AS/NZS 3008 vs BS 7671 — Standards Comparison
Detailed comparison of AS/NZS 3008 (Australian cable sizing) and BS 7671 (UK IET Wiring Regulations). Side-by-side analysis of scope, reference conditions, installation methods, derating factors, voltage drop limits, and cable selection methodology.
Introduction
AS/NZS 3008 and BS 7671 are the two most commonly referenced cable sizing standards in countries that follow the IEC-influenced tradition (as opposed to NEC/NFPA 70 in North America). Both share a common heritage in IEC 60364, but they have evolved independently to suit Australian/New Zealand and UK conditions respectively.
Engineers who work across jurisdictions — for example, Australian firms working on Middle Eastern projects (which often reference BS 7671), or UK consultants designing for mining projects in Australia — need to understand the differences. This comparison covers the key areas where the standards diverge and where they align.
Side-by-Side Comparison
| Feature | AS/NZS 3008.1.1:2017 | BS 7671:2018+A2 |
|---|---|---|
| Full title | Selection of cables — Cables for AC voltages up to 0.6/1 kV | Requirements for Electrical Installations (IET Wiring Regulations) |
| Scope | Cable selection only | Complete installation standard (cable sizing in Appendix 4) |
| IEC base | IEC 60364-5-52 (methodology) | HD 60364 / IEC 60364 (all parts) |
| Reference ambient (air) | 40°C | 30°C |
| Reference ground temp | 25°C | 20°C |
| Reference soil resistivity | 1.2 K·m/W | 2.5 K·m/W |
| Installation methods | 29 methods (Table 3) | 10 methods (Table 4A2: A1–G) |
| Cable sizes | Metric (mm²): 1–630 | Metric (mm²): 1–630 |
| Key insulation types | V-75, V-90, X-90 | PVC (70°C), XLPE (90°C), MI |
| Current rating tables | Tables 13–15 | Tables 4D1A–4D5A |
| Temp derating table | Table 22 (air), Table 23 (ground) | Table 4B1 (air), Table 4B2 (ground) |
| Grouping derating table | Table 25 | Tables 4C1–4C5 |
| VD impedance tables | Tables 30–42 | Tables 4E1A–4E4A |
| VD limit (lighting) | 3% | 3% |
| VD limit (power) | 5% | 5% |
| Companion standard | AS/NZS 3000 (Wiring Rules) | Self-contained (but references IEC/BS standards) |
Key Differences
The most significant differences between the two standards are:
1. Reference Ambient Temperature (40°C vs 30°C)
This is the single most impactful difference. AS/NZS 3008 uses 40°C because Australian climate conditions frequently produce high ambient temperatures. BS 7671 uses 30°C, reflecting the UK’s cooler climate.
The practical consequence: at 35°C ambient, an AS/NZS 3008 calculation gives a bonus (factor >1.0 because 35°C is below the 40°C reference), while a BS 7671 calculation requires derating (factor <1.0 because 35°C is above the 30°C reference). This can result in a different cable size for the identical circuit.
The tabulated current ratings are also calculated at different reference temperatures, so the base values in the tables are not directly comparable. BS 7671 ratings appear higher for the same cable size, but this is offset by the need for more derating in warm conditions.
2. Number of Installation Methods (29 vs 10)
AS/NZS 3008 defines 29 distinct installation methods in Table 3, providing very specific current ratings for each configuration. BS 7671 uses 10 broader categories (A1 through G) that encompass a wider range of configurations within each category.
The AS/NZS approach gives more precise results for each specific installation arrangement, but requires the designer to carefully identify exactly which of the 29 methods applies. The BS 7671 approach is simpler to navigate but may be slightly more conservative for unusual installations that don’t perfectly match one of the 10 categories.
3. Soil Thermal Resistivity Reference
AS/NZS 3008 uses 1.2 K·m/W (moist, well-compacted soil), while BS 7671 uses 2.5 K·m/W (dry, sandy soil). This means AS/NZS 3008 gives higher buried cable ratings under its reference conditions, but requires more derating if the soil is dry. BS 7671 is more conservative by default but gives a bonus factor in moist soil conditions.
4. Standard Scope
AS/NZS 3008 is specifically a cable selection standard — it only covers cable sizing. The broader installation requirements (maximum demand, protection coordination, earthing) are in AS/NZS 3000. BS 7671, by contrast, is a complete installation standard that covers everything from design through verification, with cable sizing being one part (Appendix 4) of a much larger document.
Key Similarities
Despite the differences, both standards share a common engineering foundation:
- Same fundamental methodology: Both follow the same cable sizing procedure — determine design current, select protective device, apply derating factors, select cable from tables, verify voltage drop. The engineering logic is identical.
- Derived from IEC: Both standards incorporate IEC 60364 methodology. The derating factor formulas, the voltage drop impedance approach, and the short circuit withstand method are shared.
- Metric cable sizes: Both use the standard metric size series (1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300, 400, 500, 630 mm²), so a cable sized under one standard uses the same size designation under the other.
- Same voltage drop limits: Both standards allow 3% for lighting and 5% for power circuits, making voltage drop calculations directly comparable.
- Same grouping methodology: The approach to grouping derating is the same — count the number of circuits, look up the factor from the table. The specific factor values are very similar between the two standards.
- Same short circuit check: Both use the adiabatic equation (I²t = k²S²) for short circuit withstand verification, with similar k values for each conductor/insulation combination.
When You Need Each Standard
The choice of standard is determined by the project location and the applicable regulatory framework:
| Region | Primary Standard | Notes |
|---|---|---|
| Australia | AS/NZS 3008 + AS/NZS 3000 | Mandatory via state/territory electrical safety regulations |
| New Zealand | AS/NZS 3008 + AS/NZS 3000 | Mandatory via EWRB (Electrical Workers Registration Board) |
| United Kingdom | BS 7671 | Referenced by Building Regulations Part P and EAWR 1989 |
| Ireland | IS 10101 (based on CENELEC) | Closely aligned with BS 7671 |
| Middle East (UAE, Qatar, KSA) | Often BS 7671 | Many Gulf states adopt BS 7671 or IEC 60364 with local amendments |
| Sub-Saharan Africa | Mixed (BS 7671 / IEC / national) | Former British colonies often use BS 7671 or derivatives |
| Southeast Asia | Mixed (IEC / national) | Some countries use AS/NZS 3008 influence (e.g., Papua New Guinea) |
| Pacific Islands | AS/NZS 3008 + AS/NZS 3000 | Many Pacific island nations adopt Australian standards |
For multinational engineering firms working across multiple jurisdictions, the ability to recalculate the same circuit under different standards is essential. Recalculating the same circuit under different standards is essential for identifying where the standards produce different results and understanding the practical implications.
Working Across Both Standards
Engineers working across multiple jurisdictions need a systematic approach to multi-standard calculations:
- Calculate under either standard with the correct tables, reference conditions, and limits applied consistently
- Compare results side by side by running the same circuit parameters under both standards to identify differences
- Generate compliant reports with the correct table references and clause numbers for the applicable standard
- Document the applicable standard clearly for projects that cross jurisdictional boundaries (e.g., an Australian mining camp with UK-specified equipment)
Every calculation result should clearly identify which standard was used and reference the specific tables and clauses, so there is no ambiguity about which regulatory framework applies.
Try the Cable Sizing Calculator
Put this methodology into practice. Calculate results with full standard clause references — free, no sign-up required.
Or embed this calculator on your siteFrequently Asked Questions
Related Resources
AS/NZS 3008 Overview
Comprehensive overview of AS/NZS 3008 tables and methodology.
Read moreBS 7671 Overview
Comprehensive overview of BS 7671 tables, amendments, and methodology.
Read moreCable Sizing Methodology
The multi-standard cable sizing methodology that applies across both standards.
Read moreResidential Cable Sizing Example
Worked example with multi-standard comparison showing how AS/NZS 3008 and BS 7671 produce different results.
Read more