Cable Sizing Calculator per BS 7671:2018+A2 for United Kingdom

BS 7671:2018+A218th Edition + Amendment 2:2022United Kingdom

Cable sizing in the United Kingdom follows BS 7671:2018+A2 (IET Wiring Regulations, 18th Edition). Engineers select conductor cross-sectional areas using Table 4D1A current-carrying capacities, apply grouping factors from Table 4C1, ambient temperature corrections from Table 4B1, and verify voltage drop against Appendix 4 limits of 3% lighting and 5% power.

Quick Reference Table

UK Cable Sizing Key References — BS 7671BS 7671:2018+A2 (18th Edition + Amendment 2:2022)
ParameterValue / RequirementClause Reference
Supply voltage230 V single-phase / 400 V three-phase (TNS or TN-C-S)Regulation 132.4
Frequency50 HzRegulation 132.4
Current-carrying capacityThermoplastic (70 °C) and thermosetting (90 °C) ratingsTable 4D1A / 4E1A
Voltage drop limits3% lighting, 5% other circuits from originAppendix 4, Table 4Ab
Grouping correction factorsReduction for circuits in same enclosure or trunkingTable 4C1
Common conductor sizes1.0, 1.5, 2.5, 4, 6, 10, 16, 25, 35 mm²Table 4D1A
Maximum demand calculationDiversity factors per Appendix A for domestic installationsAppendix A, Table A1
Protective device coordinationIb ≤ In ≤ Iz and I2 ≤ 1.45 × IzRegulation 433.1

How to Calculate Cable Sizing for United Kingdom

  1. 1

    Determine design current (Ib)

    Calculate the maximum load current for the circuit. For domestic circuits, apply BS 7671 Appendix A diversity. For commercial, use assessed maximum demand.

  2. 2

    Select protective device rating (In)

    Choose an MCB, RCBO, or fuse rating such that Ib ≤ In. Common UK ratings: 6, 10, 16, 20, 32, 40, 50, 63 A.

  3. 3

    Identify UK installation method

    Determine the installation method per BS 7671 Table 4A2 — clipped direct (C), enclosed in conduit (B), on tray (E/F), or in thermal insulation (100/101).

  4. 4

    Apply correction factors

    Apply grouping (Table 4C1), ambient temperature (Table 4B1), and thermal insulation (Reg. 523.9) factors. Divide In by the product of all factors to find the required tabulated Iz.

  5. 5

    Check voltage drop against UK limits

    Calculate voltage drop using mV/A/m values from Table 4D1B. Verify total drop stays within 3% (6.9 V) for lighting and 5% (11.5 V) for power at 230 V.

Try the Cable Sizing Calculator

Run compliant BS 7671:2018+A2 calculations for united kingdom — free, instant results with full clause references.

Calculate Cable Sizing Now

BS 7671 vs IEC 60364 Cable Sizing Comparison

ParameterBS 7671IEC 60364
ScopeUK & derivativesInternational (adopted by 60+ countries)
Voltage drop limit3% lighting / 5% other4% lighting / 5% other (typical)
Reference ambient temp30°C (air), 20°C (ground)30°C (air), 20°C (ground)
Installation methodsReference Methods A-G (Appendix 4)Reference Methods A-G (Table B.52.1)
Grouping factorsTable C.3 (BS specific)Table B.52.17 (international)
Disconnection time (230V)0.4s final / 5s distribution0.4s final / 5s distribution

Frequently Asked Questions

Typical UK domestic cable sizes are 1.0 mm² for lighting (6 A MCB), 2.5 mm² for ring finals (32 A MCB), 6 mm² for cookers up to 13 kW, and 10 mm² for showers up to 10.5 kW. All sizes must be verified against BS 7671 Table 4D1A for the specific installation method.
Yes, since harmonisation the UK nominal supply is 230 V +10%/-6% (actual 216-253 V). This is the same nominal as EU countries. Cable sizing voltage drop calculations use 230 V as the reference per BS 7671 Appendix 4.
Amendment 4, expected 2026, will align BS 7671 more closely with IEC 60364 and HD 60364. Changes may include updated installation methods, revised derating tables, and new requirements for EV charging and energy storage. ECalPro will update tables as soon as Amendment 4 is published.