Skip to main content

Voltage Drop Calculator

Voltage drop analysis per AS/NZS 3008.1.1:2017. Select a cable size and verify voltage drop compliance.

Circuit Parameters
Cable Selection
Voltage Drop Limits

No results yet. Enter parameters and click Calculate.

Voltage drop is the reduction in electrical potential along a conductor caused by its impedance when current flows through it. IEC 60364-5-52 Clause 525 limits permissible voltage drop to ensure equipment operates within rated tolerances. It is calculated using the formula Vd equals mV per amp per metre multiplied by design current and cable length.

How to Calculate Voltage Drop

  1. 1
    Gather circuit parametersRecord the design current in amperes, cable length in metres, supply voltage, number of phases, and the power factor of the load. These are the inputs required for the voltage drop formula.
  2. 2
    Find the mV/A/m valueLook up the millivolt drop per ampere per metre from the cable manufacturer's data or standard tables. This value depends on conductor size, material, and whether the circuit is AC or DC.[IEC 60364-5-52 Clause 525]
  3. 3
    Apply the voltage drop formulaCalculate Vd = (mV/A/m x Ib x L) / 1000 for single-phase, using the single-phase mV/A/m value. For three-phase balanced loads, use the three-phase mV/A/m value with the same formula (Vd = mV/A/m x Ib x L / 1000) — these values already account for the phase relationship. The result is in volts.
  4. 4
    Convert to percentageExpress the voltage drop as a percentage of the nominal supply voltage: Vd% = (Vd / Vnom) x 100. This allows direct comparison against the allowable limit for the installation.
  5. 5
    Compare against allowable limitCheck the result against the applicable standard limit. BS 7671 and IEC 60364 typically allow 5% total, while NEC recommends 3% for branch circuits and 5% total for feeder plus branch combined.[BS 7671 Regulation 525.1]

How Voltage Drop Works

The voltage drop calculator determines the voltage loss along a cable run and verifies it falls within the permissible limits defined by the applicable standard.

Voltage drop is calculated using the formula Vd = (mV/A/m x Ib x L) / 1000, where mV/A/m is the millivolt drop per ampere per metre (from cable manufacturer data or standard tables), Ib is the design current in amperes, and L is the one-way cable route length in metres. For three-phase circuits, the formula uses three-phase mV/A/m values directly; for single-phase circuits, the single-phase mV/A/m values apply.

The mV/A/m values account for both resistive and reactive components of the cable impedance. At higher power factors, the resistive component dominates, while at lower power factors the reactive component becomes significant — particularly for larger conductor sizes. AS/NZS 3008.1.1:2017 provides these values in Tables 35-42 for various conductor and insulation types.

Each standard specifies different permissible limits. BS 7671:2018+A2 Regulation 525.1 recommends a maximum of 3% for lighting circuits and 5% for other circuits from the origin of the installation. IEC 60364-5-52 Clause 525 provides similar guidance. NEC/NFPA 70:2023 Section 210.19(A) Informational Note No. 4 recommends 3% for branch circuits and 5% total (feeder plus branch circuit), though these are advisory rather than mandatory. AS/NZS 3008.1.1:2017 Clause 4.5 limits the total voltage drop to 5% from the point of supply.

Where voltage drop exceeds limits, the calculator recommends the next cable size up. The results display the voltage at the load end, percentage drop, comparison against the standard limit, and a breakdown of resistive versus reactive voltage drop components. For long runs or heavily loaded circuits, voltage drop often governs cable selection over current carrying capacity alone.

Maximum Permissible Voltage Drop by Standard

StandardLightingOther CircuitsTotal Limit
BS 76713%5%From origin
IEC 603644%5%From distribution board
NEC (NFPA 70)3% (recommended)3% branch5% total
AS/NZS 30085%5%From point of supply

Source BS 7671 Appendix 12, IEC 60364-5-52 Clause 525, NEC 210.19(A) Note 4, AS/NZS 3008.1.1 Clause 4.5

Frequently Asked Questions

What is the maximum voltage drop allowed per BS 7671?
BS 7671:2018+A2 Regulation 525.1 and Appendix 12 recommend maximum voltage drop limits of 3% for lighting circuits and 5% for other circuits, measured from the origin of the installation to the load terminals. These limits apply to the installation wiring only and do not include the voltage drop in the distributor's supply cable. For public supply installations, a total of 3% or 5% respectively from the meter is the guideline.
How do you calculate voltage drop using the mV/A/m method?
The mV/A/m method uses tabulated values from standard tables (AS/NZS 3008.1.1 Table 35-42, or BS 7671 Table 4Ab-4Db). Voltage drop in millivolts is calculated as VD = (mV/A/m) x Ib x L / 1000 for single-phase, and VD = (mV/A/m) x Ib x L x 0.577 / 1000 for three-phase circuits, where Ib is the design current in amperes and L is the cable route length in metres. The tabulated mV/A/m value already accounts for both conductor resistance and reactance at the given power factor.
What voltage drop limit does AS/NZS 3008.1.1 specify?
AS/NZS 3008.1.1:2017 Clause 4.5 states that the total voltage drop from the point of supply to any point in the installation shall not exceed 5% of the nominal supply voltage. For a 230V single-phase supply this means a maximum drop of 11.5V, and for a 400V three-phase supply the limit is 20V line-to-line. Subcircuit limits may be more restrictive per AS/NZS 3000:2018 Table C7.
How does power factor affect voltage drop calculations?
Power factor significantly affects voltage drop because cables have both resistance (R) and reactance (X) components. The effective impedance per unit length is Zeff = R cos(phi) + X sin(phi), where phi is the phase angle. At low power factors (e.g., 0.8 lagging for motor loads), the reactive component contribution increases, and for larger cables where X becomes proportionally significant, the voltage drop can be substantially higher than what resistance alone would predict. NEC Chapter 9 Table 9 provides both R and X values for this purpose.
What is the NEC voltage drop recommendation?
Unlike BS 7671 and AS/NZS 3008, the NEC does not mandate a specific voltage drop limit as a code requirement. However, NEC 210.19(A) Informational Note No. 4 and NEC 215.2(A) Informational Note No. 2 recommend that voltage drop for branch circuits should not exceed 3%, and the total drop from feeder plus branch circuit should not exceed 5%. While informational notes are not enforceable, most jurisdictions and engineers treat these as design targets.
How do you account for cable length in a voltage drop calculation?
Cable length used in voltage drop calculations must be the actual route length of the cable, not the straight-line distance. This includes vertical risers, horizontal runs, bends, and spare length at termination points. For single-phase circuits, the total conductor length is twice the route length (active + neutral). For three-phase balanced loads, the route length is used directly with the three-phase mV/A/m values, since neutral current is zero and only line conductors contribute to voltage drop.
calc.faq.voltage-drop.q7
calc.faq.voltage-drop.a7
calc.faq.voltage-drop.q8
calc.faq.voltage-drop.a8
calc.faq.voltage-drop.q9
calc.faq.voltage-drop.a9
calc.faq.voltage-drop.q10
calc.faq.voltage-drop.a10
calc.faq.voltage-drop.q11
calc.faq.voltage-drop.a11

Standard Guides

Related Calculators

Related Guides & Examples

Key Terms

Related FAQs

Standards Reference

  • AS/NZS 3008.1.1:2017 — Clause 4.5, Tables 35-42
  • BS 7671:2018+A2 — Regulation 525.1, Appendix 12
  • IEC 60364-5-52 — Clause 525
  • NEC/NFPA 70:2023 — Section 210.19(A), Chapter 9 Table 9