Skip to main content

Maximum Demand Calculator

Maximum demand assessment per AS/NZS 3000:2018 Appendix C. Table C1/C2/C3 diversity factors.

Building & Supply
Quick Templates
Load Schedule
kW
kW

Maximum Demand Results

Configure your load schedule and click Calculate.

Maximum demand is the greatest electrical load expected to occur simultaneously on a supply system, measured in amperes or kilovolt-amperes. BS 7671 Appendix 1 provides diversity allowances and assessment methods for domestic and commercial installations. Accurate maximum demand estimation prevents oversizing of supply cables, switchgear, and upstream transformer capacity.

How to Calculate Maximum Demand

  1. 1
    List all circuit loadsCatalogue every final circuit with its connected load in watts or amperes. Group circuits by type: lighting, heating, cooking, socket outlets, motors, and other loads as defined in BS 7671 Appendix 1.[BS 7671 Appendix 1]
  2. 2
    Apply diversity factors by typeApply the appropriate diversity factor from BS 7671 Table 1A to each circuit group. For example, socket outlets use 100% of the largest circuit plus 40% of the remaining circuits.[BS 7671 Table 1A]
  3. 3
    Sum diversified loadsAdd the diversified loads from all circuit groups to determine the total after-diversity maximum demand. This represents the expected simultaneous peak load on the supply.
  4. 4
    Convert to current demandConvert the total diversified load from watts to amperes using I = P / (V x pf) for single-phase or I = P / (1.732 x V x pf) for three-phase supplies. Include the power factor of the combined load.
  5. 5
    Verify supply capacityConfirm the supply authority's declared supply capacity (typically 100A single-phase domestic or 200A three-phase commercial) exceeds the calculated maximum demand with adequate headroom.[BS 7671 Regulation 311.1]

How Maximum Demand Works

The maximum demand calculator estimates the peak electrical load that an installation will draw simultaneously, which determines the required supply capacity, transformer rating, and main cable size.

The calculation begins by categorising all connected loads — lighting, power points, cooking appliances, air conditioning, motors, and other equipment. Each category has its own demand factor (diversity factor) that accounts for the statistical likelihood that not all loads operate at full capacity simultaneously.

Under AS/NZS 3000:2018 Section 2 and Tables C1-C5, demand factors are applied per load type. For example, general power outlets use a demand factor based on the number of points: 10A at the first point plus 5A for each additional point in a domestic installation. Lighting loads apply the connected wattage with diversity from Table C3. Cooking appliances use Table C4 which reduces demand based on the number of appliances.

BS 7671:2018+A2 Appendix A provides current demand values per point and diversity allowances in Table A1. The approach groups loads into categories (lighting, heating, cooking, motors, etc.) and applies percentage-based diversity to each. IEC 60364-1 Clause 311.1 establishes the general principles for assessing maximum demand through diversity.

The total maximum demand is the sum of all category demands after applying their respective diversity factors: MD_total = SUM(P_category x DF_category) / (V x PF x sqrt(3)) for three-phase supplies, yielding the demand in amperes. From this, the calculator determines the required supply phase configuration, minimum main switch rating, transformer kVA, and main cable size.

Results include a per-category demand breakdown, applied diversity factors with clause references, total maximum demand in kW and amperes, recommended supply capacity, and a visual stacking chart showing the contribution of each load category.

## Maximum Demand Calculation for 3-Phase vs Single-Phase Supplies

For single-phase installations (typical residential in UK and Australia), maximum demand is calculated as MD = Total_kW / (V x PF), where V is 230V (UK/AU) or 120V (US). For three-phase supplies (commercial and industrial), the formula becomes MD = Total_kW / (V_LL x PF x 1.732), where V_LL is the line-to-line voltage (400V UK, 415V AU, 480V US). The calculator automatically adjusts for phase configuration and regional voltage standards. Balanced loading across all three phases is assumed unless specific per-phase loads are entered.

## Maximum Demand Tables by Standard

Each standard provides its own maximum demand tables with distinct diversity allowances. AS/NZS 3000 Tables C1 through C5 cover domestic, commercial, and industrial installations with specific rules for cooking appliances, air conditioning, and EV charging. BS 7671 Appendix A (Table A1) uses a percentage-based diversity system per circuit category. NEC Article 220 provides demand factors in Tables 220.42 (lighting), 220.44 (receptacles), and 220.55 (cooking equipment). IEC 60364 Clause 311.1 establishes principles but defers detailed diversity factors to national annexes. Understanding which maximum demand table to use for your jurisdiction is critical — applying AS/NZS diversity factors to a BS 7671 installation can result in undersized or oversized supply equipment.

## Residential vs Commercial Maximum Demand

Residential maximum demand calculation follows the domestic tables in each standard, where loads are relatively predictable: lighting, socket outlets, cooking, water heating, and increasingly EV charging and heat pumps. Diversity is high (typically 40-60%) because residents use appliances intermittently. Commercial maximum demand is more complex because load profiles vary dramatically by building type. An office building with predominantly lighting and computing loads has different diversity from a restaurant with continuous cooking and refrigeration. Industrial maximum demand requires consideration of motor starting diversity, process load duty cycles, and the coincidence factor for large equipment. The calculator supports all three building types with appropriate diversity tables.

## Maximum Demand Formula: Step-by-Step

Step 1: List all connected loads by category (lighting, socket outlets, cooking, heating/cooling, motors, special loads). Step 2: Determine the connected load in watts or amperes for each category. Step 3: Apply the diversity factor from the appropriate standard table (AS/NZS 3000 Table C1, BS 7671 Table A1, or NEC Table 220.42). Step 4: Sum all diversified loads to obtain the total maximum demand in kW. Step 5: Convert to amperes using MD(A) = MD(kW) x 1000 / (V x PF) for single-phase, or MD(A) = MD(kW) x 1000 / (V x PF x 1.732) for three-phase. Step 6: Select the next standard main switch rating (63A, 80A, 100A, etc.) and size the supply cable accordingly. The calculator performs all six steps automatically with full standard clause references.

## Transformer Sizing from Maximum Demand

Once maximum demand is known in kW, transformer sizing follows: kVA_required = MD_kW / PF, where PF is typically 0.85 to 0.95 depending on the load mix. Add 15-25% growth margin per AS/NZS 3000 Clause 2.2.2 and IEC 60076-1. Select the next standard transformer rating: common sizes are 100, 160, 200, 315, 500, 630, 800, 1000, 1250, 1600, and 2000 kVA. Oversizing wastes capital and increases losses; undersizing risks overloading and premature failure. The calculator provides a direct transformer size recommendation cross-linked to the transformer calculator for detailed impedance and short-circuit analysis.

Diversity Factors — Domestic Installation (BS 7671)

Circuit TypeFirst 10ARemainderReference
Lighting66%100%Appendix 1
Heating100%100%Appendix 1
Cooking10A + 30%of remainderAppendix 1
Socket outlets100%40%Appendix 1
EV charging100%Section 722

Source: BS 7671:2018 Appendix 1

Frequently Asked Questions

How is maximum demand calculated per AS/NZS 3000:2018?
AS/NZS 3000:2018 Section 2 provides the method for calculating maximum demand. For domestic installations, Table 2.2 assigns demand per point for lighting (75W socket outlet, 10A per socket up to certain limits), and Table 2.3 provides diversity allowances. For example, cooking appliances use the first 10A at 100% plus 50% of the remaining current (Clause 2.4.2). Air conditioning and heating loads use the larger of the two if not simultaneous, per Clause 2.4.3.
What are diversity factors and why are they important?
Diversity factors account for the statistical probability that not all loads in an installation will operate simultaneously at full load. BS 7671 Appendix A Table A1 provides allowances: for example, 66% for 10A socket outlets after the first 5 points, and 50% for cooking appliances above the first 10A. Without diversity, a 100-unit apartment building might require a 10MVA supply; with proper diversity factors applied per the standard, the actual demand might be 2-3MVA, dramatically reducing infrastructure costs.
How does BS 7671 Appendix A calculate maximum demand?
BS 7671:2018+A2 Appendix A (formerly Appendix J in older editions) uses Table A1 to assign current demand per circuit type. Standard socket outlets are assessed at their rated current (13A for ring finals, 16A for radials), with diversity of 100% for the largest appliance plus 40% of remaining for cooking, and 66% after the first 5 points for socket outlets. The total maximum demand determines the main switch/fuse rating and the supply cable size, typically coordinated with the DNO per Engineering Recommendation P2.
What is the difference between connected load and maximum demand?
Connected load is the arithmetic sum of all installed load ratings, while maximum demand is the actual peak load expected in service after applying diversity and demand factors. For example, a commercial building might have 500kW of connected lighting, HVAC, and plug loads, but a maximum demand of only 300kW because not all loads operate at full output simultaneously. IEC 60364-3 Clause 311 requires that the supply be designed for maximum demand, not connected load, using the assessed diversity factor for the installation type.
How do you size a transformer based on maximum demand?
After calculating maximum demand in kW, convert to kVA by dividing by the power factor (typically 0.85-0.95). Then add a growth margin of 15-25% per engineering practice. Select a standard transformer rating (e.g., 200, 315, 500, 630, 800, 1000 kVA per IEC 60076-1) that meets or exceeds the calculated demand. AS/NZS 3000 Clause 2.2.2 requires consideration of future load growth. ECalPro's max demand calculator provides a direct cross-link to the transformer sizing calculator for this workflow.
Can I use maximum demand calculation for industrial installations?
Yes, but industrial installations require additional considerations beyond the standard domestic/commercial tables. IEC 60364-3 Clause 311.1 and AS/NZS 3000 Clause 2.2.1 note that industrial demand should be assessed based on the specific process requirements, duty cycles, and coincidence of motor starting. For motor-heavy installations, you must account for starting current diversity (not all motors start simultaneously) and the largest motor starting current added to the running load of all others, per common engineering practice endorsed by AS/NZS 3000.
How do I determine motor full-load current for cable and protection sizing?
For cable and protection sizing, always use the motor full-load current (FLC) from the standard tables rather than the nameplate value. NEC Table 430.248 (single-phase) and Table 430.250 (three-phase) provide standard FLC values. For IEC practice, IEC 60034-1 nameplate values are used but with service factor consideration. AS/NZS 3000 Table C8 provides typical motor currents. The cable must be rated for at least 125% of the motor FLC per NEC 430.22 or the appropriate derating per AS/NZS 3008.1.1.
What are the starting current requirements for DOL vs star-delta starting?
Direct-on-line (DOL) starting draws 6-8 times the full-load current (Istart/Ifull ratio per IEC 60034-12 Code letters). Star-delta starting reduces the starting current to approximately one-third of DOL values (by the factor 1/3) because the motor initially runs at reduced voltage (Vline/sqrt(3)). However, star-delta also reduces starting torque to one-third, so it is only suitable for low-torque starting applications like centrifugal pumps and fans. NEC 430.VII covers motor starting methods and their protection requirements.
How do I size motor branch circuit protection per NEC Article 430?
NEC Article 430 Part IV requires a branch circuit short-circuit and ground-fault protective device (BCSCD) sized per Table 430.52. For standard inverse-time circuit breakers, the maximum is 250% of motor FLC; for dual-element time-delay fuses, 175%; and for instantaneous-trip breakers (used with starters), 800-1300% of motor FLC depending on motor type. The overload relay is separately sized at 115% of motor nameplate current per NEC 430.32. This dual-element protection scheme allows for high starting currents while protecting against sustained overloads.
What is motor power factor and how does it affect the electrical system?
Motor power factor varies from about 0.3 at no-load to 0.85-0.90 at full load for standard AC induction motors per IEC 60034-1. At partial loads (common in oversized installations), poor power factor draws excessive reactive current, increasing cable losses, voltage drop, and transformer loading. AS/NZS 61000.3.6 and IEEE 18 provide guidance on power factor correction capacitor sizing. Individual motor correction should not exceed the no-load reactive power to avoid self-excitation, which is particularly important when motors are switched with capacitors still connected.
How does a VFD (variable frequency drive) change motor electrical requirements?
A VFD changes several electrical design considerations. The input cable must be sized for the drive input current (not motor FLC), and the drive-to-motor cable must account for additional heating from harmonic content per IEC 60034-17 (typically apply a 5% derating). NEC 430.122 covers adjustable-speed drive circuit conductors, requiring 125% of the rated input current. The output cable length is limited to avoid voltage reflection and insulation stress, typically 100m maximum without an output reactor. EMC considerations per IEC 61800-3 may require shielded cables.

Related Calculators

Related Guides & Examples

Key Terms

Related FAQ

Standards Reference

  • AS/NZS 3000:2018 — Section 2, Tables C1-C5
  • BS 7671:2018+A2 — Appendix A, Table A1
  • IEC 60364-1 — Clause 311.1