Solar PV & Energy Storage
Solar PV supply systems per IEC 60364-7-712 — string sizing, inverter matching, cable and protection design
Configure your PV system and click Calculate
Enter module specs, inverter details, and site conditions
Solar PV cable sizing determines the minimum conductor area for photovoltaic string and array cables that carry DC current from panels to the inverter. IEC 62548 specifies requirements for voltage drop, current-carrying capacity under elevated roof temperatures, and short-circuit protection. PV cables must withstand continuous operation at maximum power point current multiplied by a 1.25 safety factor.
How Solar PV & Energy Storage Works
The solar PV electrical calculator sizes the DC and AC cabling, protection, and inverter connections for photovoltaic array installations.
The calculation determines string current (Isc x 1.25 for NEC 690.8 or Isc x 1.2 for IEC 62548), string voltage range (Voc at minimum temperature to Vmpp at maximum temperature), and array configuration (series modules per string, parallel strings per MPPT). DC cable sizing accounts for the continuous current derating of 125% per NEC Article 690.8(A) and environmental correction factors.
IEC 62548 provides the international design requirements for PV arrays. NEC Article 690 covers solar PV system installations. AS/NZS 5033 defines PV array installation requirements for Australian conditions. Results include string configuration, DC and AC cable sizes, overcurrent protection ratings, inverter sizing ratio, and voltage window verification.
PV System Design Parameters
| Parameter | Requirement | Standard |
|---|---|---|
| String cable sizing | ≥ 1.25 × Isc | IEC 62548 Clause 7 |
| DC voltage limit | ≤ 1500V (utility) / 600V (residential) | IEC 62548 / NEC 690.7 |
| Voltage drop target | ≤ 1–2% (string), ≤ 1% (main DC) | IEC 62548 |
| Inverter AC cable | ≥ 1.25 × max output current | AS/NZS 4777.2 |
| Earth fault detection | Required | IEC 62548 Clause 8 |
Source: IEC 62548, AS/NZS 4777.2, NEC Article 690
Frequently Asked Questions
How do I calculate the maximum PV string voltage?
How do I size DC cables for a solar PV array?
What overcurrent protection is required for PV arrays?
How do I match a PV array to an inverter?
What earthing requirements apply to PV systems?
Related Calculators
Related Guides & Examples
Related FAQ
Standards Reference
- IEC 62548 — PV array design
- NEC Article 690 — Solar PV systems
- AS/NZS 5033 — PV array installation