced engineers stare at AS/NZS 3008.1.1:2017 Table 13 for minutes, scrolling back and forth between columns, unsure which one applies. The table is dense. It has dozens of columns spanning multiple insulation types, conductor configurations, and installation methods. But once you understand its structure, you can read any value in seconds.
This tutorial breaks down exactly how Table 13 is organised and walks through a specific lookup so you never second-guess your column selection again.
What Table 13 Actually Contains
Table 13 provides the current carrying capacity in amperes for cables installed in air. These are the base ratings before any derating factors are applied.
AS/NZS 3008.1.1, Table 13 — Sustained current rating for cables in airThe table is organised along two axes:
- Rows: Conductor cross-sectional area in mm2 (1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300, 400, 500, 630)
- Columns: A combination of insulation type, number of cores, and installation method
The values in the cells are amperes at the reference ambient temperature of 40 degrees C for cables in air. This reference temperature is specific to AS/NZS 3008 — BS 7671 uses 30 degrees C, which is why you cannot simply borrow values between standards.
Understanding the Column Groups
Table 13 is divided into major column groups by insulation type:
V-75 (PVC, 75 degrees C maximum conductor temperature)
This is standard PVC insulation. Lower maximum temperature means lower current ratings compared to XLPE. Common in building wiring, light commercial, and residential.
V-90 (PVC, 90 degrees C maximum conductor temperature)
Heat-resistant PVC. Higher rating than V-75 but still lower than XLPE. Used where higher temperature tolerance is needed but XLPE cost is not justified.
X-90 (XLPE, 90 degrees C maximum conductor temperature)
Cross-linked polyethylene. The workhorse insulation for industrial and commercial installations. Higher current ratings than PVC for the same conductor size. Standard in mining, heavy industry, and infrastructure.
How to identify your insulation type
Check the cable manufacturer's datasheet or the cable marking printed on the outer sheath. Australian cables are marked with their insulation designation. A cable marked "4C x 16mm2 Cu X-90" is a 4-core 16mm2 copper cable with XLPE insulation rated to 90 degrees C.
Within each insulation group, columns are further divided by:
- Number of loaded cores: 2-core (single-phase) or 3/4-core (three-phase). Single-core cables have their own sub-columns for trefoil and flat formation.
- Installation method: Referenced by number from Table 3.
Understanding Installation Methods (Table 3)
Before you can select the correct column in Table 13, you must identify your installation method from Table 3. Here are the most common ones:
AS/NZS 3008.1.1, Table 3 — Description of installation methods| Method | Description |
|---|---|
| 1 | Enclosed in thermally insulating material (worst case) |
| 3 | In conduit in air |
| 4 | In conduit on/in wall |
| 7 | Against or spaced from a non-thermally insulating wall |
| 11 | On unperforated cable tray |
| 13 | On perforated cable tray |
| 14 | Suspended from or incorporating a support wire |
| 22 | Free air (best case for air installations) |
The method number tells Table 13 which column to use. Higher-numbered methods generally allow better heat dissipation and therefore higher current ratings. A cable on a perforated tray (Method 13) can carry more current than the same cable in conduit (Method 3), because the tray allows air to circulate around the cable.
Worked Example: Reading the Table
Let us look up a specific value. Our cable is:
- 16 mm2 conductor size
- 4-core (three-phase plus neutral)
- X-90 (XLPE) insulation
- Installed on perforated cable tray (Method 13)
Step 1: Find the correct insulation group
Navigate to the X-90 section of Table 13. Skip past V-75 and V-90 columns.
Step 2: Find the core count sub-group
Within X-90, find the columns for multicore cables (not single-core). Then find the 3 or 4 loaded core columns. For a 4-core cable supplying a three-phase load with a neutral that carries negligible current (balanced load), you use the 3-loaded-conductor columns. If the neutral carries significant current (harmonic-laden loads), you must treat it as a 4-loaded-conductor cable, which has lower ratings.
3 loaded cores vs 4 loaded cores
A 4-core cable on a balanced three-phase circuit has 3 loaded cores (the neutral carries only imbalance current). Use the 3-loaded-core column. If your circuit has significant third-harmonic neutral current — common with LED lighting, VFDs, and IT loads — the neutral is loaded and you must use the 4-loaded-core rating, which is approximately 14% lower.
Step 3: Find the installation method column
Within the 3-loaded-core sub-group, find the column for Method 13 (perforated cable tray).
Step 4: Read the value at the correct row
Go down to the 16 mm2 row. The value you read is approximately 86 A.
This means a 16 mm2 4-core X-90 copper cable on a perforated tray can carry 86 A continuously at 40 degrees C ambient, in isolation (no grouping), before any derating is applied.
Where Engineers Go Wrong
Confusion 1: 2-Core vs 4-Core Columns
The 2-core column gives higher values than the 4-core column for the same cable size. This is because two loaded conductors generate less heat per unit length than four. A junior engineer looking up a three-phase cable who accidentally reads the 2-core column will overestimate the cable's capacity. Always verify you are in the correct core count sub-group.
Confusion 2: V-75 vs V-90 vs X-90
A 10 mm2 cable rated under V-75 might carry 54 A, while the same physical conductor size under X-90 might carry 65 A. The difference is purely the maximum operating temperature of the insulation. Using the wrong insulation column can easily lead to a one-size error in cable selection.
Confusion 3: Trefoil vs Flat for Single-Core Cables
Single-core cables have separate columns for trefoil formation (three cables bundled in a triangle) and flat formation (three cables in a row, either touching or spaced). Flat spaced gives the highest current rating because each cable has maximum exposure to ambient air. Trefoil gives lower ratings but offers better electromagnetic balance and lower induced voltages in cable sheaths.
AS/NZS 3008.1.1, Table 13, Note 3 — Single-core cable formationsConfusion 4: Forgetting the Reference Temperature
Table 13 values are at 40 degrees C ambient. If your installation is at 50 degrees C (common in engine rooms, roof spaces, and tropical outdoor installations), you must apply the temperature derating factor from Table 22 before the table value is usable.
AS/NZS 3008.1.1, Table 22 — Rating factors for ambient air temperatureComparing Methods: How Much Does It Matter?
To illustrate the impact of installation method, here are the approximate current ratings for the same cable (16 mm2 4C X-90 copper, 3 loaded cores) across different methods:
| Installation Method | Description | Current Rating (A) |
|---|---|---|
| Method 3 | In conduit in air | 73 |
| Method 7 | Against wall | 78 |
| Method 11 | Unperforated tray | 82 |
| Method 13 | Perforated tray | 86 |
| Method 22 | Free air | 93 |
The difference between conduit and free air is roughly 27%. This is not negligible. An engineer who selects a cable based on the free air rating and then installs it in conduit may have an undersized cable.
The Tables You Need Beyond Table 13
Table 13 gives you the starting point. A complete cable sizing calculation also requires:
| Table | Purpose |
|---|---|
| Table 3 | Identify installation method number |
| Table 21 | Grouping derating factors |
| Table 22 | Ambient temperature derating factors |
| Table 23 | Thermal resistivity of soil (for buried cables — Table 14 gives buried ratings, not Table 13) |
| Tables 35-42 | Voltage drop values (mV/A/m) |
Table 13 is for air installations only
If your cable is direct buried or in underground ducts, you need Table 14, not Table 13. The reference conditions change from 40 degrees C ambient air to 25 degrees C soil temperature and 1.2 K.m/W soil thermal resistivity. Using Table 13 values for a buried cable will give incorrect results.
Practice Exercise
Try this yourself before checking the answer:
Question: What is the current rating for a 25 mm2 2-core V-75 copper cable installed in conduit in air (Method 3)?
Steps:
- Find the V-75 insulation group in Table 13
- Find the 2-core (or 2 loaded conductor) sub-group
- Find the Method 3 column
- Read the value at the 25 mm2 row
Answer: Approximately 77 A at 40 degrees C ambient, single circuit, no grouping.
If you got that right, you can read any value from Table 13. The structure is identical across all insulation types and installation methods. Find your insulation, find your core count, find your installation method, read the value. Then apply your derating factors from Tables 21 and 22 to get the actual usable current capacity for your specific installation.
Try the Cable Sizing Calculator
Free online tool — no signup required

Lead Electrical & Instrumentation Engineer
18+ years of experience in electrical engineering at large-scale mining operations. Specializing in power systems design, cable sizing, and protection coordination across BS 7671, IEC 60364, NEC, and AS/NZS standards.
Related Articles
Your First Cable Sizing Calculation: A Tutorial for Junior Engineers
Step-by-step cable sizing tutorial for junior engineers. Walk through a real 22kW motor circuit from design current to voltage drop verification, with every number shown and every step explained.
AS/NZS 3008.1.1:2017 — Understanding the Cable Sizing Tables (Appendix A vs B)
A deep dive into AS/NZS 3008.1.1:2017 cable sizing tables — installation methods (Table 3), current ratings (Tables 13-14), derating factors (Tables 22, 25, 27, 28), and the critical difference between Appendix A and Appendix B approaches.
Understanding Power Factor Correction: A Tutorial with Worked Calculations
Learn how to calculate capacitor bank sizing for power factor correction. Includes the power triangle, kVAR calculation, before-and-after current comparison, harmonic considerations, and IEC 60831 capacitor selection.