Skip to main content
All Comparisons
COMPARISON

Maximum Demand: The 20-Unit Apartment Block — 14% Gap Between Standards

20 apartments at 10kW each. NEC says 95kW design load. IEC says 115kW. That 14% gap changes your transformer size, main switch rating, and project cost.

KholisFebruary 27, 20269 min read

Maximum demand calculation is where engineering standards diverge the most — not because the physics differs, but because the statistical assumptions about human behaviour differ between countries. How much of a building's installed load will actually be used simultaneously? The answer depends on where you are.

The Scenario

A residential apartment building:

  • 20 apartments, each with 10kW installed load (oven, hot water, general power, lighting, A/C)
  • Common areas: 15kW (lifts, corridor lighting, fire systems, car park ventilation)
  • Supply voltage: 400V three-phase
  • No gas heating — all-electric building

Total installed load: 20 × 10kW + 15kW = 215kW

Nobody expects all 20 apartments to draw maximum load simultaneously at 10pm on a weeknight. The question is: what fraction of that 215kW should we design the supply for?

Side-by-Side Results

Scenario

20 apartments × 10kW each + 15kW common areas, 400V three-phase, all-electric

ParameterAS/NZSBS 7671IEC 60364NEC
Diversity method
Table C1 lookupPrescriptive diversity factorsAS/NZS 3000, Table C1Engineer judgmentNo prescriptive diversity tableBS 7671, Appendix AAnnex A factorsGuideline diversity valuesIEC 60364-3, Annex AArticle 220 OptionalDemand factor tablesNEC 220.84
Diversity factor (apartments)
52%Table C1 for 20 unitsAS/NZS 3000, Table C150-60%Typical engineering estimateCIBSE Guide, ACE 11455%For 20 dwellingsIEC 60364-3, Annex A40%Optional method for dwellingsNEC 220.84
Common area demand
15kW (100%)Common loads at full demand15kW (100%)Essential loads at full demand15kW (100%)Common loads at full demand15kW (100%)House loads at full demand
Design maximum demand
119kW200 × 0.52 + 15110-130kWEngineer's assessment range125kW200 × 0.55 + 1595kW200 × 0.40 + 15
Supply current (A) at 400V
172A119k / (√3 × 400)159-188ARange based on judgment180A125k / (√3 × 400)137A95k / (√3 × 400)
Transformer size
200kVANext standard size up from 119kW200kVAConservative selection200kVANext standard size up from 125kW150kVA95kW at 0.85 PF = 112kVA
Main switch rating
200AStandard frame size200AStandard frame size200AStandard frame size150AOr 200A if derated
Most conservative: IEC 60364 (125kW design demand — highest diversity factor)
Run this comparison yourself
Standards agreeModerate differenceSignificant difference

Why the Numbers Differ

Different Statistical Bases

Each standard's diversity factors are derived from different population studies:

AS/NZS 3000 (Table C1): Based on Australian Bureau of Statistics energy surveys and utility metering data from Australian distribution networks. Reflects Australian living patterns — high air conditioning use in summer, relatively low heating loads (mild climate in most population centres).

IEC 60364 (Annex A): Based on European metering data, primarily from continental European countries. Reflects higher heating loads (colder climates) and different appliance usage patterns.

NEC Article 220: Based on US utility data. The Optional Method in Article 220.84 uses a demand factor that reflects American building patterns — larger dwellings on average, different HVAC profiles, and 120V/240V split-phase supply.

BS 7671: Deliberately does not provide a prescriptive diversity table. The IET Wiring Regulations leave diversity assessment to the designer's judgment, supplemented by guidance documents (ACE 114, CIBSE Guide). This is philosophically different — the standard trusts the engineer rather than prescribing a value.

Why BS 7671 Has No Diversity Table

The British approach is that diversity depends on the specific building, its occupancy, and its equipment. A luxury apartment with underfloor heating, a home gym, and an EV charger has a fundamentally different demand profile than a social housing unit. One table cannot capture this variation — so BS 7671 expects the engineer to assess each project individually.

The NEC Optional Method

NEC 220.84 is notably permissive. For dwelling units served by a single feeder or service:

  • First 10kVA at 100%
  • Remainder at 40%

This produces the lowest design demand of any standard. The reasoning: American homes are typically larger with more installed load per dwelling, but the actual simultaneous usage (as measured by utilities) is proportionally lower. Americans have more installed capacity than they use simultaneously.

What About Electric Vehicles?

None of the traditional diversity tables account for EV charging. A 7kW EV charger per apartment adds 140kW of installed load — and if all residents arrive home at 6pm and plug in, the actual diversity may be much higher than historical tables suggest.

ScenarioTraditional Max DemandWith 20 × 7kW EVImpact
AS/NZS (52%)119kW119 + (140 × 0.5) = 189kW+59%
NEC (40%)95kW95 + (140 × 0.4) = 151kW+59%
IEC (55%)125kW125 + (140 × 0.45) = 188kW+50%

All standards are currently updating their diversity guidance for EV charging. AS/NZS 3000:2018 Amendment 2 includes specific EV diversity provisions. NEC 2023 added Article 625 requirements. BS 7671 Annex F provides EV demand factors.

EV Charging Changes Everything

A 20-unit apartment block designed in 2020 with a 200kVA supply may need 315kVA when all units get EV chargers. Transformer replacement costs $50,000-$100,000. Design new buildings with EV capacity from day one.

Cost Impact of Getting It Wrong

Undersizing (Using Too-Low Diversity)

If the NEC 40% factor is applied to a building where actual demand is closer to IEC's 55%:

  • 150kVA transformer overloads → reduced lifespan, possible failure
  • Main cable overheats → voltage drop issues, potential fire risk
  • Network operator supply rejection — utility will not connect an undersized installation

Oversizing (Using Too-High Diversity)

If the IEC 55% factor is applied where NEC's 40% is more realistic:

  • 200kVA transformer instead of 150kVA → $15,000 extra cost
  • Larger main cable → $5,000 extra
  • Higher standing charges from the utility for maximum demand tariff

Neither error is harmless, but undersizing has safety consequences while oversizing only has cost consequences. This is why most prudent designers round up.

Practical Guidance

  1. Use the standard required by your jurisdiction — not the one that gives the cheapest answer
  2. For international projects, IEC 60364 Annex A is a reasonable middle ground
  3. Never use NEC diversity factors for non-US buildings — American usage patterns don't transfer
  4. Include EV charging capacity in any new residential design, regardless of current demand
  5. Measure actual demand on similar existing buildings if possible — real data beats any table

Key Takeaways

  1. 14% difference between NEC (95kW) and IEC (125kW) for the same 20-unit building
  2. NEC is most permissive (40% diversity) — produces the smallest supply requirement
  3. IEC is most conservative (55% diversity) — produces the largest supply
  4. BS 7671 avoids prescriptive tables entirely — trusts the engineer
  5. EV charging invalidates all historical diversity tables — design for the future

Try the Maximum Demand Calculator

Free online tool — no signup required

Open Calculator
Kholis

Kholis

Lead Electrical & Instrumentation Engineer

18+ years of experience in electrical engineering at large-scale mining operations. Specializing in power systems design, cable sizing, and protection coordination across BS 7671, IEC 60364, NEC, and AS/NZS standards.

18+ years electrical engineering experienceLead E&I Engineer at major mining operationECalPro founder & developer