Skip to main content

Voltage Drop Calculation Guide — Formulas, Methods & Limits

How to calculate voltage drop in electrical cables using AS/NZS 3008, BS 7671, IEC 60364, and NEC methods. Covers the mV/A/m method, AC impedance, power factor effects, worked examples, and allowable limits by standard.

Multi-Standard14 min readUpdated February 21, 2026
Share:

Introduction

Voltage drop is the reduction in voltage along a cable caused by the cable's electrical impedance. When current flows through a conductor, the cable's resistance and reactance consume a portion of the supply voltage, delivering less voltage to the load than is available at the source.

Excessive voltage drop causes real problems: motors lose torque and overheat, lighting dims or flickers, electronic control equipment malfunctions, and energy is wasted as heat in the cable. Every major electrical standard sets maximum permissible limits, and voltage drop verification is a mandatory step in any cable sizing calculation.

This guide covers the fundamental voltage drop formulas, the practical mV/A/m tabulated method used by most standards, allowable limits across AS/NZS 3008, BS 7671, IEC 60364, and NEC, and a complete worked example demonstrating the calculation process.

Voltage Drop Formulas

The voltage drop across a cable depends on the current, cable length, and cable impedance. The impedance has two components: resistance (R) which dissipates energy as heat, and reactance (X) which stores and releases energy in the cable's magnetic field.

Single-phase AC circuits:

ΔV = 2 × I × L × (R×cosφ + X×sinφ) / 1000 — (Eq. 1)

Three-phase AC circuits:

ΔV = √3 × I × L × (R×cosφ + X×sinφ) / 1000 — (Eq. 2)

DC circuits:

ΔV = 2 × I × R × L / 1000 — (Eq. 3)

Where:

SymbolDescriptionUnit
ΔVVoltage dropV
IDesign current (load current)A
LCable route length (one way)m
RAC resistance of conductormΩ/m
XReactance of cablemΩ/m
cosφPower factor of the load
sinφReactive factor (= √(1 − cos²φ))

The factor of 2 in the single-phase and DC formulas accounts for the go-and-return path (current flows out on the active conductor and returns via the neutral or negative conductor). The √3 factor in the three-phase formula arises from the 120° phase displacement between the three conductors.

Note: For DC circuits, reactance is zero, so the formula simplifies to a pure resistance calculation. For AC circuits at 50/60 Hz with small cable sizes (<25 mm²), reactance is typically small compared to resistance and can sometimes be neglected for rough estimates, but should always be included for accurate calculations.

The mV/A/m Tabulated Method

Rather than looking up separate R and X values and applying the full impedance formula, most standards provide pre-calculated voltage drop values in millivolts per ampere per metre (mV/A/m). This tabulated approach combines resistance, reactance, and the circuit configuration (single-phase or three-phase) into a single lookup value.

Simplified voltage drop formula:

ΔV = mV/A/m × I × L / 1000 — (Eq. 4)

The mV/A/m values are tabulated for specific cable types, sizes, and installation conditions. The key voltage drop tables in each standard are:

StandardTablesOrganisation
AS/NZS 3008Tables 30–42By cable type (V-75, V-90, X-90) and conductor (Cu, Al)
BS 7671Tables 4E1A–4E4ABy cable type (PVC, XLPE) and cores (2-core, 3/4-core)
IEC 60364Tables B.52.11–B.52.12By installation method and insulation type
NECChapter 9, Table 9AC resistance and reactance by conduit type (PVC, steel, Al)

Most tables provide separate columns for resistive (R) and reactive (X) components, allowing you to calculate the effective impedance at any power factor:

mV/A/m = mV/A/mR × cosφ + mV/A/mX × sinφ — (Eq. 5)

Some tables (notably AS/NZS 3008 Tables 35–42) provide a single combined column for unity power factor (cosφ = 1), which is conservative for most loads since resistive voltage drop dominates at typical cable sizes.

Temperature correction: The mV/A/m values in standard tables are given at a reference conductor temperature (typically 75°C for PVC cables in service). If the cable operates at a different temperature, the resistance component should be adjusted. AS/NZS 3008 Clause 4.5.1 provides a method for this correction.

Maximum Allowable Voltage Drop by Standard

Each electrical standard specifies maximum permissible voltage drop limits, typically expressed as a percentage of the nominal supply voltage. These limits represent the maximum acceptable voltage loss between the origin of the installation and the point of utilisation.

StandardLighting CircuitsPower CircuitsTotal (Origin to Load)Reference
AS/NZS 30003%5%5% totalClause 3.6.2, Table 3.2
BS 76713%5%See noteTable 4Ab, Appendix 4
IEC 60364-5-523%5%Clause 525
NEC/NFPA 703%3%5% total210.19(A) FPN No. 4, 215.2(A) FPN No. 2
BS 7671 note: Table 4Ab gives two sets of values depending on whether the installation is public supply (3% lighting / 5% other) or private supply such as a generator (6% lighting / 8% other). The higher limits for private supply recognise that the supply voltage can be adjusted at the generator.

In the NEC, the 3% and 5% values are informational notes (not enforceable requirements), but they are universally adopted as best practice. Local authorities having jurisdiction (AHJ) may enforce them as requirements.

For installations with a sub-distribution board, the total voltage drop is split between the feeder (origin to sub-board) and the final circuit (sub-board to load). A common design rule is to allocate half the total budget to each section — for example, 2.5% feeder + 2.5% final circuit = 5% total under AS/NZS 3000.

Factors Affecting Voltage Drop

Several factors influence the magnitude of voltage drop in a cable installation:

  • Cable length: Voltage drop is directly proportional to length. Doubling the cable run doubles the voltage drop. This is the single most significant factor for long installations.
  • Load current: Voltage drop is directly proportional to current. Higher loads produce proportionally higher voltage drops.
  • Conductor cross-section: Larger cables have lower resistance per metre. Doubling the cable cross-section roughly halves the resistive voltage drop.
  • Conductor material: Copper has a resistivity of approximately 17.2 nΩ·m at 20°C, while aluminium is approximately 28.3 nΩ·m — about 1.64× higher. Aluminium cables therefore have approximately 64% higher voltage drop than equivalent copper cables of the same cross-section.
  • Power factor: At lower power factors, the reactive component of voltage drop becomes more significant. For highly inductive loads (motors, transformers), the reactive voltage drop can be comparable to or exceed the resistive component, particularly for larger cable sizes where reactance is relatively higher.
  • Conductor temperature: Resistance increases with temperature. A cable operating at 75°C has approximately 20% higher resistance than the same cable at 20°C. Most tabulated mV/A/m values are given at the cable's operating temperature, not ambient temperature.
  • Cable construction: Single-core cables in trefoil formation have different reactance than flat-spaced cables. Steel-wire-armoured (SWA) cables have higher reactance than unarmoured cables due to the magnetic effect of the steel armouring.

Worked Example: 3-Phase Motor Circuit

Calculate the voltage drop for a three-phase motor circuit with the following parameters:

ParameterValue
Supply voltage415 V (3-phase)
Load current63 A
Cable type4-core Cu/XLPE/SWA
Cable size (from current rating calculation)16 mm²
Route length50 m
Power factor0.85 lagging
StandardBS 7671:2018+A2

Step 1: Look up mV/A/m values

From BS 7671 Table 4E4A, Column 3 (4-core XLPE/SWA), for 16 mm²:

  • mV/A/m (resistive component, r) = 2.8
  • mV/A/m (reactive component, x) = 0.170

Step 2: Calculate effective mV/A/m at load power factor

cosφ = 0.85, therefore sinφ = √(1 − 0.85²) = 0.527

mV/A/meff = 2.8 × 0.85 + 0.170 × 0.527 = 2.380 + 0.090 = 2.470

Step 3: Calculate voltage drop

ΔV = 2.470 × 63 × 50 / 1000 = 7.78 V

Step 4: Calculate percentage voltage drop

ΔV% = 7.78 / 415 × 100 = 1.87%

Result: The voltage drop is 1.87%, which is well within the BS 7671 limit of 5% for power circuits. ✓ PASS

If the voltage drop had exceeded 5%: The solution would be to increase the cable size to the next standard size (25 mm²), which has lower impedance and therefore lower voltage drop. The current rating check would then need to be re-verified to ensure the larger cable is still compatible with the protective device.

Voltage Drop in Long Cable Runs

For cable runs exceeding approximately 50 metres, voltage drop frequently becomes the governing factor for cable selection rather than current-carrying capacity. This is common in:

  • Rural and agricultural installations with long overhead or underground runs
  • Large commercial buildings with distant sub-distribution boards
  • Industrial plants with motor control centres far from the main switchboard
  • Mining and tunnelling installations
  • Solar PV string cables running from arrays to the inverter

Strategies to manage voltage drop in long cable runs include:

  1. Increase cable size: The most straightforward solution, though it increases cost and may require larger containment systems.
  2. Increase supply voltage: Moving from 230/400 V to 415/690 V distribution reduces current for the same power, significantly reducing voltage drop. Common in industrial installations.
  3. Relocate the distribution board: Positioning the switchboard closer to the major loads reduces the longest cable run.
  4. Use a local transformer: For very long distances, stepping up to medium voltage (e.g., 11 kV) for the cable run and stepping back down at the load end virtually eliminates the voltage drop problem.
  5. Power factor correction: Installing capacitors at the motor terminals improves power factor and reduces the reactive component of voltage drop. This is particularly effective for large motor loads.

When voltage drop governs cable size, the resulting cable is larger than needed purely for current capacity. This provides extra thermal margin, which can be beneficial in installations with variable loading or future load growth.

Automating Voltage Drop Calculations

Voltage drop calculations involve multiple lookup steps and factor adjustments that benefit from automation. A reliable calculation workflow should:

  • Look up the correct mV/A/m values from the applicable standard's impedance tables
  • Apply temperature correction where required
  • Calculate voltage drop using the full impedance method (R×cosφ + X×sinφ)
  • Compare the result against the applicable standard's limit
  • Clearly indicate pass/fail status with the exact percentage and absolute voltage drop
  • Document all intermediate calculation steps with specific standard references

Each standard uses different impedance tables and voltage drop limits. Professional tools should handle the correct table selection automatically when switching between AS/NZS 3008, BS 7671, IEC 60364, and NEC.

Try the Voltage Drop Calculator

Put this methodology into practice. Calculate results with full standard clause references — free, no sign-up required.

Or embed this calculator on your site
Calculate Voltage Drop

Frequently Asked Questions

Most standards allow up to 5% total voltage drop from the origin of the installation to the furthest point of utilisation. For residential circuits in Australia/New Zealand (AS/NZS 3000), the limit is 5% for power circuits and 3% for lighting. In the UK (BS 7671), it is 5% for power and 3% for lighting from public supply. In practice, well-designed residential installations achieve 2-3% total voltage drop.
The most common approach is to increase the cable cross-sectional area to the next standard size, which reduces the cable's resistance per metre. Other strategies include: increasing the supply voltage (e.g., 400V to 690V for industrial), relocating the distribution board closer to loads, using power factor correction capacitors at the load, or for very long distances, using a medium-voltage feeder with a local step-down transformer.
Yes. The total voltage drop has both resistive (proportional to R×cosφ) and reactive (proportional to X×sinφ) components. At lower power factors, the reactive component becomes more significant. However, for most cable sizes below 50 mm², resistance dominates over reactance, so the power factor effect is relatively small. For large cable sizes (95 mm² and above), reactance can be comparable to resistance, making power factor correction more beneficial for reducing voltage drop.

Related Resources