Skip to main content

Worked Example: Residential Cable Sizing — Multi-Standard

Step-by-step worked example sizing a cable for a residential cooker circuit. Includes full derating factor calculations, voltage drop verification, protective device coordination, and a multi-standard comparison across AS/NZS 3008, BS 7671, and IEC 60364.

AS/NZS 300814 min readUpdated February 21, 2026
Share:

Scenario

Size a cable for a single-phase electric cooker in a residential kitchen. The full installation details are:

ParameterValue
Supply230 V single-phase, 50 Hz
Load7.2 kW, power factor 1.0 (resistive)
Cable route length22 m (from consumer unit to kitchen)
Installation methodEnclosed in wiring enclosure in thermally insulated wall
Ambient temperature35°C
Grouping2 circuits in the same conduit
Cable typeV-90 (PVC 90°C) thermoplastic TPS, copper conductor
Primary standardAS/NZS 3008.1.1:2017

This example walks through the complete cable sizing procedure step by step, with full standard references at each stage, then compares the result across three international standards.

Step 1: Calculate Design Current (I_b)

For a single-phase resistive load:

Ib = P / (V × PF) — (Eq. 1)

Ib = 7,200 / (230 × 1.0)

Ib = 31.3 A

The design current is the maximum sustained current the circuit is expected to carry. For a resistive load like a cooker, the power factor is 1.0, simplifying the calculation.

Step 2: Select Protective Device (I_n)

The protective device must have a rated current not less than the design current:

In ≥ Ib — (Eq. 2)

From the standard protective device ratings (6, 10, 16, 20, 25, 32, 40, 50, 63 A...), the next rating above 31.3 A is:

In = 32 A (MCB, Type B or C)

A Type B MCB trips at 3–5× rated current (instantaneous magnetic trip). Type C (5–10×) could also be used but Type B is more common for resistive loads in domestic installations.

Step 3: Determine Derating Factors

The installation conditions differ from the standard reference conditions. We need to apply derating factors from AS/NZS 3008.1.1:2017:

Ambient temperature derating (k1):

Reference ambient for AS/NZS 3008 is 40°C. Our ambient is 35°C, which is below the reference, so the temperature factor is actually greater than 1.0.

From Table 22, Row: 35°C, Column: 90°C rated cable:

k1 = 1.04 (slight increase because ambient is below 40°C reference)

Note: This is a key difference between AS/NZS 3008 (40°C reference) and BS 7671 (30°C reference). At 35°C, AS/NZS 3008 gives a bonus factor (>1.0) while BS 7671 would require derating (<1.0).

Grouping derating (k2):

From Table 25, Row: 2 circuits, enclosed in conduit:

k2 = 0.80

Combined derating factor:

ktotal = k1 × k2 = 1.04 × 0.80 = 0.832

Step 4: Calculate Required Current Rating and Select Cable

The cable must have a current-carrying capacity (after derating) at least equal to the protective device rating:

Iz ≥ In / ktotal — (Eq. 3)

Iz ≥ 32 / 0.832

Iz ≥ 38.5 A

Now select from AS/NZS 3008 Table 13 (multicore cables), Column 6 (enclosed in wiring enclosure, V-90 insulation, copper conductor):

Cable Size (mm²)Current Rating (A)Result
431✗ Too low (31 < 38.5)
640✓ Passes (40 ≥ 38.5)
1054✓ Passes with margin

The minimum cable size based on current-carrying capacity is 6 mm², rated at 40 A from Table 13, Column 6.

However, we should verify that 6 mm² passes the voltage drop check before finalising this selection.

Step 5: Voltage Drop Verification

Check voltage drop for the 6 mm² cable first. From AS/NZS 3008 Table 35, for 6 mm² V-90 single-phase copper cable:

mV/A·m = 7.3 (at unity power factor)

ΔV = mV/A·m × Ib × L / 1000 — (Eq. 4)

ΔV = 7.3 × 31.3 × 22 / 1000

ΔV = 5.03 V

ΔV% = 5.03 / 230 × 100 = 2.19%

The AS/NZS 3000 Clause 3.6.2 limit for power circuits is 5%. This circuit at 2.19% passes comfortably.

Now let’s also check the 10 mm² option for comparison:

mV/A·m = 4.0 (Table 35, 10 mm²)

ΔV = 4.0 × 31.3 × 22 / 1000 = 2.75 V = 1.20%

Both 6 mm² and 10 mm² pass the voltage drop check. Since 6 mm² is the smaller and cheaper option and passes all checks, it is the correct selection for this scenario.

Step 6: Short Circuit Check

For completeness, verify the cable can withstand the prospective short circuit current at the consumer unit. Using the adiabatic equation:

k²S² ≥ I²t — (Eq. 5)

Where k = 115 (PVC insulated copper, initial temperature 90°C, final 250°C per AS/NZS 3008 Table 52), S = 6 mm², and I²t is determined by the protective device clearing time and fault current.

k²S² = 115² × 6² = 13,225 × 36 = 476,100 A²s

For a typical domestic installation with 16 kA prospective fault current and a 32 A Type B MCB tripping in approximately 5 ms at fault level, the energy let-through is well within the cable’s withstand. The 6 mm² cable passes the short circuit check.

Result Summary

CheckRequirementActualStatus
Current capacity≥ 38.5 A (derated)40 A (6 mm², Table 13 Col 6)✓ PASS
Voltage drop≤ 5.0%2.19%✓ PASS
Short circuitk²S² ≥ I²t476,100 A²s > device let-through✓ PASS

Selected cable: 6 mm² V-90 TPS copper, protected by 32 A Type B MCB.

The governing factor is current-carrying capacity. The grouping derating (2 circuits) reduced the effective cable capacity enough that 4 mm² was insufficient, requiring a 6 mm² cable. Voltage drop was not the governing factor for this relatively short 22 m run.

Multi-Standard Comparison

Calculating the same circuit under different standards reveals how reference conditions and table values affect cable selection. Here is how this cooker circuit sizes across three standards:

ParameterAS/NZS 3008BS 7671IEC 60364
Design current31.3 A31.3 A31.3 A
Protective device32 A MCB32 A MCB32 A MCB
Reference ambient40°C30°C30°C
Temp derating at 35°C1.04 (bonus)0.94 (penalty)0.94 (penalty)
Grouping derating (2 ccts)0.800.800.80
Combined derating0.8320.7520.752
Required Iz38.5 A42.6 A42.6 A
Selected cable size6 mm²10 mm²10 mm²
Voltage drop2.19%1.25%1.25%
Key insight: The same cooker circuit requires 6 mm² under AS/NZS 3008 but 10 mm² under BS 7671 and IEC 60364. The difference is entirely due to the reference ambient temperature: AS/NZS 3008 uses 40°C (so 35°C gets a bonus), while BS 7671 and IEC use 30°C (so 35°C incurs a penalty). This demonstrates why multi-standard capability matters for engineers working across jurisdictions.

Try the Cable Sizing Calculator

Put this methodology into practice. Calculate results with full standard clause references — free, no sign-up required.

Or embed this calculator on your site
Calculate Cable Sizing

Frequently Asked Questions

For a 10 kW cooker on 230 V single-phase (43.5 A), the cable size depends on installation conditions. With minimal derating, 10 mm² may suffice. With conduit in insulated wall and grouping derating, 16 mm² is more likely. Always perform the full calculation with your specific derating factors — there is no single universal answer.
Yes. Cables in conduit have restricted heat dissipation compared to cables in free air or clipped direct. The conduit acts as a thermal blanket, trapping heat around the cable. Additionally, if multiple circuits share the same conduit, grouping derating factors apply — typically 0.80 for 2 circuits, 0.70 for 3 circuits, and lower for more. Both factors must be applied together.
Longer cable runs increase voltage drop. For the 6 mm² cable in this example (mV/A·m = 7.3), the voltage drop reaches 5% at approximately 50 m, at which point you would need to upsize to 10 mm². As a rule of thumb, if your cable run exceeds 30 metres for a high-current circuit, always check voltage drop carefully — it may govern the cable size rather than current capacity.

Related Resources