Skip to main content

Voltage Drop Calculator per BS 7671 for Solar PV Systems

BS 767118th Edition + Amendment 2:2022Solar PV Systems

Solar PV voltage drop under BS 7671 Section 712 applies to both DC string cables and AC output cables. The 5% limit from Table 4Ab applies to the AC side, while DC cable sizing must ensure the inverter's MPPT range is maintained. Excessive DC voltage drop reduces energy yield by shifting the operating point away from maximum power.

Quick Reference Table

BS 7671 Voltage Drop Considerations — Solar PVBS 7671 (18th Edition + Amendment 2:2022)
ParameterValue / RequirementClause Reference
AC side voltage drop limit5% (11.5 V at 230 V single-phase)Appendix 4, Table 4Ab
PV installation requirementsSection 712 specific provisionsSection 712
DC cable mV/A/m valuesUse manufacturer data or Table 4D1B Column 2 (two-core DC equivalent)Table 4D1B
Permissible drop measurement pointFrom meter position to inverter AC output terminalsRegulation 525.1
DC string cable sizingDetermined by inverter MPPT voltage window, not Table 4AbRegulation 712.512.2

How to Calculate Voltage Drop for Solar PV Systems

  1. 1

    Calculate DC string voltage and current

    Determine the Voc and Isc of each PV string at STC conditions. Apply temperature correction for the coldest expected ambient temperature (Voc increases in cold weather). The total string voltage must remain within the inverter MPPT range after accounting for cable voltage drop.

  2. 2

    Size DC string cables for voltage drop

    Calculate DC voltage drop using VD = 2 × Isc × R × L, where R is the conductor resistance per metre and L is the one-way cable length from the string to the inverter. Keep DC voltage drop below 1-2% to maximise energy yield — this is a design choice, not a BS 7671 requirement.

  3. 3

    Size AC cables from inverter to consumer unit

    The AC cable from the inverter to the consumer unit is subject to the standard BS 7671 voltage drop limits. Use Table 4D1B mV/A/m values with the inverter's maximum output current.

  4. 4

    Check total AC voltage drop

    For domestic PV systems, the AC cable run is typically short (under 15 m), making voltage drop minimal. For commercial roof-top systems with inverters in plant rooms, the run may be longer. Verify the drop is within the 5% limit per Table 4Ab.

  5. 5

    Document DC and AC voltage drops separately

    Record the DC and AC voltage drop calculations separately in the design documentation. Include string Voc, cable lengths, conductor sizes, and the resulting voltage at the inverter DC input and AC output terminals.

Try the Voltage Drop Calculator

Run compliant BS 7671 calculations for solar pv systems — free, instant results with full clause references.

Calculate Voltage Drop Now

BS 7671 vs IEC 60364 Cable Sizing Comparison

ParameterBS 7671IEC 60364
ScopeUK & derivativesInternational (adopted by 60+ countries)
Voltage drop limit3% lighting / 5% other4% lighting / 5% other (typical)
Reference ambient temp30°C (air), 20°C (ground)30°C (air), 20°C (ground)
Installation methodsReference Methods A-G (Appendix 4)Reference Methods A-G (Table B.52.1)
Grouping factorsTable C.3 (BS specific)Table B.52.17 (international)
Disconnection time (230V)0.4s final / 5s distribution0.4s final / 5s distribution

Frequently Asked Questions

No. BS 7671 Table 4Ab limits apply to the AC side of installations. DC string cable sizing is driven by the inverter MPPT voltage range and current-carrying capacity per Section 712. However, industry best practice is to limit DC voltage drop to 1-2% to avoid energy losses. A 3% DC voltage drop on a 50 kWp system could waste over 1,500 kWh per year.
For DC circuits, use VD = 2 × I × ρ × L / A, where I is the string short-circuit current (Isc), ρ is the conductor resistivity (1.72 × 10⁻⁸ Ω·m for copper at 20°C), L is the one-way cable length, and A is the conductor cross-sectional area. The factor of 2 accounts for the positive and negative conductors. At elevated temperatures, increase ρ by 0.393% per degree above 20°C.
Calculate at the maximum power point current (Imp) for energy yield assessment, and at Isc for worst-case cable sizing. The voltage drop at Imp determines the actual energy loss during normal operation. At Isc, the panels are in short-circuit and no power is generated, but this current flows through the DC switch-disconnector and must be safely carried by the cables.

Related Guides