Skip to main content

IEC 60364 Table B.52: Cable Current Ratings

IEC 60364-5-52 Table B.52 explained — current-carrying capacity for PVC and XLPE cables across installation methods A1 to G. Reference table with common sizes.

IEC 6036411 min readUpdated March 19, 2026
Share:

What Is IEC 60364 Table B.52?

Table B.52 in IEC 60364-5-52 (Annex B) provides the current-carrying capacity of cables installed according to the reference installation methods defined in Table B.52.1. It is the international equivalent of BS 7671 Tables 4D1A–4D5A and forms the basis for cable sizing in countries that adopt IEC standards directly.

The table series covers:

  • Table B.52.2: Current ratings for PVC insulated cables (maximum conductor temperature 70°C)
  • Table B.52.3: Current ratings for XLPE insulated cables (maximum conductor temperature 90°C)
  • Table B.52.4: Current ratings for mineral insulated cables

All values are calculated under reference conditions: 30°C ambient air temperature, 20°C ground temperature, soil thermal resistivity of 2.5 K·m/W, and a single loaded circuit. When actual conditions differ, correction factors from Tables B.52.14 through B.52.21 must be applied.

Installation Methods (Table B.52.1)

IEC 60364-5-52 defines reference installation methods using an alphanumeric code system. Each method represents a specific physical arrangement with characteristic heat dissipation properties:

MethodDescriptionHeat Dissipation
A1Insulated conductors in conduit in a thermally insulated wallPoorest — lowest ratings
A2Multicore cable in conduit in a thermally insulated wallPoor
B1Insulated conductors in conduit on a wallModerate
B2Multicore cable in conduit on a wallModerate
CMulticore cable on a wooden wall (clipped direct)Good
D1Multicore cable in ducts in the groundDepends on soil
D2Multicore cable direct in the groundDepends on soil
EMulticore cable in free air on horizontal perforated trayVery good
FSingle-core cables touching in free air on trayVery good
GSingle-core cables spaced in free airBest — highest ratings

These method codes are shared with BS 7671 (which is derived from IEC 60364), making cross-referencing between the two standards straightforward. However, the specific current rating values may differ slightly due to differences in cable constructions covered by each standard.

Reference Current Ratings — PVC Copper (Table B.52.2)

The following table shows current-carrying capacity values for copper conductors with PVC insulation (70°C) in two-loaded-conductor configurations under IEC reference conditions:

Size (mm²)A1 (A)A2 (A)B1 (A)B2 (A)C (A)E (A)F (A)
1.514.51417.516.519.52224
2.519.518.52423273033
426253230364045
634324138465157
1046435752637076
16615776698594101
25807510190112119131
359992125111138148162
50119110151133168180196
70151139192168213232251
95182167232201258282304
120210192269232299328352
150240219300258344379406
185273248341294392434463
240320291400344461514546

Note: For three-phase circuits with three loaded conductors, the values differ slightly. The table above shows the two-loaded-conductor (single-phase or DC) configuration. Always verify which conductor loading applies to your circuit.

XLPE vs PVC Current Ratings (Table B.52.3 vs B.52.2)

XLPE (cross-linked polyethylene) insulated cables operate at a maximum conductor temperature of 90°C compared to 70°C for PVC, giving them significantly higher current-carrying capacity for the same cross-sectional area:

Size (mm²)PVC 70°C — Method C (A)XLPE 90°C — Method C (A)Increase (%)
1.519.523+18%
43642+17%
106376+21%
25112138+23%
50168209+24%
95258325+26%
150344435+26%
240461590+28%

The advantage of XLPE increases with cable size because larger cables are more thermally constrained. For cables above 50 mm², XLPE provides approximately 25% more capacity — which can mean a reduction of one or two cable sizes compared to PVC, often offsetting the higher material cost.

Buried Cable Ratings — Methods D1 and D2

Installation methods D1 (in ducts in the ground) and D2 (direct buried) have their own current rating tables because heat dissipation in soil depends on factors not present in above-ground installations:

  • Soil thermal resistivity: Reference value 2.5 K·m/W. Dry sandy soil may have 3.0+ K·m/W (poorer), while moist clay may have 1.0 K·m/W (better). Correction factors are in Table B.52.16.
  • Depth of laying: Deeper cables have poorer heat dissipation. Standard reference depth is 0.7 m for ducts and 0.5–0.8 m for direct burial.
  • Ground temperature: Reference value 20°C. Correction factors for other temperatures are in Table B.52.15.

Direct-buried cables (Method D2) generally have higher ratings than cables in ducts (Method D1) because the cable is in direct thermal contact with the surrounding soil, providing better heat transfer. However, direct burial makes future cable replacement more difficult and provides less mechanical protection.

Relationship to BS 7671 Tables

BS 7671 Appendix 4 is directly derived from IEC 60364-5-52 Annex B, so the table structures and installation method codes are identical. The main differences are:

  • Cable types: BS 7671 includes UK-specific cable constructions (flat twin-and-earth, mineral-insulated copper cables) not found in IEC 60364.
  • Table numbering: IEC uses B.52.x (e.g., B.52.2), while BS 7671 uses 4Dxx (e.g., 4D1A). The mapping is systematic but not always one-to-one.
  • National deviations: Some countries that adopt IEC 60364 apply national annexes with different values for specific cable types or conditions.

For standard cable types (PVC and XLPE, copper and aluminium), the current rating values in IEC 60364 Table B.52 and the corresponding BS 7671 tables are identical or very close, reflecting their shared technical basis.

Try the Cable Sizing Calculator

Put this methodology into practice. Calculate results with full standard clause references — free, no sign-up required.

Or embed this calculator on your site
Calculate Cable Sizing

Frequently Asked Questions

Table B.52 in IEC 60364-5-52 and Table 4D1A in BS 7671 share the same technical basis — BS 7671 is the UK national implementation of IEC 60364. The installation method codes (A1, B1, C, E, etc.) are identical. The main difference is that BS 7671 includes additional UK-specific cable types (flat twin-and-earth, MICC) and uses a different table numbering system. For standard PVC and XLPE cables, the current rating values are essentially the same.
IEC 60364-5-52 current ratings use: 30°C ambient air temperature, 20°C ground temperature for buried cables, soil thermal resistivity of 2.5 K·m/W, and a single loaded circuit (no grouping). These are the same reference conditions as BS 7671. When actual conditions differ, correction factors from Tables B.52.14 through B.52.21 must be applied.
Method G (single-core cables spaced in free air) gives the highest current rating because it provides maximum heat dissipation on all sides of the cable. Method A1 (cables in conduit in a thermally insulated wall) gives the lowest ratings. The difference is significant — a 10 mm² PVC cable carries 46 A in Method A1 but 76 A or more in Method G, nearly double the capacity.

Related Resources