Skip to main content

Worked Example: Sizing a Power Factor Correction Capacitor Bank for an Industrial Site

Step-by-step calculation for sizing a power factor correction capacitor bank to improve power factor from 0.72 to 0.95 lagging at a 500 kVA industrial site. Covers reactive power calculation, capacitor bank selection, cable sizing, fuse rating, and harmonic considerations.

IEC 61439 / AS/NZS 300012 min readUpdated March 6, 2026
Share:

Project Description

An industrial manufacturing facility is experiencing power factor penalties from their electricity retailer. The measured power factor is 0.72 lagging, well below the target of 0.95 lagging typically required to avoid penalty charges. This worked example sizes a capacitor bank to correct the power factor, then determines the cable and fuse ratings for the capacitor bank connection.

Poor power factor increases apparent power (kVA) drawn from the supply, resulting in higher current for the same real power output. This wastes transformer and cable capacity, increases losses, and triggers utility penalty charges — typically 1–3% of the electricity bill per 0.01 below the target power factor.

Given Data

ParameterValue
Supply voltage400 V, three-phase, 50 Hz
Maximum demand500 kVA (measured)
Existing power factor0.72 lagging
Target power factor0.95 lagging
Cable from MDB to PFC panel15 m (short run)
Installation methodMulticore on cable tray, 3 grouped circuits
Cable typeXLPE 90°C copper
Ambient temperature35°C
Harmonic contentTHDv < 5% (linear loads dominate)

Step 1: Calculate Real Power (kW)

The real (active) power drawn by the facility:

P = S × cosφ1  — (Eq. 1)

Where:
  S = 500 kVA (apparent power)
  cosφ1 = 0.72 (existing power factor)

P = 500 × 0.72
P = 360 kW

This real power remains constant — the loads still consume 360 kW regardless of power factor correction. Only the reactive component changes.

Step 2: Calculate Existing and Target Reactive Power

Calculate the reactive power at the existing and target power factors:

Existing reactive power:
  Q1 = P × tanφ1  — (Eq. 2)

  φ1 = arccos(0.72) = 43.95°
  tanφ1 = tan(43.95°) = 0.9640

  Q1 = 360 × 0.9640
  Q1 = 347.0 kVAr

Target reactive power:
  Q2 = P × tanφ2  — (Eq. 3)

  φ2 = arccos(0.95) = 18.19°
  tanφ2 = tan(18.19°) = 0.3287

  Q2 = 360 × 0.3287
  Q2 = 118.3 kVAr

Step 3: Determine Required Capacitor Bank Rating

The required capacitor bank must supply the difference between the existing and target reactive power:

Qc = Q1 − Q2  — (Eq. 4)

Qc = 347.0 − 118.3
Qc = 228.7 kVAr

Select the next standard capacitor bank size. Standard ratings are typically available in 25, 50, 75, 100, 125, 150, 200, 250, 300 kVAr increments. For automatic stepped banks, common step sizes are 12.5, 25, or 50 kVAr per step.

Selected capacitor bank: 225 kVAr (automatic, 9 × 25 kVAr steps)

Verify achieved power factor with 225 kVAr:
  Qcorrected = Q1 − Qc(actual) = 347.0 − 225 = 122.0 kVAr

  Scorrected = √(P² + Qcorrected²)
  Scorrected = √(360² + 122²)
  Scorrected = √(129,600 + 14,884)
  Scorrected = √144,484
  Scorrected = 380.1 kVA

  PFcorrected = P / Scorrected = 360 / 380.1 = 0.947

  0.947 ≈ 0.95 ✓ (close enough to target)
Note: An automatic stepped bank is preferred over a fixed bank for sites with variable load. Fixed banks risk over-correction to a leading power factor during low-load periods, which can cause voltage rise and resonance issues. The controller switches steps in/out to maintain the target power factor as load varies.

Step 4: Calculate Capacitor Bank Current

The full-load current drawn by the capacitor bank at rated output:

Ic = Qc / (√3 × V)  — (Eq. 5)

Ic = 225,000 / (√3 × 400)
Ic = 225,000 / 692.8
Ic = 324.8 A

This is the steady-state capacitor current. However, capacitors experience transient inrush currents during switching that can reach 20–200 times the rated current for a few milliseconds. The cable and fuse must be rated for the steady-state current with an overrating factor.

Step 5: Size the Protective Device (Fuse)

Per IEC 61439-1 and capacitor manufacturer recommendations, the protective device for a capacitor bank must be rated at 1.36 to 1.50 times the capacitor rated current to account for:

  • Capacitor tolerance (+5% to +15% capacitance per IEC 60831)
  • Harmonic currents (even with low THD)
  • Voltage variations (+10%)
Minimum fuse rating:
  Ifuse = 1.43 × Ic  — (Eq. 6, using 1.43 as mid-range factor)

  Ifuse = 1.43 × 324.8
  Ifuse = 464.5 A

Select next standard fuse rating: 500 A gG (general purpose HRC fuse)

Verify: 500 A ≥ 464.5 A  ✓
Note: Some designers use a factor of 1.50 for additional margin, which would give 487.2 A — still rounded to a 500 A fuse. The 1.36 minimum comes from the combined effect of +10% voltage (current rises proportionally) and +15% capacitance tolerance and 5% harmonics: 1.10 × 1.15 × 1.05 ≈ 1.33. The factor of 1.43 includes an additional safety margin.

Step 6: Size the Cable

The cable must carry the overrated current continuously. Per AS/NZS 3008.1.1:2017 and IEC 60364-5-52, the cable current-carrying capacity after derating must be at least equal to the fuse rating:

Required cable capacity:
  Iz ≥ Ifuse / (k1 × k2)  — (Eq. 7)

Derating factors:
  k1 (ambient 35°C, 90°C XLPE cable):
    Reference ambient = 30°C (IEC 60364)
    From IEC 60364-5-52 Table B.52.14: k1 = 0.96

  k2 (3 grouped circuits on tray):
    From IEC 60364-5-52 Table B.52.17: k2 = 0.82

  ktotal = 0.96 × 0.82 = 0.787

  Iz ≥ 500 / 0.787
  Iz ≥ 635.3 A

From IEC 60364-5-52, Table B.52.2 for multicore XLPE copper on perforated tray (Installation Method E):

Cable Size (mm²)Current Rating (A)Result
120539✗ Too low
150607✗ Too low
185679✓ Passes (679 ≥ 635.3)
240773✓ Passes with margin
Selected cable: 185 mm² XLPE copper, rated 679 A

Verify: 679 A × 0.787 = 534.4 A > 500 A (fuse rating)  ✓

Wait — 534.4 A > 500 A, so the cable is protected by the fuse  ✓

Also verify the derated capacity exceeds the actual capacitor current:
  534.4 A > 324.8 A (capacitor rated current)  ✓

Step 7: Verify Voltage Drop

For completeness, check the voltage drop on the 15 m cable run. For capacitive loads the reactive voltage drop component actually raises the voltage, but we conservatively check the resistive component:

From cable data, 185 mm² XLPE copper:
  mV/A·m (resistive) = 0.210

ΔV = mV/A·m × Ic × L / 1000  — (Eq. 8)
ΔV = 0.210 × 324.8 × 15 / 1000
ΔV = 1.023 V

ΔV% = 1.023 / 400 × 100 = 0.26%

The voltage drop of 0.26% is negligible for a 15 m run. This is not a governing factor.

Result Summary

ParameterBefore CorrectionAfter Correction
Power factor0.72 lagging0.947 lagging
Apparent power (kVA)500 kVA380.1 kVA
Reactive power (kVAr)347.0 kVAr122.0 kVAr
Real power (kW)360 kW360 kW (unchanged)
Supply current722 A549 A (−24%)
Equipment SelectionValue
Capacitor bank225 kVAr automatic stepped (9 × 25 kVAr)
Fuse500 A gG HRC fuse
Cable185 mm² XLPE copper (multicore on tray)
Voltage drop (15 m)0.26% ✓ PASS

The 225 kVAr automatic capacitor bank corrects the power factor from 0.72 to 0.947, freeing 120 kVA of transformer capacity and reducing supply current by 24%. The annual savings from avoided penalty charges and reduced losses typically pay back the capacitor bank installation cost within 12–18 months.

Key References

  • IEC 61439-1 — Low-voltage switchgear and controlgear assemblies, general rules
  • IEC 60831-1 — Shunt power capacitors for AC power systems ≤ 1 kV, tolerances and ratings
  • AS/NZS 3000:2018, Clause 4.7 — Requirements for capacitor installations
  • IEC 60364-5-52, Tables B.52.2, B.52.14, B.52.17 — Cable current ratings and derating factors
  • AS/NZS 3008.1.1:2017 — Cable sizing and current-carrying capacities
  • Schneider Electric Guide, Chapter K — Power factor correction design methodology

Try It Yourself

Use the ECalPro Cable Sizing Calculator to verify cable and fuse ratings for your power factor correction installation. Enter the capacitor bank current with the 1.43× overrating factor applied, and the calculator will determine the correct cable size with all derating factors and voltage drop verification.

Try the Cable Sizing Calculator

Put this methodology into practice. Calculate results with full standard clause references — free, no sign-up required.

Or embed this calculator on your site
Calculate Cable Sizing

Frequently Asked Questions

It is generally not recommended to correct to unity or beyond. A leading power factor (over-correction) during low-load periods can cause voltage rise on the supply bus, excite resonance with system inductance, and may incur leading power factor penalties from some utilities. A target of 0.95-0.98 lagging provides optimal correction without these risks. Automatic stepped banks manage this by adjusting capacitor steps to match the actual load.
Capacitors have decreasing impedance at higher frequencies, which means they can amplify harmonic currents. If the site has significant harmonic content (THDv > 5% or THDi > 20%), detuned reactors (typically 7% or 14% detuning) must be added in series with the capacitors. Without detuning, harmonic resonance can occur between the capacitor bank and transformer inductance, causing capacitor failure and dangerous overcurrents.
Capacitors can draw more than their rated current due to three compounding factors: voltage tolerance (+10% per IEC), capacitance manufacturing tolerance (+5% to +15% per IEC 60831), and harmonic currents that are amplified by the capacitor. The combined effect means actual current can be up to 1.43 times the nominal rated current. The fuse and cable must be sized for this worst-case continuous current, not just the nameplate rating.

Related Resources