Skip to main content

Cable Sizing Calculator per SANS 10142-1 (IEC 60364) for South Africa

SANS 10142-1 (IEC 60364)Edition 2.2:2019South Africa

Cable sizing in South Africa follows SANS 10142-1:2019 (The Wiring of Premises), based on IEC 60364. Engineers select conductor sizes using SANS 10142 current-carrying capacity tables, apply derating factors for South African ambient temperatures (25-40 °C depending on region), and verify voltage drop at 230 V single-phase / 400 V three-phase, 50 Hz Eskom supply.

Quick Reference Table

South Africa Cable Sizing Key References — SANS 10142SANS 10142-1 (IEC 60364) (Edition 2.2:2019)
ParameterValue / RequirementClause Reference
National standardSANS 10142-1:2019 — The Wiring of PremisesSANS 10142-1, Clause 1
Supply voltage230 V single-phase / 400 V three-phase (Eskom)SANS 10142-1, Clause 6.2
Frequency50 HzSANS 10142-1, Clause 6.2
Current-carrying capacityBased on IEC 60364-5-52 with SA amendmentsSANS 10142-1, Table 10.1
Voltage drop limit5% from the point of supply to any point of useSANS 10142-1, Clause 6.12.1
Ambient temperature range25 °C coastal, 30-35 °C inland, 40 °C+ in Limpopo/Northern CapeSANS 10142-1, Table 10.4
Load shedding considerationsInverter/battery backup circuits — separate DB with changeoverSANS 10142-1, Amendment 1
Common conductor sizes1.5, 2.5, 4, 6, 10, 16, 25 mm²SANS 10142-1, Table 10.1

How to Calculate Cable Sizing for South Africa

  1. 1

    Calculate load per SANS 10142

    Determine design current per SANS 10142-1 maximum demand calculations. For residential, apply diversity factors from Table 3.1. Include solar PV and battery backup loads if applicable.

  2. 2

    Select cable type per SABS standards

    Choose cable insulation — PVC (SANS 1507) or XLPE (SANS 1339). South African cables must carry the SABS mark. For solar installations, use UV-resistant PV cables per SANS 62930.

  3. 3

    Apply South African derating factors

    Apply ambient temperature correction from SANS 10142-1 Table 10.4. South Africa's diverse climate means design ambient varies: Cape Town 25 °C, Johannesburg 30 °C, Musina 40 °C. Apply grouping factors for bundled circuits.

  4. 4

    Select conductor size from SANS tables

    Choose minimum conductor size from SANS 10142-1 Table 10.1 after derating. For circuits protected by MCBs, verify that the cable ampacity exceeds the MCB rating per Clause 7.12.

  5. 5

    Verify voltage drop per SANS 10142

    Check total voltage drop from Eskom supply point stays within 5% (11.5 V at 230 V). South African residential plots can be large (1,000+ m² in suburbs), making voltage drop a real concern for outbuildings.

Try the Cable Sizing Calculator

Run compliant SANS 10142-1 (IEC 60364) calculations for south africa — free, instant results with full clause references.

Calculate Cable Sizing Now

Frequently Asked Questions

South Africa uses SANS 10142-1:2019 (The Wiring of Premises), which is based on IEC 60364 with South African amendments. It is published by SABS and is a mandatory standard — all electrical work must be done by registered electricians and issued with a Certificate of Compliance (CoC).
Load shedding has driven massive adoption of inverter/battery/solar installations. These require separate distribution boards with changeover switches per SANS 10142-1 Amendment 1. The battery-backed circuits need properly sized cables considering both grid and inverter supply, with attention to DC cable sizing for battery connections.
Standard Eskom prepaid connections are 60 A or 80 A single-phase. A 60 A connection requires 16 mm² copper from the meter to the main distribution board. An 80 A connection needs 25 mm². These sizes assume short runs; longer distances may require upsizing for voltage drop per SANS 10142-1 Clause 6.12.

Related Guides