Earthing & Grounding Calculator
Design earthing systems with touch/step voltage verification per IEEE 80 and IEC 60364-5-54.
Calculation Mode
Soil Properties
Electrode Configuration
Target Resistance
Configure electrode parameters and click Calculate to see earthing system analysis.
Export Professional Reports
Save your earthing & grounding calculator results as branded PDF, Excel, or Word reports with full standard references and clause numbers.
Earth fault loop impedance is the total impedance of the fault current path from the source through the phase conductor, fault, and protective conductor back to the source. BS 7671 Regulation 411.4 requires that this impedance be low enough to ensure the protective device disconnects the supply within the specified time to prevent electric shock.
How to Size an Earth Protective Conductor
- 1Determine the fault current — Calculate or obtain the maximum earth fault current at the point of installation. This requires knowledge of the earth fault loop impedance and the supply voltage.[IEC 60364-5-54 Clause 543.1]
- 2Determine device disconnection time — Find the disconnection time of the protective device at the calculated earth fault current from its time-current characteristic curve. This is the duration the conductor must withstand the fault.[BS 7671 Regulation 411.3.2]
- 3Select the k factor — Look up the k value for the protective conductor material and insulation from IEC 60364-5-54 Table A.54.1 through A.54.6. Copper with PVC insulation has k = 115.[IEC 60364-5-54 Tables A.54.1-6]
- 4Apply the adiabatic equation — Calculate the minimum conductor size using S = sqrt(I2t) / k, where I is the fault current, t is the disconnection time, and k is the material factor from the previous step.[IEC 60364-5-54 Clause 543.1]
- 5Apply minimum size rules — Verify the calculated size meets the minimum requirements from BS 7671 Table 54.7 or use the simplified method: CPC size equals phase conductor size up to 16mm2, half the phase size above that.[BS 7671 Table 54.7]
How Earthing System Works
The earthing calculator designs ground electrode systems and verifies that touch and step voltages remain within safe limits during earth fault conditions.
Using IEEE Std 80-2013 methodology, the calculator determines the ground potential rise (GPR), mesh voltage, and step voltage for a given grid geometry and soil resistivity. The tolerable touch voltage is calculated as Etouch = (1000 + 1.5 x Cs x rho_s) x 0.116 / sqrt(ts), where Cs is the surface layer derating factor, rho_s is the surface material resistivity, and ts is the fault duration.
IEC 60364-5-54 defines earthing arrangements (TN, TT, IT systems) and minimum conductor sizes. NEC Article 250 establishes grounding electrode requirements. AS/NZS 3000 Section 5 covers earthing and bonding. Results include the required earth grid geometry, electrode sizing, touch and step voltage compliance, earth resistance, and conductor cross-section.
Maximum Earth Fault Loop Impedance Zs (BS 7671)
| Device Rating | Type B (Ω) | Type C (Ω) | Type D (Ω) |
|---|---|---|---|
| 6A | 7.67 | 3.83 | 1.92 |
| 10A | 4.60 | 2.30 | 1.15 |
| 16A | 2.87 | 1.44 | 0.72 |
| 20A | 2.30 | 1.15 | 0.57 |
| 32A | 1.44 | 0.72 | 0.36 |
| 40A | 1.15 | 0.57 | 0.29 |
| 63A | 0.73 | 0.36 | 0.18 |
Source: BS 7671:2018 Table 41.3
Frequently Asked Questions
What earth resistance value is required per AS/NZS 3000?
How do I calculate touch and step voltage per IEEE 80?
How does soil resistivity affect earthing design?
How do I size an earthing conductor per BS 7671?
What is the difference between TN, TT, and IT earthing systems?
What grounding requirements does NEC Article 250 specify?
Related Calculators
Related Guides & Examples
Related FAQ
Standards Reference
- IEEE Std 80-2013 — Substation grounding
- IEC 60364-5-54 — Earthing arrangements
- NEC Article 250 — Grounding
- AS/NZS 3000:2018 — Section 5