BS 7671 Regulation 525: Voltage Drop Limits
BS 7671 Regulation 525 voltage drop limits explained — 3% lighting, 5% other loads, mV/A/m method. Includes Tables 4Ab, 4E1A-4E4A reference and worked examples.
What Is Regulation 525?
Regulation 525 of BS 7671:2018+A2 sets the maximum permissible voltage drop between the origin of an electrical installation and any point of utilisation. Excessive voltage drop causes reduced equipment performance, dimming of lighting, overheating of motors, and potential nuisance tripping of sensitive electronics.
The regulation applies to all circuits in a low-voltage installation and requires the designer to verify that the voltage at the terminals of every item of current-using equipment is sufficient for it to operate safely and effectively.
Voltage drop verification is the final step in cable sizing: after selecting a cable based on current-carrying capacity and derating factors, the designer must confirm that the selected cable does not exceed the voltage drop limits specified in Table 4Ab.
Voltage Drop Limits — Table 4Ab
Table 4Ab in BS 7671 Appendix 4 specifies the maximum voltage drop for different supply types and load categories:
| Supply Type | Lighting (%) | Other Uses (%) |
|---|---|---|
| Public supply (DNO connection) | 3% | 5% |
| Private supply (generator, UPS) | 6% | 8% |
For a standard 230 V single-phase supply from the public network:
- Lighting circuits: Maximum 3% = 6.9 V
- Power circuits: Maximum 5% = 11.5 V
For a 400 V three-phase supply:
- Lighting circuits: Maximum 3% = 12 V
- Power circuits: Maximum 5% = 20 V
The higher limits for private supplies recognise that the generator or UPS voltage can be adjusted at the source to compensate for voltage drop in the distribution system.
The mV/A/m Method
BS 7671 uses the mV/A/m method (millivolts per ampere per metre) for voltage drop calculations. Tables 4E1A through 4E4A provide voltage drop values in mV/A/m for each cable type and size:
| Table | Cable Type |
|---|---|
| 4E1A | Single-core PVC/thermoplastic cables |
| 4E2A | Multicore PVC/thermoplastic cables |
| 4E3A | Single-core XLPE/thermosetting cables |
| 4E4A | Multicore XLPE/thermosetting cables |
The voltage drop calculation formula is:
Single-phase: VD = (mV/A/m × Ib × L) / 1000
Three-phase: VD = (mV/A/m × Ib × L) / 1000
where:
- mV/A/m = voltage drop value from the appropriate Table 4E
- Ib = design current of the circuit in amperes
- L = route length of the cable in metres (one way, not return)
- VD = voltage drop in volts
The percentage voltage drop is then: VD% = (VD / U0) × 100, where U0 is the nominal supply voltage (230 V single-phase or 400 V three-phase).
Worked Example — Voltage Drop Verification
A 32 A single-phase power circuit uses 6 mm² multicore PVC copper cable (Method C, clipped direct) with a cable run length of 35 m.
Step 1: Look up mV/A/m from Table 4E2A
6 mm² multicore PVC copper = 7.3 mV/A/m
Step 2: Calculate voltage drop
VD = (7.3 × 32 × 35) / 1000
VD = 8,176 / 1000
VD = 8.18 V
Step 3: Calculate percentage
VD% = (8.18 / 230) × 100 = 3.56%
Step 4: Compare with limit
Power circuit limit = 5%
3.56% ≤ 5% √ PASS
If this were a lighting circuit:
3.56% > 3% × FAIL — would need to increase cable to 10 mm²
This example shows why voltage drop can sometimes be the governing factor in cable selection, especially for long cable runs. The 6 mm² cable is adequate for current capacity (46 A in Method C vs 32 A required) but is marginal on voltage drop for lighting circuits.
Submain Plus Final Circuit Voltage Drop
In installations with distribution boards fed by submains, the total voltage drop is the sum of the submain drop and the final circuit drop. Both must be within the overall limits of Table 4Ab.
There are two common approaches to allocating the voltage drop budget:
- Even split: Allocate roughly equal percentages to the submain and final circuit. For a 5% limit: 2.5% each.
- Proportional: Allocate based on expected cable lengths. Longer submains may need 3% while shorter final circuits take 2%.
Example: 400 V three-phase submain + 230 V single-phase final circuit
Submain: 70 mm² XLPE, 50 m, 200 A design current
mV/A/m = 0.55 (Table 4E3A, three-phase)
VD = (0.55 × 200 × 50) / 1000 = 5.5 V
VD% = (5.5 / 400) × 100 = 1.38%
Final circuit: 6 mm² PVC, 25 m, 32 A
mV/A/m = 7.3 (Table 4E2A, single-phase)
VD = (7.3 × 32 × 25) / 1000 = 5.84 V
VD% = (5.84 / 230) × 100 = 2.54%
Total VD% = 1.38% + 2.54% = 3.92% ≤ 5% √ PASSReactance Component for Large Cables
For cable sizes above approximately 25 mm², the inductive reactance of the cable becomes significant and cannot be ignored. Tables 4E1A–4E4A provide separate columns for the resistive (r) and reactive (x) components of voltage drop.
For circuits with a power factor less than unity, the voltage drop is calculated using:
VD = Ib × L × (r × cosφ + x × sinφ) / 1000
where cosφ is the circuit power factor. For resistive loads (power factor = 1.0), the reactive term drops out and the calculation simplifies to using only the ‘r’ column. For motor loads with power factor 0.8, the reactive component can add 10–20% to the voltage drop for large cables.
For cables 16 mm² and below, the reactance is negligible and the single mV/A/m value from the tables is sufficiently accurate for most installations.
Try the Voltage Drop Calculator
Put this methodology into practice. Calculate results with full standard clause references — free, no sign-up required.
Or embed this calculator on your siteFrequently Asked Questions
Related Resources
Voltage Drop Calculator
Automated voltage drop calculation to BS 7671 with mV/A/m lookup and compliance verification.
Read moreBS 7671 Table 4D1A: Current Ratings
Current-carrying capacity table for single-core PVC cables — the first step before voltage drop verification.
Read moreBS 7671 Appendix 4: Correction Factors
Derating factors that must be applied before selecting a cable for voltage drop verification.
Read moreCable Sizing Calculator
Complete cable sizing with integrated current rating and voltage drop checks to BS 7671.
Read more