What Are BS 7671 Correction Factors?

BS 7671 current-carrying capacity tables (4D1A through 4D5A) are calculated under specific reference conditions: 30°C ambient air temperature, single circuit, no thermal insulation contact. When actual installation conditions differ from these references, correction factors (also called derating factors or rating factors) must be applied to adjust the effective cable capacity.

The correction factors are multiplicative — they are combined into a single overall factor that reduces (or occasionally increases) the cable’s usable current rating. The four main correction factors in BS 7671 are:

  • Ca — Ambient temperature correction (Tables 4B1, 4B2)
  • Cg — Grouping correction (Tables 4C1–4C5)
  • Ci — Thermal insulation correction (Regulation 523.7)
  • Cc — Protective device correction (Table 4B3, BS 3036 fuses only)

The required tabulated current rating is calculated as:

It = In / (Ca × Cg × Ci × Cc)

where In is the nominal rating of the protective device and It is the minimum tabulated current rating the cable must have.

Ca — Ambient Temperature Correction Factor

Table 4B1 provides correction factors for ambient air temperatures different from the 30°C reference. Table 4B2 provides equivalent factors for ground temperatures different from the 20°C reference (used for buried cables, Methods D1/D2).

Table 4B1 — Air temperature correction factors (selected values):

Ambient Temp (°C)70°C PVC90°C XLPE
251.031.02
301.001.00
350.940.96
400.870.91
450.790.87
500.710.82
550.610.76
600.500.71

Key insight: At 50°C ambient, a PVC cable loses 29% of its capacity (Ca = 0.71), while an XLPE cable loses only 18% (Ca = 0.82). This is because XLPE has a larger temperature headroom — the difference between its maximum operating temperature (90°C) and the ambient is greater.

Below 30°C: When the ambient temperature is below 30°C, Ca > 1.0, which effectively increases the cable’s usable rating. In the UK, where ambient rarely exceeds 30°C, this is common — but the table values should only be used for uprating if the lower ambient can be guaranteed throughout the cable’s life.

Cg — Grouping Correction Factor

When multiple circuits or cables share the same enclosure, tray, or route, mutual heating reduces each cable’s effective current capacity. Tables 4C1 through 4C5 provide grouping factors for different arrangements:

Table 4C1 — Cables bunched in conduit, trunking, or on a surface (selected values):

Number of CircuitsBunched (enclosed or clipped)Single layer on wall or floorSingle layer on perforated tray
11.001.001.00
20.800.850.88
30.700.790.82
40.650.750.77
50.600.730.75
60.570.720.73
70.540.720.73
80.520.710.72
90.500.700.72
120.450.700.70
160.410.700.70
200.380.700.70

Grouping has the largest impact of all correction factors in typical installations. With 6 circuits bunched in a conduit, the cable capacity is reduced by 43% (Cg = 0.57). This often drives cable sizes up significantly.

Practical tip: Where possible, space circuits on separate trays or use perforated cable tray instead of trunking. The grouping factors for spaced cables on perforated tray are considerably more favourable than for bunched cables in enclosed trunking.

Ci — Thermal Insulation Correction Factor

When a cable is enclosed in or in contact with thermal insulation (such as building insulation in walls, ceilings, or floors), heat dissipation is severely restricted. Regulation 523.7 specifies:

ConditionCi Factor
Cable enclosed in thermal insulation on one side0.75
Cable enclosed in thermal insulation on all sides (< 0.5 m length)0.89
Cable enclosed in thermal insulation on all sides (0.5–1.0 m)0.63
Cable enclosed in thermal insulation on all sides (> 1.0 m)0.50

A cable totally surrounded by thermal insulation for a length exceeding 1 metre has its capacity halved (Ci = 0.50). This is a severe derating and is a common issue in modern energy-efficient buildings with extensive insulation.

Where the length in insulation is less than 0.5 m (such as a cable passing through an insulated stud wall), the factor is less severe at 0.89. Engineers should always try to minimise the length of cable enclosed in thermal insulation.

Cc — Protective Device Correction Factor

The correction factor Cc applies only when the circuit is protected by a BS 3036 semi-enclosed (rewirable) fuse. These fuses have a higher fusing factor (1.9 × rating) compared to modern BS 88 HRC fuses or MCBs (typically 1.45 × rating), meaning the cable must be able to carry a higher current before the fuse operates.

For BS 3036 fuses: Cc = 0.725.

For all other protective devices (MCBs, RCBOs, BS 88 fuses): Cc = 1.0 (no correction needed).

In modern installations, BS 3036 fuses are rarely used in new work, so Cc is typically 1.0. However, when working on older installations that still have rewirable fuses, this factor must be applied.

Combining Multiple Correction Factors

When multiple correction factors apply, they are multiplied together to give the overall correction factor. The combined factor can result in a very significant increase in the required cable size:

Example: Cable in conduit on wall, 40°C ambient, 4 grouped circuits, BS 3036 fuse

  Ca = 0.87  (Table 4B1, 40°C, PVC)
  Cg = 0.65  (Table 4C1, 4 circuits bunched)
  Ci = 1.00  (no thermal insulation)
  Cc = 0.725 (BS 3036 fuse)

  Overall factor = 0.87 × 0.65 × 1.00 × 0.725 = 0.410

  For a 32 A circuit: It = 32 / 0.410 = 78.1 A

  Without derating, a 10 mm² cable (57 A in Method B1) would suffice.
  With derating, a 25 mm² cable (101 A in Method B1) is needed.

  The combined derating increased the required cable by 2.5 sizes.

This demonstrates why it is critical to account for all applicable derating factors. Omitting even one factor can result in an undersized cable that may overheat under normal operating conditions.

Try the Cable Sizing Calculator

Put this methodology into practice. Calculate results with full standard clause references — free, no sign-up required.

Or embed this calculator on your site
Calculate Cable Sizing

Frequently Asked Questions

The grouping factor (Cg) is the most commonly overlooked correction factor. Engineers often calculate the design current and look up a cable size directly from Table 4D1A without considering that other circuits in the same conduit or tray cause mutual heating. In commercial installations with multiple circuits sharing trunking, the grouping factor can reduce capacity by 30-50%.
Yes. Below 30°C, the correction factor Ca is greater than 1.0, which effectively increases the cable's usable rating. For example, at 25°C for PVC cable, Ca = 1.03. However, you should only use an uprating factor if you can guarantee the temperature will remain below 30°C for the cable's entire service life — which may be 25-40 years.
BS 7671 and AS/NZS 3008 both derate for thermal insulation, but the values differ. BS 7671 uses fixed factors based on the length enclosed (0.50 for >1 m on all sides), while AS/NZS 3008 Clause 3.3.4 uses similar principles but with different numerical values reflecting Australian building practices. Both standards treat total enclosure as the worst case.

Related Resources