Worked Example: Earth Fault Loop Impedance Verification for a TN-S System per BS 7671 Chapter 41
Step-by-step earth fault loop impedance verification for a 32 A Type B MCB circuit in a TN-S system. Covers conductor resistance at 20°C, temperature correction to 70°C, Zs calculation, and comparison against BS 7671 Table 41.3 maximum values.
Project Description
This worked example verifies that a final circuit in a TN-S earthing system achieves automatic disconnection of supply within the time required by BS 7671:2018+A3, Regulation 411.3.2.2. The verification centres on calculating the total earth fault loop impedance Zs at the furthest point of the circuit and comparing it against the maximum permitted value from Table 41.3.
Earth fault loop impedance is a critical safety parameter. If Zs is too high, the fault current will be insufficient to trip the protective device within the required time (0.4 s for final circuits up to 63 A), leaving the exposed-conductive-part energised at a dangerous voltage.
Given Data
| Parameter | Value |
|---|---|
| Supply voltage | 230 V single-phase, 50 Hz |
| Earthing system | TN-S (separate neutral and earth conductors from DNO) |
| Protective device | 32 A Type B MCB (BS EN 60898) |
| Line conductor | 6 mm² copper, XLPE insulated (70°C maximum operating temperature) |
| Protective conductor (PE) | 6 mm² copper, same cable as line conductor |
| Cable route length | 25 m (from distribution board to final point) |
| Cable type | Twin + earth, XLPE 70°C rated copper |
| External earth fault loop impedance (Ze) | 0.35 Ω (measured at origin of installation) |
| Conductor operating temperature | 70°C (design maximum under fault conditions) |
| Ambient temperature | 30°C |
The task is to determine whether Zs at the remote end of the circuit is low enough to ensure the 32 A Type B MCB disconnects within 0.4 seconds under an earth fault condition.
Step 1: Determine Conductor Resistance at 20°C
First, we calculate the resistance of the line conductor (R1) and the protective conductor (R2) at the standard reference temperature of 20°C. From BS 7671 Table I1 (Onsite Guide), the resistance per metre of 6 mm² copper conductor at 20°C is:
Resistivity of copper at 20°C: ρ20 = 1.724 × 10&sup-8; Ω·m
For 6 mm² conductor:
r1 = ρ / A = (1.724 × 10&supmin;&sup8;) / (6 × 10&supmin;&sup6;)
r1 = 2.873 × 10&supmin;³ Ω/m
r1 = 3.08 mΩ/m (tabulated value from BS 7671 Table I1)
Since the line and PE conductors are both 6 mm² copper:
r1 = 3.08 mΩ/m (line conductor)
r2 = 3.08 mΩ/m (protective conductor)
(r1 + r2) at 20°C = 3.08 + 3.08 = 6.16 mΩ/m
For 25 m route length:
(R1 + R2)20°C = 6.16 × 25 / 1000
(R1 + R2)20°C = 0.154 Ω
Step 2: Apply Temperature Correction Factor
Conductor resistance increases with temperature. During a fault, the conductor heats rapidly. We must calculate the resistance at the maximum operating temperature to determine the worst-case loop impedance. The correction factor from 20°C to the operating temperature is given by BS 7671 Regulation 411.4.4 and Appendix 14:
Temperature correction factor:
Ct = [1 + α20 × (top − 20)]
Where:
α20 = 0.00393 /°C (temperature coefficient for copper at 20°C)
top = 70°C (maximum conductor operating temperature for XLPE 70°C cable)
Ct = 1 + 0.00393 × (70 − 20)
Ct = 1 + 0.00393 × 50
Ct = 1 + 0.1965
Ct = 1.20
This factor of 1.20 means the conductor resistance at 70°C is 20% higher than at 20°C. This is a significant increase and must not be neglected.
Step 3: Calculate (R1+R2) at Operating Temperature
Apply the temperature correction factor to the 20°C resistance:
(R1 + R2)70°C = (R1 + R2)20°C × Ct
(R1 + R2)70°C = 0.154 × 1.20
(R1 + R2)70°C = 0.185 Ω
This represents the combined resistance of the line and protective conductors over the 25 m route at the worst-case operating temperature.
Step 4: Calculate Total Earth Fault Loop Impedance (Zs)
The total earth fault loop impedance is the sum of the external earth fault loop impedance (Ze) provided by the electricity distributor and the internal circuit impedance (R1 + R2):
Zs = Ze + (R1 + R2)70°C — (Eq. 1, BS 7671 Reg 411.4.5)
Zs = 0.35 + 0.185
Zs = 0.535 Ω
Step 5: Compare Against BS 7671 Table 41.3
From BS 7671 Table 41.3 — Maximum earth fault loop impedance (Zs) for Type B MCBs to BS EN 60898, the maximum permitted Zs for a 32 A Type B MCB to achieve disconnection within 0.4 seconds is:
| MCB Rating (A) | Type B Zs max (Ω) | Type C Zs max (Ω) | Type D Zs max (Ω) |
|---|---|---|---|
| 6 | 7.67 | 3.83 | 1.92 |
| 10 | 4.60 | 2.30 | 1.15 |
| 16 | 2.87 | 1.44 | 0.72 |
| 20 | 2.30 | 1.15 | 0.57 |
| 25 | 1.84 | 0.92 | 0.46 |
| 32 | 1.44 | 0.72 | 0.36 |
| 40 | 1.15 | 0.57 | 0.29 |
| 50 | 0.92 | 0.46 | 0.23 |
For a 32 A Type B MCB:
Zs (max) = 1.44 Ω (from Table 41.3)
Our calculated Zs = 0.535 Ω
0.535 Ω < 1.44 Ω → COMPLIANT
The calculated Zs of 0.535 Ω is well within the maximum permitted value of 1.44 Ω. The circuit will achieve automatic disconnection within 0.4 seconds as required by Regulation 411.3.2.2.
Step 6: Verify Prospective Fault Current
As a supplementary check, calculate the prospective earth fault current to confirm it is sufficient to trip the MCB within the required time:
If = U0 / Zs — (Eq. 2)
If = 230 / 0.535
If = 430 A
For a 32 A Type B MCB, the magnetic trip threshold is 5 × In = 5 × 32 = 160 A. Our fault current of 430 A is 2.7 times the magnetic trip threshold, confirming instantaneous tripping (typically within 10–20 ms, well within the 0.4 s requirement).
Fault current ratio: If / In = 430 / 32 = 13.4
Type B magnetic trip range: 3× to 5× In
Lower threshold: 3 × 32 = 96 A
Upper threshold: 5 × 32 = 160 A
430 A > 160 A → guaranteed instantaneous magnetic trip
Result Summary
| Parameter | Requirement | Calculated Value | Status |
|---|---|---|---|
| (R1+R2) at 20°C | — | 0.154 Ω | — |
| Temperature correction factor | — | 1.20 (to 70°C) | — |
| (R1+R2) at 70°C | — | 0.185 Ω | — |
| Ze | — | 0.35 Ω (measured) | — |
| Zs total | ≤ 1.44 Ω (Table 41.3) | 0.535 Ω | ✓ PASS |
| Prospective fault current | ≥ 160 A (5 × In) | 430 A | ✓ PASS |
| Disconnection time | ≤ 0.4 s | < 0.02 s (instantaneous) | ✓ PASS |
The circuit is compliant with BS 7671 Chapter 41 for automatic disconnection of supply in a TN-S system. The earth fault loop impedance of 0.535 Ω provides a substantial margin below the maximum of 1.44 Ω, ensuring reliable protective device operation even with supply impedance variations.
Key References
- BS 7671:2018+A3, Regulation 411.3.2.2 — Automatic disconnection for TN systems (0.4 s for final circuits ≤ 63 A)
- BS 7671:2018+A3, Table 41.3 — Maximum Zs values for MCBs to BS EN 60898
- BS 7671:2018+A3, Regulation 411.4.5 — Earth fault loop impedance formula
- BS 7671:2018+A3, Appendix 14 — Temperature correction for conductor resistance
- IET On-Site Guide, Table I1 — Conductor resistance per metre at 20°C
- BS EN 60898-1 — MCB characteristics (Type B: 3–5 × In)
Try It Yourself
Use the ECalPro Cable Sizing Calculator to verify earth fault loop impedance for your own circuits. Select BS 7671 as the standard, enter your Ze value and cable details, and the calculator will automatically check Zs against Table 41.3 — including temperature correction, the 80% rule, and full intermediate step reporting.
Try the Cable Sizing Calculator
Put this methodology into practice. Calculate results with full standard clause references — free, no sign-up required.
Or embed this calculator on your siteFrequently Asked Questions
Related Resources
Cable Sizing Calculator
Verify earth fault loop impedance with automatic Table 41.3 compliance checking.
Read moreBS 7671 Standards Overview
Reference guide for BS 7671 protective device tables and earthing requirements.
Read moreEarthing Systems Explained
Understand the differences between TN-S, TN-C-S, and TT earthing systems.
Read more