Fault Loop Impedance Zs
Fault loop impedance Zs is the measured or calculated total impedance of the earth fault current path from the supply transformer through the phase conductor, fault, and protective conductor back to the source. BS 7671 Regulation 411.4.5 specifies maximum Zs values for each protective device to ensure fault disconnection within 0.4 or 5 seconds depending on circuit type.
Detailed Explanation
Fault loop impedance is a critical parameter that links cable design to protection performance. Zs comprises two components: Ze, the external impedance from the supply transformer to the consumer's main earthing terminal (typically provided by the distribution network operator), and R1 + R2, the combined impedance of the phase conductor and circuit protective conductor from the distribution board to the furthest point of the circuit. Maximum permissible Zs values are tabulated for each protective device type and rating to ensure sufficient fault current flows to operate the device within the required disconnection time. For Type B MCBs, the instantaneous trip at 3–5 times rated current determines the maximum Zs, while for Type C MCBs (5–10 times), the maximum Zs is lower. Measurement is performed during commissioning using a loop impedance tester, and the measured value must be compared against the tabulated maximum after applying a correction factor (typically 0.8) to account for conductor temperature rise during a fault. For ring final circuits, both legs must be tested to verify continuity and correct interconnection.
Formula
Standard References
| Standard | Clause | Relevance |
|---|---|---|
| BS 7671:2018 | Regulation 411.4.5 | Maximum earth fault loop impedance for automatic disconnection |
| IEC 60364-4-41 | Clause 411.4 | Requirements for automatic disconnection of supply |
Related Terms
Earth Fault Loop Impedance
Earth fault loop impedance is the total impedance of the fault current path from the source through the phase conductor,...
Touch Voltage
Touch voltage is the potential difference between simultaneously accessible conductive parts that a person could contact...
Earthing Resistance
Earthing resistance is the opposition to current flow between an earth electrode and the general mass of earth, measured...
RCD Operating Time
RCD operating time is the interval between the occurrence of a residual current exceeding the rated threshold and the au...