Skip to main content
Cable SizingAlso: volt drop, cable voltage loss, Vd

Voltage Drop

Voltage drop is the reduction in electrical potential along a conductor caused by its impedance when current flows through it. IEC 60364-5-52 Clause 525 limits permissible voltage drop to ensure equipment operates within rated tolerances. It is calculated using the formula Vd equals mV per amp per metre multiplied by design current and cable length.

Detailed Explanation

Every conductor has resistance and, for AC circuits, reactance. When current flows, these impedances cause the voltage at the load terminals to be lower than the supply voltage. This reduction must be controlled because motors may stall, lighting may dim, and electronic equipment may malfunction if the terminal voltage falls too far below rated values. Most standards limit total voltage drop to 3–5% of nominal supply voltage. The mV/A/m method simplifies calculation: manufacturers publish millivolt-drop-per-ampere-per-metre values for each cable size and type, allowing engineers to compute voltage drop as Vd = (mV/A/m × Ib × L) / 1000 for single-phase circuits. For three-phase balanced loads, use the three-phase mV/A/m values from standard tables — these already account for the phase relationship and no additional factor is needed. Long cable runs, high currents, and small conductors increase voltage drop, often forcing selection of a larger cable than the current-carrying capacity alone would require. Power factor also affects voltage drop in AC circuits — highly inductive loads increase the reactive component of impedance, raising the overall drop.

Formula

Vd = (mV/A/m × Ib × L) / 1000

Standard References

StandardClause
IEC 60364-5-52Clause 525
BS 7671:2018Regulation 525.1

Related Terms